Troubleshooting (continued)
Problem
Check
Action
Heat-on time too
short.
— anticipator setting. (See Fig. 6.)
Increase anticipator setting by 0.05 Observe
heating system operation.
Heat-on time too
long.
— anticipator setting. (See Fig. 6.)
Decrease anticipator setting by 0.05.
Observe heating system operation.
No cooling.
— system switch. May be in OFF or
HEAT position.
Move switch to COOL position.
— fuse or circuit breaker.
If fuse is blown or breaker tripped, replace or
reset.
— condensor switch position.
Located outdoors and may be
turned off.
Move to ON position.
— Y, G, RC thermostat connections.
Turn off power to cooling system. Check for
correct terminal hookups. Repair any frayed
or broken wires. Firmly tighten all terminal
screws.
(continued)