Honeywell CR7075 Product Data Download Page 6

CR7075 TWO-STAGE LIGHTING CONTROLLER

63-2180—1

6

OPERATION

In many applications, outdoor cosmetic lighting and parking lot 

lighting activate either simultaneously or with independent 

controllers by means of a time of day clock with a photocell 

override. The photocell override turns on lighting during 

abnormal weather conditions (such as overcast sky).

NOTE: Overriding the time of day feature with a photocell 

controller provides optimum lighting control, but does 

not maximize energy savings.

The Two-Stage Lighting Controller overcomes the energy 

saving and calibration deficiencies mentioned above. Each 

stage functions separately to control the on/off times of the 

outdoor cosmetic and parking lot lighting.

NOTE: At the time of installation, one can operationally 

check the photocell by covering the lens with their 

hand from a distance of a few inches.

IMPORTANT

Calibration is accomplished by setting light level 

potentiometers to turn the lights on at the user-

determined ambient light level.

After a period of time, the photocell characteristics can 

change due to accumulation of airborne particles on the lens. 

Certain environmental conditions (such as high humidity 

levels) can accelerate this accumulation. This can require 

changing the light level potentiometer settings. (Refer to the 

Checkout section for calibration instructions.)

Typical Sequencing

The following is an example of a typical on/off sequence.

NOTES:

Refer to Fig. 8 for sequence of operation.

For 24-hour stores, lights simply remain on unless 

sufficient light exists to warrant their shut-off. As 

operation in such an arrangement depends only 

on the photocell, TOD override need only operate 

on a manual basis.

Typical Evening Start-up

As ambient light level decreases, cosmetic lighting (stage 1) 

turns on first. As ambient light level decreases further, parking 

lot lights (stage 2) turn on. Both turn off after the business 

closes using a separate time of day clock. If desired, 

independent TOD override for each stage allows turning off 

one stage at a different time than the other.

Fig. 8. Sequence of operation.

Typical Morning Start-up

Both cosmetic and parking lot lighting turn on with the time of 

day clock. If desired, independent TOD override for each 

stage allows turning on one stage at a different time than the 

other. As ambient light level increases, the parking lot lights 

(stage 2) turn off first and the cosmetic lighting (stage 1) turns 

off last as the ambient light level increases further.

LIGHT

INTENSITY

TIME

DELAY

DECREASING LIGHTING CONDITIONS

(SUNSET)

STAGE 2

SETPOINT

(ADJUSTABLE)

HIGH

LOW

M1045

STAGE 1 - ON

STAGE 2 - ON

STAGE 1

SETPOINT

(ADJUSTABLE)

TIME

DELAY

TIME

Summary of Contents for CR7075

Page 1: ...de outdoor cosmetic and parking lot lighting in fast food restaurants retail establishments supermarkets banks and lighted billboards FEATURES Light intensity threshold levels field adjustable by user Independent Time of Day TOD override inputs Optimum start stop of lighting loads Tamper proof cover LED annunciation for power on and relay state Wide ambient temperature range Up to 1000 foot separa...

Page 2: ...s Spain Taiwan United Kingdom U S A SPECIFICATIONS Model CR7075A1000 Two Stage Lighting Controller Dimensions See Fig 1 Electrical Ratings Voltage Input 120 240 Vac 50 60 Hz Power Consumption 5 VA Maximum Switching Single Pole Double Throw SPDT Sensor Cadmium sulfide photocell C7057A1000 1000 ft maximum distance between sensor and controller shielded wire not required Indicators LED annunciation p...

Page 3: ...ulfide photocell sensor C7057A1000 supplied with this controller so that the lens is exposed to full daylight See Fig 2 NOTES Select an area which will not become shaded Mount only with light entrance facing horizontally Avoid overexposure to direct east west sunlight Fig 2 Vertical mounting configuration Mounting IMPORTANT Mount the photocell sensor to the top of a watertight outdoor FS junction ...

Page 4: ...es 60 control of two separate lighting banks based on user determined ambient light intensity level via a single sensor Set point indexing is relative The SET RUN switch removes the integrating time delay short cycle protection circuitry in the SET position In the RUN position normal operation there is a 30 10 second time delay for both light fall and light rise initiated relay action Two independ...

Page 5: ...RLOAD PROTECTION AS REQUIRED WHEN SWITCHING 24 VOLT LOADS MAKE SURE BARRIER IS INSTALLED L1 HOT L2 1 CAUTION ONE POWER SOURCE ONLY LINE POWER OUTPUT 1 OUTPUT 2 120 VAC 240 VAC COM N0 COM NC N0 COM NC M1088 LIGHT LEVEL SET RUN POWER STAGE 1 STAGE 2 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 T O D 1 T O D 2 SENSOR 1 2 3 4 5 T2 WHITE BLACK L1 L2 LOAD 2 LOAD 1 S7005 T3 T4 T5 1 1 POWER SUPPLY PROVIDE DI...

Page 6: ...can require changing the light level potentiometer settings Refer to the Checkout section for calibration instructions Typical Sequencing The following is an example of a typical on off sequence NOTES Refer to Fig 8 for sequence of operation For 24 hour stores lights simply remain on unless sufficient light exists to warrant their shut off As operation in such an arrangement depends only on the ph...

Page 7: ...ear the light conditions required for switching the equipment Attempting calibration at extreme light conditions can cause switching to be unachievable 1 At the desired outdoor light level place SET RUN switch to the SET position 2 Slowly rotate stage 1 light level potentiometer counter clockwise until the stage 1 LED lights 3 Stage 1 is now calibrated to the light level existing at the sensor and...

Page 8: ...ational Honeywell Europe Honeywell Latin American Honeywell Honeywell Limited Honeywell Limitée Home and Building Control S A Region 1985 Douglas Drive North 35 Dynamic Drive Honeywell Building 3 Avenue du Bourget 480 Sawgrass Corporate Parkway Golden Valley MN 55422 Scarborough Ontario 17 Changi Business Park Central 1 1140 Brussels Suite 200 M1V 4Z9 Singapore 486073 Belgium Sunrise FL 33325 ...

Reviews: