43
Component
Type
Comments
EPMs
while its ETH2 port is left disconnected. Before it is inserted into its
slot, the 100x rotary switch on the EPM board must be set to indicate
the type of network connectivity in use. This is done by setting it to
position 4. The IP address of the EPM is assigned by the UOC CPM
based on the module number set on the 10X and 1x rotary switches.
These switches must also be set before the EPM is inserted into its
slot.
Unmanaged
Switches
900 I/O racks with EPM gateways have been qualified to
communicate with UOC through unmanaged switches. EPMs may not
be connected through managed switches.
Stratix
Switches
EIP I/O, devices and PLCs may be connected to UOC through
qualified, Stratix managed switches. For further information on how to
deploy and configure Stratix switches, see
EtherNet IP User's Guide_
EPDOC-X399-en-510A.pdf
.
Following section provides information about installing racks, EPM,
power supply and so on.
Table 4-1: Reference for installing racks, EPM, power supply and so on
Components
Reference section
Racks
For information about options and types of racks, see the sections
and
. For information about installing
Racks, see the section
EPM
For information about installing EPM, see the section
.
Power Supply
For information about connecting to AC or DC power supply, see
the section
.
Configuration
For information about configuration, refer to the Software
Configuration Guide.
Environmental
For information about environmental consideration to be taken
care, see the section
.
Hardware configuration of UOC-CPM
For more information refer to the UOC User’s Guide (PLC to UOC
conversion).
Summary of Contents for ControlEdge 900 platform
Page 6: ...6 Contents ...
Page 12: ...12 Chapter 1 About this guide ...
Page 52: ...52 ...
Page 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Page 59: ...59 One Slot Rack ...
Page 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Page 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Page 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Page 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Page 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Page 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Page 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Page 222: ...Appendix A Installing RTP 222 ...
Page 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...