Honeywell ComfortPoint Open XFL5 Mounting Instructions Download Page 2

XFL5 HARDWARE MIGRATION ADAPTER

MU1B-0074 IE10 R0518

2

REMOVING XFL5xx I/O MODULES FROM XSL513/XSL514 
TERMINAL BLOCKS

1.

Disconnect the power from the XSL513/XSL514 ter-
minal blocks.

2.

Unlock the safety latch(es) by moving the slider to the 
right on the terminal blocks as shown in the following 
figure.

3.

Make a note of the XFL5xx I/O module type and the 
location.

4.

Remove the electronics module from the terminal 
block (or manual terminal disconnect module) by 
pushing a screwdriver between the electronics mod-
ule and the spring clip on the terminal block (or man-
ual terminal disconnect module).

5.

Unlock the spring clip by lightly bending upwards 
with the screwdriver.

6.

Open the plastic cover on the XFL5xx I/O module and 
make a note of the module address which is set on 
the rotary switch if applicable. 

7.

Remove all safety latches present at the top of the 
terminal blocks in the following sequence:
a. Rotate the safety latch in anti-clockwise direction 

as shown in step ‘a’ and ‘b’. 

b.

c.

Remove the safety latch.

INSTALLATION

WARNING

Electrical Shock Hazard.

Can cause severe injury, death or 

property damage.

Disconnect the power supply before beginning 
installation to prevent electrical shock and 
equipment damage. More than one power supply 
may have to be disconnected.

When Installing This Product…

1.

Read these instructions carefully. Failure to follow 
them could damage the product or cause a hazard-
ous condition.

2.

Check the ratings given in the instructions and 
marked on the product to make sure the product is 
suitable for your application.

3.

Installer must be a trained, experienced service 
technician.

4.

After installation is complete, check out the product 
operation as provided in these instructions.

5.

Be sure wiring complies with all applicable codes, 
ordinances and regulations.

on terminal blocks

on XSL512

Safety latch

Summary of Contents for ComfortPoint Open XFL5

Page 1: ...egamenti a 230VCA devono essere eseguiti da personale qualificato S Denna instruktion skall förvaras tillsammans med regler eller anläggningsdokumentationen Elektrisk anslutning med 230 VAC får endast utföras av behörig personal DK Opbevar denne vejledning sammen med regler eller med anlægsdokumentationen Elektrisk tilslutning for 230 VAC bør kun foretages af autoriserede personer N Denne veiledni...

Page 2: ...ve all safety latches present at the top of the terminal blocks in the following sequence a Rotate the safety latch in anti clockwise direction as shown in step a and b b c Remove the safety latch INSTALLATION WARNING Electrical Shock Hazard Can cause severe injury death or property damage Disconnect the power supply before beginning installation to prevent electrical shock and equipment damage Mo...

Page 3: ...ht and width increases by 29mm and 15mm respec tively ALL DIMENSIONS ARE IN MM 1 Refer to the notes See step 6 of the Removing XFL5xx I O Modules from XSL513 XSL514 terminal blocks section on page 2 for the module address of the XFL5xx I O module and adjust the rotary dial on the XFL5 Hardware Migration Adapter to set the address 2 Install the new safety latches between each terminal block as show...

Page 4: ... shown in Fig 2 Type A Safety Latch If the XSL512 Manual Terminal Disconnect Module is installed it is recom mended that you use a screwdriver or similar for locking as shown in Fig 3 Type B Safety Latch Fig 2 Type A safety latch Fig 3 Type B safety latch 5 Insert the XF8xx XFR8xx I O module on the XFL5 Hardware Migration Adapter 6 Make sure that the T shape of the XF8xx XFR8xx I O module is align...

Reviews: