CPO-PC400-W/CPO-PC400-UW HVAC CONTROLLER
EN0B-0085 IE10 R0420
8
Connection to Buses
NOTES:
—
The communication rate across each commu
-
nication interface is dependent upon the given
communication protocol.
—
*Not more than one channel can be configured
as C-Bus channel.
—
**Not more than one channel can be configured
as M-Bus channel.
—
**The CPO-PC400-W/CPO-PC400-UW con
-
troller can function as an M-Bus Master. It uses
a standard level converter (e.g. PW60) to con
-
nect to the M-Bus devices.
Communication Baud Rates
—
The country code for the CPO-PC400-W is con
-
figurable to comply with local country regula
-
tions.
Connection to Panel Buses
The CPO-PC400-W/CPO-PC400-UW can communicate
with various Panel Bus I/O modules. See "Connection to
Table 12. Connection to Buses
Protocols
Max. No. of
Devices per
Channel
R
S4
85
-1
R
S4
85
-2
R
S4
85
-3
R
S4
85
-4
Panel Bus
16
Yes
Yes
Yes
Yes
CP-IO Bus
16
No
No
No
Yes
Field Bus
31
Yes
Yes
Yes
No
MSTP
30
Yes
Yes
Yes
No
Modbus
30
Yes
Yes
Yes
No
M-Bus**
60
Yes**
Yes**
Yes**
No
C-Bus*
30
Yes*
Yes*
Yes*
No
Table 13. Communication Baud Rates
Ethernet
10/100 Mbit/s, RJ45
BACnet MSTP
9.6, 19.2, 38.4, 76.8, 115.2 Kbps
Modbus
0.3 to 115.2 Kbps
Panel Bus
115.2 Kbps
CP-IO Bus
56.7 Kbps
C-Bus
9.6, 38.4, and 76.8 Kbps
M-Bus
0.3 to 19.2 Kbps
Field Bus
38.4 Kbps
Wi-Fi
802.11b: up to 11 Mbps
802.11a/g: up to 54 Mbps
802.11n: up to 150 Mbps
802.11ac: up to 433 Mbps
Bluetooth
BR: up to 1Mbps
EDR: up to 3Mbps
BLE: up to 1Mbps
MMI Port
5Vdc power output and RS485
Table 14. Panel I/O modules
Name
Descripti
on
In
pu
t
O
ut
pu
t
M
an
ua
l O
ve
rr
id
es
St
at
us
L
E
D
s
(a
)
XF821
Pluggable
AI module
8
–
–
–
XF822
Pluggable
AO
module
–
8
–
8
XFR822
Pluggable
AO
module
–
8
8
8
XF823
Pluggable
BI module
12
–
–
12