Honeywell CM921 Product Specification Sheet Download Page 5

CM921

 CHRONOTHERM

 

 

 

5

EN0H 8557 UK07 R0 09/06 

DIMENSIONS 

 

 

Parameter 

Installer Set-
Up Number / 
Abbreviation 
(Press  + or - 
keys to 
select) 

Factory Setting 

 

Optional Setting 

 

Category 2 Parameters – System Settings (press the 

>

 button to access this category) 

  

Display 

Description 

Display 

Description 

Minimum boiler ON 
Time  

1:Ot 

1 minute minimum ON time 

2 to 5 

Selection of 2,3,4 or 5 minutes minimum 
ON time 

Cycle Rate 

2:Cr 

6 cycles per hour (cph) 

3, 9 or12 

Selection of 3,9 or 12 cph 

Heat / Cool Change 

4:HC 

Disabled 

Enabled 

Pump Exercise 

5:PE 

Pump Exercise Disabled 

Pump Exercise Enabled 

System 
Synchronisation 

6:Sn 

Standard operation of the 
Room Unit 

Room unit configured as Synchroniser 

Loss of Communication 
Instruction 

7:LC 

Relay Off 

Relay 20% on / 80% off 

The following parameters are for the control of other Honeywell Wireless products such as Wireless Underfloor Heating controls and 
Wireless Radiator controls. For more information please contact Honeywell sales. 

Room Temperature 
Sensor Use 

8:Su 

HC60 Control 

1,2,3 or 4 

1 - HR80/HM80 control with own/remote 
sensor (no temperature displayed) 
 
2 - Hr80/HM80/HCE80 control with CM 
Sensor 
 
3 - HC60 control and HR80/HM80/ 
HCE80 control with own/remote sensor 
 
4 – Hr80/HM80/HCE80 control with own/ 
remote sensor (temperature displayed) 

 

HR80 Window-Open 
Function 

9:HO 0 

Disabled 

Enabled 

HR80 Local Override 

10:HL 

Enabled 

Disabled 

Maximum Flow 
Setpoint 

11:uF 

55 

55°C Maximum Flow Temp. 

0 to 99 

0°C to 99°C adjustments in 1°C steps 

Minimum Flow Setpoint 

12:LF 

15 

15°C Minimum Flow Temp. 

0 to 50 

0°C to 50°C adjustments in 1°C steps 

Mixing Value Run Time 

13:Ar 

150 

150 seconds 

0 to 240 

0 to 240 sec. adjustments in 1sec steps 

Summary of Contents for CM921

Page 1: ...minate the display for easier viewing in low light conditions Reliable RF communication utilising 868 MHz band with 1 duty cycle limit to minimise communication disturbance Every room unit can be bound with several relay boxes e g to control several electric heating panels Armchair programmed Holiday button that provides energy savings by reducing to a constant temperature for 1 to 99 days when pe...

Page 2: ...ds EN60730 1 Nov 2000 EN55014 1 1997 EN55014 2 2000 ETSI EN300 220 3 2000 ETSI EN301 489 3 2000 TEMPERATURE CONTROL Sensing element 100K 25 o C NTC thermistor Control form Fuzzy Logic Algorithm Minimum ON time 10 of cycle time min one minute adjustable to 2 to 5 min see installer set up Cycle rate Selectable by application see installer set up Temperature control accuracy 0 5 K nominal 20 o C 50 l...

Page 3: ...itions Abbreviated Set Up Description e g Cl Clock Format Factory Setting or New Choice Press TEMP or to change e g 12 AM PM Format 24 24hr Format Installer Set up Number Press or to change e g 1 Clock Format Brief Description of the Parameter Function Specific Applications Setting What do you need to change Cycle Hour Minimum ON time in minutes Note All parameters listed below belong to category ...

Page 4: ...f 5 C can be increased up to 21 C to protect inhabitants from cold Set parameter 6 uL category 1 to the desired upper limit Set parameter 7 LL category 1 Parameter Installer Set Up Number Abbreviation Press or keys to select Factory Setting Optional Setting Category 1 Parameters Room Thermostat Settings Display Description Display Description AM PM 24hr Display 1 Cl 24 24 hr clock display 12 12 hr...

Page 5: ...Off 1 Relay 20 on 80 off The following parameters are for the control of other Honeywell Wireless products such as Wireless Underfloor Heating controls and Wireless Radiator controls For more information please contact Honeywell sales Room Temperature Sensor Use 8 Su 0 HC60 Control 1 2 3 or 4 1 HR80 HM80 control with own remote sensor no temperature displayed 2 Hr80 HM80 HCE80 control with CM Sens...

Page 6: ...oles IMPORTANT 1 The installer must be a trained service engineer 2 Disconnect the power supply before beginning installation INSTALLATION The CM921 is a radio frequency device and for the best performance should be installed in an open space Leave at least 30cm distance from any metal objects including wall boxes and at least 1 metre from any other electrical equipment e g radio TV PC etc Do not ...

Page 7: ...em pack includes HC60 1 day RF system pack includes HC60 1 day RF system pack includes HC60 1 day room unit spare 1 day room unit spare 1 day room unit spare HC60 Spare HC60 Spare HC60 Spare CMT921A1018 CMT921A1026 CMT921A1042 CMS921B1018 CMS921B1026 CMS921B1042 R6660D1017 R6660D1025 R6660D1041 Honeywell Honeywell Honeywell Honeywell Honeywell Honeywell Honeywell Honeywell Honeywell French Dutch F...

Reviews: