Honeywell CM701 Installation Manual Download Page 2

Category 1 Parameters - Programmable Thermostat Settings

CM707/701 - InSTAllATIon GuIdE

You have now installed the Programmable Thermostat. For gas boiler applications, the factory system settings will not need to 

be changed (for other applications see below). You can now use the 

uSER GuIdE

 to program the unit and demonstrate how 

it works to the homeowner.

using the Programmable Thermostat for Specific Applications

Application

 

Gas Boiler (<30kW)

Oil Boiler 

Thermal Actuator

Zone Valve

Electric Heating 

(resistive load 3-5A)

Settings

Cycle /Hour 

6

12

6

12

Minimum ON 

time

1

1

1

1

What to change

Note: All parameters listed below belong to category 2 

– system parameters (see Installer Parameter Table)

No changes required

Set 1:Ot parameter to 4 

Set 2:Cr parameter to 3

Set 2:Cr parameter to 12

No changes required

Set 2:Cr parameter to 12

Entering the Installer Mode

1.

  Press the 

oFF 

button.

2. 

Press and hold the   button and the two 

PRoGRAM

 

 

or 

 buttons together. 

3. 

The  unit  will  display  the  first  parameter  of  installer 

parameter group category 1 (from Parameter No. 1 to 20).

4. 

Press the     or   button to change the factory setting. 

The display will flash indicating that a change has been 

made.

5. 

Press  the  green 

  button  to  confirm  the  change.  The 

display will stop flashing.

6. 

Press the     button to go to the next parameter.

7. 

Press the 

PRoGRAM

   button to go to Installer parameter 

group category 2 (from Parameter No. 1 to 5).

8. 

To  exit  installer  mode,  press  the 

AuTo

MAn 

or 

oFF 

button.

 

AM-PM / 24hr Display 

Reset Time/ Temp 

Program

 

Auto Summer/Winter 

Time Change

LCD Backlight

Upper Temp Limit 

Lower Temp Limit 

Optimisation

Temperature Offset 

Proportional Band 

Width

Scheduled Maintenance 

Alert Period (months)

Reset Parameters to 

Factory Defaults

Minimum boiler ON 

time

Cycle Rate

Pump Exercise

 

1:CL 

2:rP 

 

3:tC 

5:bL

6:UL 

7:LL 

8:Op

12:tO 

13:Pb 

19:SP 

20:FS 

1:Ot 

2:Cr

5:PE

notes: 

Always remember to press the green 

 button to confirm that you want to store the new Installer Set-Up setting. To exit 

the Installer Set-Up Mode press the 

AuTo 

or 

MAn 

button.

System Commissioning

To enter the diagnostic mode press the 

oFF 

button then press and hold the   button for 5 sec. The unit will enter the user settings 

mode. Next press and hold the   and     buttons together. The unit will hold the relay on for 5 minutes and the following information 

will be available on the display: model ID, date code (WW/YY) and checksum. To view this info press the     or   button.

Display 

12 

 

1

35 

0

1.5 

6

0

Factory default Settings

Parameter

Parameter 

no.

Description

  

12 hr – AM/PM clock display 

format

Time / Temp profile set to factory 

default

Changes to 0 when one of the 

time/temp profiles are changed

Auto Summer/Winter Time 

Change enabled

Backlight enabled

5°C Lower Temp. Limit 

No temperature offset 

Optimisation disabled

Proportional band of 1.5 degree 

All settings at factory defaults. 

Scheduled Maintenance Alert 

Period disabled

Changes to 0 when one of the 

parameter is changed

1 minute minimum ON time 

6 cycles per hour (cph)

Pump exercise disabled

Display

 

24 

0

21-34 

6-20 

1

-3 to +3 

1.6 to 3.0 

0 to 48 

0

2 to 5 

3,9,12

1

optional Settings

Description

  

24 hr clock display format 

Time / Temperature are as 

programmed

To restore the factory profile 

set to 1

Auto Summer/Winter Time 

Change disabled

Backlight disabled

21°C to 34°C adjustment in 

1°C steps

6°C to 21°C adjustment in 

1°C steps

Optimisation enabled

-3°C to +3°C adjustment in 

0.1°C steps

1.6°C to 3.0°C adjustment in 

0.1°C steps

0 to 48 months adjustment in 1 

month steps

Settings are as modified above

To restore the factory profile set to 1 

Selection of 2, 3, 4 or 5 

minutes minimum ON time

Selection of 3, 9 or 12 cph

Pump exercise enabled

COPY

DAY

DATE/

DAY

1..4

MANAUTO

1

2

3

4

5

6

7

AUTO

MAN

OFF

1

Installer Parameters Table

“Manufactured for and on behalf of the Environment and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, 

Switzerland by its Authorised Representative Honeywell International Inc.”

42010938-007 R1
© 2006 Honeywell International Inc.

Honeywell Control Systems ltd.

Arlington Business Park,
Bracknell
Berkshire
RG12 1EB
Technical Help Desk: 08457 678999
www.honeywelluk.com

using the Special Features of the Thermostat

Special Feature

Summer/Winter Auto 

time change

Optimisation 

(Variable Start Time) 

Scheduled 

Maintenance Alert 

Period

desctiption

This  feature  moves  time  automatically  on  the  last  Sunday  of  March 

and the last Sunday of October. The feature is factory enabled.

The thermostat will adjust the start time in the morning/afternoon 

so the desired temperature is reached by the start of the program 

period. The system will restrict the start time to a max of 2 hours.

If the installation requires scheduled maintenance and the user 

needs to be reminded that the service is due the parameter value 

can be set to the required number of months (1-48). When the preset 

period expires the CM701/CM707 will display the ‘

SERVICE

’ icon.

Enable/disable this feature

To enable: Set parameter 3:

tC (category 1) to 1.

To enable: Set parameter 8:

OP (category 1) to 1. 

Set parameter 19 to the 

required value to enable 

maintenance alert. Value set 

to zero disables the function.

2

2

COPY

DAY

DATE/

DAY

1..4

1

2

3

4

5

6

7

AUTO

MAN

OFF

1 2

Category 2 Parameters - System Settings (press PRoGRAM   to access this category)