INSTALLER SET-UP

This feature allows you to adjust CM61RF system to match the specific requirements of the application. Installer Set-up allows

Set-up specific applications parameters

Enable special features

Establish support for ATS module

Specific Applications

Setting

Description

Cycle/
Hour

Minimum
ON time

(in minutes)

Heating

Gas Boilers

(<30kW)

6

1

Number of cycles per hour and minimum ON time are the key
parameters which allow the adjustment of the control algorithm
to meet specific application requirements.

Cycles/Hour – Parameter n.9; settings range: 3, 6*, 9,12 cph

Minimum ON time – Parameter n.2, setting range:1*,2,3,4,5 min

Oil Boiler

3

4

Thermal Actuator

12

1

Zone valve

6

1

Electric heating

12

1

Air
conditionin
g

Heat Pump/
Air conditioner

3

4

CM61RF is designed to perform heating or cooling operation. To
switch from heating to cooling set parameter n.6 in the installer
set-up mode to 0. If you switch between heating and cooling the

Special Features

Description

Setting

Adaptive Intelligent
Recovery TM

The CM61RF will adjust the start time at upward setpoint changes so the
desired temperature is reached at the programmed time e.g. 7:00
temperature 21

o

C.The chronotherm will monitor the start-up period and

use this information to modify the start time calculation for the next
upward setpoint change. The system will restrict the start time to a max of
3 hours before the programmed comfort time

AIR does not function in cooling mode.

0* – disabled

1 – enabled

AM-PM/ 24hr Display

Change display format (default 24hr)

0* – 24 hr display

1 – AM/PM display

Pump exercise

When enabled the Pump Exercise will switch the relay on for 1 minute at
12:00 a.m. if the relay has not been switched on since 12:00 the previous
day.

0* - disabled

1 – enabled

Upper Temperature
Limit

The normal upper temperature limit of 30

o

C can be reduced to 21

o

C to

save energy. Useful for small commercial premises.

21-30

o

C

Factory setting 30

o

C*

Lower Temperature
Limit

The normal lower temperature limit of 5

o

C can be increased up to 16

o

C to

protect the inhabitants from cold. Useful for nursing homes.

5-16

o

C

Factory setting 5

o

C*

Temperature Offset

If the Chronotherm is located in a hot/cold location and cannot be moved
then the measured/ displayed temperature can be adjusted by +/- 3

o

C.

-3 - +3

o

C

Factory setting 0

o

C*

Proportional Band
Width (PB)

The PB can be adjusted up to 3

o

C (default is 1.5

o

C) to provide better

temperature control (less overshoot). Useful for:
a. Well insulated homes with over-sized heating systems
b. Air systems with fast response

1.5-3.0 K (adjustment
step 0.1 K)

Factory setting1.5 K*

Fail-safe mode

The CM61RF allows you to set the fail-safe mode of operation of the
heating system when radio communication is lost. By default HC60 output
relay will be switched OFF in case of communication loss. Alternatively
you may choose to cycle the boiler at 2 min ON and 8min OFF. Useful
when the building is not occupied for long periods of time and there is a
high risk of frost damage.

0* – relay OFF

1 – relay cycles

Accessory

Description

Setting

Automatic Time
Setting (ATS)
Module

The ATS module picks up a time signal daily from a European transmitter,
so you never need to set or adjust the time.

– no accessory

1 – ATS module

*Factory settings indicated with bold font.

Summary of Contents for CM61RF

Page 1: ...y box may be surface or wallbox mounted Frost protection is ensured when the slider is in the OFF position Frost protection setpoint may be adjusted by installer minimum setting 5 o C Installer Set Up Mode allows extra functions to be set at the discretion of the installer to match the consumers applications Optimisation Pump Exercise Upper Lower Setpoint Limit Adjust Temperature offset Minimum ON...

Page 2: ... Proportional Integral PI Minimum ON time 10 of cycle time min one minute adjustable to 2 to 5 min see installer set up Cycle rate 3 6 default 9 12 Selectable through the installer set up mode Environmental Operating temperature range 0 to 40 o C Shipping and storage temperature range 20 to 55 o C Humidity range 0 to 90 rh non condensing Approvals Designed to meet European EN approvals EN60730 1 1...

Page 3: ...ode 0 disabled 1 enabled AM PM 24hr Display Change display format default 24hr 0 24 hr display 1 AM PM display Pump exercise When enabled the Pump Exercise will switch the relay on for 1 minute at 12 00 a m if the relay has not been switched on since 12 00 the previous day 0 disabled 1 enabled Upper Temperature Limit The normal upper temperature limit of 30 o C can be reduced to 21 o C to save ene...

Page 4: ...etc It is recommended that the R6660C relay box is installed before commencing with the room unit installation refer to appropriate Installation Guide R6660C Relay box T6661C room unit WIRING The R6660C relay box is designed for fixed wiring only and must be installed in accordance with latest l E E regulations Ensure the wiring connection to the supply is via a fuse rated at no more than 10 amps ...

Page 5: ...WIRING ORDERING SPECIFICATION Description Model Logo Literature Spec Sheet Radio Frequency Chronotherm 1 day System Pack Y6661C1001 Honeywell English ENOR8508 RF Chronotherm room unit 1 day T6661C1006 Honeywell English ENOR8508 RF Chronotherm relay box HC60 R6660C1001 Honeywell English ENOR8508 Automatic Time Setting Module Europe Q6667B1007 Multi Language ENOR8501 ...

Reviews: