
CLASS 500 ADVANCED KWH/DEMAND METER
15
62-0304—05
NOTE: To change device ID, set single point at 46049 with data set to new device ID (e.g., 1 to 247).
To set date/time, set multiple points at 46025 for 4 points with data set to HHMM SSDW MMDD YYYY (DW=day of week).
To clear single meter kWh/kW, set single point at 41001 with data set to 0000 (similarly for 41003, 41005, 41007).
To clear multiple meter readings, set multiple point at 41001 for 8 points with data set to 0000's.
NOTE: Jumper J5 & J6 must be closed in order for kWh del/rec and kVARh del/rec to be cleared.
ITEM PM-I W
DATA
(SAMPLE)
DESCRIPTION
46001
8 504D 324B 0106 0421 0800 454D 4F4E 2020 Firmware version: PM 5K, Ver, Ver date/time,
Honeywell
R
46009
8 456E 6572 6779 204D 6574 6572 0000 0000 Device description: Honeywell Energy Meter
R
46017
8 1356 4503 0613 0300 0000 0000 0000 0000 Initialize device with date/time
W
46025
8 1356 4503 0613 0300 0000 0000 0000 0000 RTC date/time, will accept broadcast
command
R/W
46033
8 1356 4503 0527 0300 0000 0000 0000 0000 CPU date/time (7 bytes, rest is reserved for
other future formats)
R/W
46041
8 0001 0001 0000 0000 0000 0311 0020 1100
Group, location, Device ID number
R/W
46049
8 0041 0000 0000 0000 0000 0311 0020 1100
Dev. ID, Hookup, Serial numbers….
R/W
46057
8 0592 0007 0000 0000 0000 0000 0000 0000 Recorder info.: idr, dem. int., dem. win.,
dem. syn., timezone, DST…
R/W
46065
8 0101 0001 0D03 3531 1000 0320 0000 0000 Meter info.: SN1&2, pulse rate, Volt/Amp/
CTs, PF/mult1&2, CT, PT
R/W
46513
8 0000 0101 0000 0000 0000 0100 0000 0000 Flags L1
46521
8 0000 0000 0000 0000 0000 0000 0613 0316 Flags L2
46529
8 0000 0000 0000 0000 0000 0000 0000 0000 Flags L3
46537
8 0000 0000 0000 0000 0000 0000 0000 0000 Flags L4
Table 4. Honeywell Modbus point map