CIPer
TM
MODEL 50 CONTROLLER
–
INSTALLATION AND COMMISSIONING INSTRUCTIONS
23
31-00233-02
Set Up and Configuration
You can access the CIPer Model 50 controller via the RS232 interface using a terminal program (serial port)
such as "PuTTY." This can be helpful in the following cases:
•
When the CIPer Model 50 controller cannot be accessed via network. Solution: The network can be
configured to the required settings (see step 6 below).
•
When the CIPer Model 50 controller application or status is unknown Solution: The controller can be reset
to the factory defaults (see step 7 below).
Before proceeding (see section "Procedure" below), you must first connect the RS232 interface of the CIPer
Model 50 controller and the PC on which PuTTY is running using the following two cables connected end-to-
end: TECHTOO USB 3.0 and YIOVVOM DB9
The interface parameters for serial communication are as shown in the following screenshot:
Procedure
1.
Start PuTTY. As soon as the following line displays, press
C
.
RESULT: The Boot menu displays.