Honeywell Chronotherm IV T8611G Installation Instructions Manual Download Page 3

T8611G CHRONOTHERM

®

 IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS

3

69-1406—1

Using Thermostat Keys (Fig. 6)

The thermostat keys are used to:
• set current day and time,
• program times and setpoints for heating and cooling,
• temporarily override program temperatures, 
• display present setting, 
• configure Installer Setup, 
• check System-Test,
• display outdoor temperature (select models),
• set the system operation, 
• set the fan operation. 

NOTE: Always press the keys with your fingertip or sim-

ilar blunt tool. Sharp instruments like a pen or 
pencil point can damage the keyboard. 

SETTINGS

System and Fan Settings 

The system default setting is Heat and the fan default 
setting is Auto. Use the System and Fan keys to change 
the settings. See Fig. 7. The fan settings can be set for 
each program period individually. The system selection is 
for all the program periods.

System settings control the thermostat operation:

Em Heat: Emergency heat relay is on continuously. 

Thermostat cycles highest stage of heat. Cooling 
system is off. Compressor is de-energized.

Heat: The thermostat controls the heating.
Off: Both the heating and cooling are off.
Cool: The thermostat controls the cooling.
Auto: The thermostat automatically changes between 

heating and cooling operation, depending on the 
indoor temperature.

Fan settings control the system fan:

On: Fan operates continuously.
Auto: Fan operates with equipment.

LED Indication

Two LED indicators are located in the upper right of the 
thermostat. They indicate when a Check or Fail signal is 
sent to the thermostat from the system. See Fig. 8.

Fig. 6. T8611G key locations and descriptions.

Fig. 7. Thermostat System and Fan key locations.

Fig. 8. LEDs location.

M14624

Time

Set Program

System

Fan

Run

Program

Hold Temp

Set Current

Day/Time

Wake

Leave

Return

Sleep

Day

Heat/Cool

Settings

Daylight

Time

Copy

INCREASE TEMPERATURE 
SETTING OR SCROLL 
FORWARD THROUGH 
INSTALLER SETUP OPTIONS

DECREASE TEMPERATURE 
SETTING OR SCROLL 
BACKWARD THROUGH 
INSTALLER SETUP OPTIONS

DISPLAY INFORMATION
SUCH AS PRESENT 
SETTINGS AND OUTDOOR 
TEMPERATURE

RETURN TO 
NORMAL
OPERATIONS

ENTER 
INDEFINITE 
OR TIMED 
HOLD MODE

SET CURRENT 
DAY AND TIME

SET CURRENT OR
PROGRAM DAY

CHANGE BETWEEN 
DAYLIGHT SAVINGS 
AND STANDARD TIME

INCREASE TIME SETTING
OR SCROLL FORWARD 
THROUGH INSTALLER SETUP 
AND SYSTEM TEST

DECREASE TIME SETTING OR 
SCROLL BACKWARD THROUGH 
INSTALLER SETUP AND SYSTEM TEST

COPY ONE PROGRAMMED 
DAY TO ANOTHER DAY

SET WAKE TIMES 
AND SETPOINTS

CHANGE BETWEEN 
HEATING AND COOLING 
SETPOINTS 

SET LEAVE TIMES 
AND SETPOINTS

SET RETURN TIMES 
AND SETPOINTS

SET SLEEP TIMES 
AND SETPOINTS

SELECT SYSTEM 
OPERATION 

SELECT FAN 
OPERATION 

M14625

Hold Temp

Run

Program

Copy

Daylight

Time

Set Current

Day/Time

System

Fan

Time

Set Program

Day

System

Fan

Wake

Leave

Return

Sleep

Heat/Cool

Settings

M10675A

TWO LED INDICATORS

Summary of Contents for Chronotherm IV T8611G

Page 1: ...out the product operation Location Install the thermostat about 5 ft 1 5m above the floor in an area with good air circulation at average temperature See Fig 1 Do not install the thermostat where it can be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys unheated uncooled areas such as an outsid...

Page 2: ...kup of T8611G in a heat pump system Fig 4 Correct wiring technique Mounting Thermostat 1 Engage tabs at the top of the thermostat and wall plate See Fig 5 2 Press lower edge of case to close and latch NOTE To remove the thermostat from the wall first pull out at the bottom of the thermostat remove top last Fig 5 Mounting thermostat on wallplate 5 FEET 1 5 METERS YES NO NO NO M10106 WIRES THROUGH W...

Page 3: ...stem fan On Fan operates continuously Auto Fan operates with equipment LED Indication Two LED indicators are located in the upper right of the thermostat They indicate when a Check or Fail signal is sent to the thermostat from the system See Fig 8 Fig 6 T8611G key locations and descriptions Fig 7 Thermostat System and Fan key locations Fig 8 LEDs location M14624 Time Set Program System Fan Run Pro...

Page 4: ...e Installer Setup numbers backward press the Time key To exit the Installer Setup press Run Program Fig 9 Display of all LCD segments Fig 10 Display of Installer Setup number and setting IMPORTANT Only configurable numbers are shown on the device Example If thermostat does not have a system key Installer Setup Number 12 will not be displayed Review Table 3 factory settings and mark any desired cha...

Page 5: ...al energized for reversing valve in heating Deadband 30 3 Heating and cooling setpoints can be set no closer than 3 F 1 5 C 4 thru 10 Heating and cooling setpoints can be set no closer than the chosen value 4 4 F 2 C 5 5 F 2 5 C 6 6 F 3 C 7 7 F 3 5 C 8 8 F 4 C 9 9 F 4 5 C 10 10 F 5 C Not Used 31 and 32 Minimum off time for the compressor 33 5 5 minute minimum off time for the compressor 0 thru 4 M...

Page 6: ... adjusts to 3 F higher than actual room temperature 1 Display adjusts to 1 F lower than actual room temperature 2 Display adjusts to 2 F lower than actual room temperature 3 Display adjusts to 3 F lower than actual room temperature Furnace Air Filter Timer 43 0 Off 1 2 3 4 1 10 days 2 30 days 3 60 days 4 120 days Times counted when heat cool or fan is running Humidifier Pad Monitor 44 0 Off 1 2 3 ...

Page 7: ...test and Time to go back to the previous test Press Run Program to exit the system test M14619 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy Set Day Time Mon PM M14620 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Day Heat Cool Setting...

Page 8: ...fan is also energized 12 Stage two heat comes on Stage one heat and system fan remain on 11 Stage two heat turns off 10 Stage one heat and system fan turn off Emergency Heating Equipment System Test Time 20 Change from heating to emergency heating equipment System Test 21 Emergency heat come on 20 Emergency heat turn off Cooling Equipment System Test Time 30 Change from heating or emergency heatin...

Page 9: ...soft ware identification code Example 02 software ID code 2 4 Press the increase key again to display the soft ware revision number Example 001 Revision number 1 5 Press the increase key again to display the EEPROM identification code Example 314 EEPROM ID 314 6 Press the Run Program key to exit the system test The system test times out after four minutes without any key presses CHECKOUT Outdoor T...

Page 10: ...ot come on No power to the thermostat Check for 24 Vac between R and C terminals If missing 24 Vac check if the circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check if the power switch on the HVAC equipment is in the Off position set to the On position check wiring between thermostat and HVAC equipment replace any broken wires and tighten an...

Page 11: ...self test Outdoor tempera ture not displayeda Option not activated Enter Installer Setup number 24 and set to 1 Thermostat must have OT terminals and a C7089B1000 installed Outdoor temperature display is incorrecta Outdoor sensor is connected incorrectly Refer to C7089B1000 Installation Instructions and check wiring between the thermostat and sensor Wrong sensor Replace sensor with C7089B1000 Sens...

Page 12: ...yourhome T8611G CHRONOTHERM IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS Automation and Control Solutions Honeywell Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z ...

Reviews: