Honeywell CHRONOTHERM III T8611M User Manual Download Page 28

28

the auxiliary heat even when the T8611 is calling for it.
(Balance point is the outdoor temperature below which the
heat pump must call on auxiliary heat to help handle the
load.) The resulting unnecessarily long recovery times
reduce building energy savings.

When Adaptive Intelligent Recovery™ Is Used

Adaptive Intelligent Recovery™ is used during recov-

ery from energy savings. It is bypassed when the setpoint
is changed, and when the CHANGE TO LAST PERIOD,
SKIP NEXT PERIOD or HOLD TEMP key is pressed. If
Adaptive Intelligent Recovery™ is bypassed, the system
operates the stages of equipment like a conventional ther-
mostat.

WHAT TO EXPECT DURING RECOVERY
FROM ENERGY SAVINGS IN HEATING

The T8611 controls the heating equipment based on the

indoor sensed temperature, which is a combination of air
temperature and wall temperature.

In Mild Weather

When the outdoor temperature is mild, say 50

°

F [10

°

C], the recovery from energy savings will be handled
completely by the heat pump, without using the more
costly auxiliary heat. The heat pump starts only after the
control point has risen above the sensed temperature and
is locked on until the comfort setpoint is reached. During
the comfort period, the heat pump will cycle on and off as
needed to maintain the sensed temperature /-1

°

 F

of the setpoint. During energy savings periods, the T8611
will call the heat pump on only if the sensed temperature
falls below the control point.

In Moderate Weather

When outdoor temperature is below the balance point

of the heat pump, the heat pump will run continuously
during the recovery period and the auxiliary heat will cycle
as necessary. During the comfort period, the heat pump
runs continuously and auxiliary heat cycles until the next
energy savings period begins. During energy savings, the
heat pump cycles on only when the sensed temperature
falls below the control point. Under these conditions,
auxiliary heat is typically not needed during the energy
savings period.

In Severe Weather

When the outdoor temperature is severe, say 0

°

 F [-18

°

C], the heat pump is on continuously and auxiliary heat

cycles even during the energy savings period. When re-
covery from energy savings begins, the heat pump will
stay on and auxiliary heat will cycle. During recovery, the
auxiliary heat ON times will be long, and the OFF times
will be short. The ON times will shorten as the control
point approaches the comfort setpoint. During the comfort
period, the heat pump is on continuously and auxiliary heat
cycles until the next energy savings period. When energy
saving begins, the heat pump cycles off until the sensed
temperature falls below the control point. Although the
heat pump comes on when the sensed temperature falls
below the control point, the sensed temperature may lag 2

°

or 3

°

 F below the control point because of the time required

to warm up the walls and furniture. Auxiliary heat will
cycle as necessary during the energy savings period.

THERMAL PERFORMANCE WITH T8611

During severe weather, the T8611 actually controls

closer to the setpoint than a conventional thermostat. This
is because the heat anticipator is replaced by two elec-
tronic control strategies—cycling by heat anticipation and
proportional plus integral control.

Electronic cycling by heat anticipation acts like a tradi-

tional heat anticipator, except that never needs adjustment
for various control circuit load currents. It cycles the heat
pump off slightly before the room temperature reaches the
setpoint to keep heat remaining in the ductwork from
overheating the room.

In severe weather, a conventional thermostat with a

heat anticipator tends to turn off the thermostat too soon,
so the effective control point is somewhat below the
setpoint. In very cold weather, the difference between
setpoint and effective control point may be 5

°

 or 6

°

 F [2

°

or 3

°

 C] with a conventional thermostat. This phenomenon

is called droop.

Proportional plus integral action eliminates droop by

adjusting the on-time of the stage that is cycling longer or
shorter until the control point matches the setpoint. The
T8611 controls space temperature within one degree of
setpoint, when the temperature has stabilized after an
energy savings period.

This  zero droop performance of the T8611 provides

improved occupant comfort and energy savings. Occu-
pants do not need to continually adjust thermostat setting
to maintain desired temperature, even during severe
weather.

MINIMUM-OFF TIMING

A minimum-off timer in the T8611 ensures that the

compressor will not come on again for at least five minutes
after it turns off. The minimum-off timer is triggered when
the compressor goes off, or when the system switch is
moved. If the compressor turns off when the setpoint is
changed or the CHANGE TO LAST PERIOD key is
pressed, then the minimum-off timer is triggered. The
minimum-off timer operates during the first stage of both
heating and cooling.

T8611M

OPERATION

Summary of Contents for CHRONOTHERM III T8611M

Page 1: ...ous time of day day of week cur rent period and room temperature AdaptiveIntelligentRecovery bringsroomtem perature to programmed temperature at program med time maximizing comfort and energy sav ings Temperature control program maintains tempera ture within 1 F of setpoint Temporaryprogramoverrideavailablebyusing WARMER and COOLER keys SKIP next period key CHANGE to last period key HOLDTEMPkeypro...

Page 2: ...tat heating and cooling ON cycles EM HT LED red on subbase lights when system switch is in EM HT On some systems light may indicate need to switch to EM HT because of heat pump problem AUX HT LED green on subbase lights when ther mostat is calling for operation of auxiliary heat CHECK LED yellow on subbase lights when an equipment or system problem needs to be checked Consult heat pump literature ...

Page 3: ...ting dimensions in in mm 4 121 3 4 3 83 5 16 7 179 1 46 13 16 5 135 5 16 M5181A 4 3 32 104 1 31 32 50 Fig 2 202905AA Remote Sensor dimensions in in mm 4 3 32 104 FRONT 1 31 32 50 SIDE M5244 2 51 1 31 32 50 41 64 16 3 8 1 19 64 9 64 1 2 8 4 DIA 13 35 1 25 BACK ...

Page 4: ...STEM RUN PROGRAM PERIOD TIME TEMPERATURE PRESENT SETTING SKIP NEXT PERIOD CHANGE TO LAST PERIOD SET PRESENT DAY TIME HOLD TEMP DAY SET HEAT COOL CANCEL PERIOD COPY FROM AHEAD WARMER BACK COOLER M5360 WED MIDDAY AM HEAT ON HEAT OFF COOL ON AUTO FAN ROOM COPY TO ...

Page 5: ...ate equipment and thermostat IMPORTANT The T8611 requires a conductor to trans former common to provide continuous 24V power for thermostat operation This feature is commonly specified and provided by equipment manufacturer IF RETROFIT REPLACEMENT APPLICATION CONSIDER equipment requirements systemswitching manual EM HT HEAT OFF COOL automatic EM HT HEAT OFF AUTO COOL unique heat pump functions of ...

Page 6: ... Y2 If applying T8611M to 1 stage cooling system leave Y2 Stage 2 cool unconnected Second Stage Heat W2 If applying T8611M to 2 stage heat systems in which the Auxiliary Resistive second stage is compressorized connect stage 2 to W2 Third Stage Heat W3 leave W3 unconnected If 2 stage heat system in which the second stage is auxillary electric resistive connect auxiliary stage to W3 leave W2 unconn...

Page 7: ...rich a na na na na Changeover on heat check LED optional Bard a N1024 F1261 N1036 F1299 Changeover on heat typical R1129 L1181 R1146 L1185 checkLEDoptional equipment terminal W1 to thermostat B Bryant Day Night Payne b a b b G1451 F1113b G1166 F1125 Check LED optional F X1 a G1261 F1253 jump X2 to C Note P terminal a J1010 L1371 G1174 available on manual changeover a R1335 L1405 T8611R models only...

Page 8: ...lay isolation Crispaire Marvair G1089 F1162 G1208 F1166 F1204 F1323 R1111 L1215 R1156 L1094 Fedders Airtemp Climatrol a C1398 L1090 C1509 L1102 Separate first stage heat cool a C1406 C1517 terminals required check LED a C1414 C1541 optional equipment terminal K to thermostat E Florida Heat Pump a na na na na Optional check LED X X1 jump X2 to C Heatwave Southwest Mfg G1105 F1170 G1232 F1224 Heil Q...

Page 9: ...t R1004 B1042 R1008 B1046 Y W1 to B K to E B1109 R1057 L1037 R1152 L1207 R1198 L1227 R1285 L1157 R1350 L1181 Janitrol Tappan G1147 F1139 G1109 F1117 Equipment terminal C to thermostat C Lennox NOTE Rewire for single 75 VA transformer if two transformer system G1014 F1113 G1026 F1067 G1022 E1148 G1125 E1019 C G1162 G1091 DoD specs use guard G1154 F1105 G1323 L1201 R1024 B1160 R1040 B1202 R1178 L135...

Page 10: ...PB series separate first stage heat cool a na na na na Late PE series optional check LED X1 X1 jump X2 to R Rheem Ruud G1097 F1238 G1133 F1158 G1238 G1141 L1157 R1081 L1045 G1220 R1107 L1136 R1079 R1095 Square D Sun Dial a C1224 F1071 C1525 F1182 Separate first stage heat cool required optional check LED X X1 jump X2 to R Trane General Electric a G1204 J1043 G1059 J1039 Optional check LED F X1 jum...

Page 11: ...ransformer G1281 Westinghouse G1048 F1121 G1034 F1141 F1246 F1091 F1279 F1257 J1019 J1013 J1050 J1062 R1103 L1108 R1149 L1110 L1173 L1128 L1151 na na na na Separate first stage heat cool ter minals required D1108 L1223 G1356 L1219 2 speed heat pump optional check LED L X1 jump X2 to C White Rodgers na na na na 1F58 910 S28 series Williamson R1236 L1348 na na N1008 F1196 na na Changeover on heat W1...

Page 12: ...spots behind doors in corners or under cabinets hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys unheated uncooled areas behind the sensor such as an outside wall IF REPLACING AN EXISTING THERMOSTAT Turn thermostat power off at furnace or heat pump This thermostat requires a single transformer A two transformer system may require turning off two switches ...

Page 13: ...crews Fig 6 Mounting remote sensor base on wall WIRING All wiring must comply with local electrical codes and ordinances Disconnect power before wiring to prevent electrical shock or equipment damage The shape of the terminal barrier permits insertion of straight or conventional wraparound wiring connections Either method is acceptable Push excess wire back into the hole and plug hole with nonhard...

Page 14: ...STEM TRANSFORMER TO R TO C X2 X1 CHECK LED YELLOW FAULT DETECTION SWITCH SWITCH TO C COMMON SIDE OF SYSTEM TRANSFORMER TO R TO C X2 X1 CHECK LED YELLOW SWITCHING DEVICE SWITCH IN SECONDARY OF SEPARATE TRANSFORMER L1 HOT L2 24 Vac 1 MONITOR AUXILIARY HEAT RELAY HEAT 2 L1 HOT L2 HEAT OFF AUTO SYSTEM SWITCH COOL 1 COOL 2 AUTO ON FAN SWITCH 7 1 R C L W3 W2 E G O B Y Y2 X2 STAGE 2 HEAT RELAY EMERGENCY ...

Page 15: ...LOW FAULT DETECTION SWITCH SWITCH TO R POWER SIDE OF SYSTEM TRANSFORMER TO R TO C X2 X1 CHECK LED YELLOW FAULT DETECTION SWITCH SWITCH TO C COMMON SIDE OF SYSTEM TRANSFORMER TO R TO C X2 X1 CHECK LED YELLOW SWITCHING DEVICE SWITCH IN SECONDARY OF SEPARATE TRANSFORMER L1 HOT L2 24 Vac 1 M1018D HEAT 2 L1 HOT L2 HEAT OFF AUTO SYSTEM SWITCH COOL 1 COOL 2 AUTO ON FAN SWITCH 4 1 R C L W3 W2 E G O B Y Y2...

Page 16: ...T RELAY L1 HOT L2 HEAT OFF AUTO SYSTEM SWITCH COOL 1 AUTO ON FAN SWITCH 4 1 R C L W3 W2 E G O B Y Y2 X2 EMERGENCY HEAT RELAY FAN RELAY CHANGEOVER RELAY HEAT STAGE 1 COMPRESSOR CONTACTOR 3 C O EM HT COOL X1 CHANGEOVER RELAY COOL AUX HEAT LED GRN HEAT 3 EM HEAT LED RED HIGH LIMIT C O HEAT 1 HIGH LIMIT CHECK LED YELLOW 2 S1 S2 S3 S1 S2 S3 AA AA A A AA AA AA AA 202905 REMOTE SENSOR 5 X2 X1 CHECK LED Y...

Page 17: ...he display will flash REPL BAT Homeowner will have 20 30 seconds to install new batteriesafterremovingoldbatteriesfrombackofthermo stat After 20 30 seconds it will be necessary to repro gram REPL BAT indication will disappear within 5 10 minutes when thermostat is remounted on the powered subbase IMPORTANT Forproperthermostatoperation always replace dead batteries with new alkaline batteries If ba...

Page 18: ...hould shut off followed by the fan NOTE On an AUTO changeover thermostat the cooling temperature must be set at least 3 F 2 C above the heating temperature or display will flash COOLING CAUTION Do not operate cooling if outdoor temperature is below 50 F 10 C Refer to manufacturer s recommendations NOTE When cooling setting is changed thermostat will wait up to five minutes before turning on the co...

Page 19: ...enter self test 3 Press each key as listed below and look for re sponses listed as key is held down and released Keys may be pressed in any order except RUN PROGRAM should be pressed last because it ends self test M 525A AM SUN MORNING REPL BAT SET PT ROOM PM OUTDOOR TUE WED THU FRI SAT TEMPORARY MON MIDDAY EVENING NIGHT COOL ON HEAT ON CHANGE TO LAST PERIOD SKIP NEXT PERIOD PRESENT SETTING PRESEN...

Page 20: ...ows 1 00 PM Mon Press and hold until the current day ap pears in the display Press and hold until the current time ap pears in the display Be sure AM or PM appears as desired This completes setting the current day and time Go on to Step 2 STEP 2 SETTING THE PROGRAM TIMES AND TEMPERATURES FOR ONE DAY Chooseadaytoprogramfirst Monday is used in the examples Start by pro gramming the MORNING time and ...

Page 21: ...to start the energy saving period Press and hold until the display shows the desired temperature NOTE It is possible to cancel any period showing on the display ex cept MORNING by pushing the CANCEL PERIOD key To move to the next period while program ming simply press the PERIOD key again Program the EVENING time and tem perature if desired Press and release The display shows EVENING but no time o...

Page 22: ...s 72 F the minimum cooling setting is 75 F To set the cooling temperature lower first lower the heating setting Press and release The display shows the preprogrammed cooling temperature and theprogrammedstarttimeforMORNING Press and hold until the display shows the desired cooling temperature for MORN ING Press and release The display shows the preprogrammed cooling temperature and the programmed ...

Page 23: ...til all days are shown not flashing press COPY TO key once more Press and release to copy the program into all the days selected STEP 4 SETTING THE SCHEDULES AND TEMPERATURES FOR THE REMAINING DAYS Use the procedures described in Steps 2 and 3 and summarized in this step to program the remaining days Press and release to enter the programming mode Press and hold until the day desired to program sh...

Page 24: ...air cleaning FAN AUTO Normal setting for most homes and businesses The fan starts and stops with the compressor in heat pump systems when the system switch is set to HEAT AUTO or COOL When system switch is set to EM HT the fan operates withtheauxiliaryheat onsomemodels EM HT The thermostat controls only the backup heat The heat pump is off HEAT Thethermostatcontrolstheheat ing system OFF Both the ...

Page 25: ...OOL AUTO M2756 IMPORTANT The CHANGE feature will be operable the day after the thermostat has been programmed and operating The thermostat requires this time to learn the programmed schedule To temporarily raise or lower the tem perature for the current period only To change back T8611M PROGRAMMING THE THERMOSTAT OPERATING THE THERMOSTAT M2736 SET PT PM TUE MIDDAY EVENING M2737 MORNING SET PT PM T...

Page 26: ...ing After a few seconds the display will show the current temperature Press and release to check the temperature setting Pressandreleasetocancelmanualcon trol CANCELING PROGRAM SETTINGS The thermostat requires time and tem peraturesettingsintheMORNINGtime period for each day but any of the others can be canceled Each time period for each day must be canceled separately Press and hold until the des...

Page 27: ...ysavingssettingtothecomfortsettingallatonce This provides additional energy savings When Adaptive Intelligent Recovery is used in the heatingmode thecontrolpointraisesgradually maximiz ing the use of the more economical heat pump to bring the sensed temperature to the desired comfort setpoint This minimizes the use of the typically more expensive auxil iary heat In both heating and cooling the the...

Page 28: ...imes will shorten as the control point approaches the comfort setpoint During the comfort period theheatpumpisoncontinuouslyandauxiliaryheat cycles until the next energy savings period When energy saving begins the heat pump cycles off until the sensed temperature falls below the control point Although the heat pump comes on when the sensed temperature falls below the control point the sensed temp...

Page 29: ... TO BE ADJUSTED ON A REGULAR BASIS WARMER COOLER KEYS BEING USED TO ADJUST TEMPERATURE REPROGRAM THERMOSTAT TO MAKE PERMANENT CHANGE IN PROGRAM WARMER COOLER KEYS ARE TEMPORARY UNLESS PERIOD KEY IS PRESSED FIRST PROGRAM IS LOST DUE TO POWER OUTAGE OR DISPLAY GOES BLANK WHEN POWER IS TURNED OFF BATTERIES ARE INCORRECTLY INSTALLED REMOVE AND REPLACE PER MARKINGS ON THERMOSTAT BATTERIES ARE DEAD REPL...

Page 30: ...period when the owner can set back heating or set up cooling the temperature for energy savings because family members are asleep or the building is unoccupied Often a NIGHT energy savingstemperatureissetonlyfortheheatingseasonso family members can sleep cool in summer Glossary AUX HT light green This light glows whenever the thermostat is calling for operation of the backup heater Backup auxiliar...

Page 31: ...etting the Program Times and Temperatures for One Day 20 Copying the Program to the Desired Days 23 Setting the Schedules and Temperatures For the Remaining Days 23 Setting the System and Fan Switches on the Subbase 24 Operating The Thermostat 25 Temporarily Changing the Program 25 Reprogramming the Thermostat 26 Holding a Temperature for Extended Absence 26 Canceling Program Settings 26 Checking ...

Page 32: ...ome and Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A QUALITY IS KEY ...

Reviews: