
CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
176
NOTIFIER® European Panels (EN)
Connecting to the Panels
C.11 NOTIFIER® European Panels (EN)
C.11.1 Connection Options
The CLSS Gateway mainboard operates only with the NOTIFIER fire alarm control panels
listed in the table below:
Table C.9: NOTIFIER European Panel Connection Options
C.11.2 Preparing for Connections
For INPIRE panel power connection, you can use either a serial card or an I/O card.
•
Configure the serial card or the I/O card for the power connection at the Serial
Communication screen of the CLSS Fusion Tool Suite.
•
Configure the communication settings at the Serial Communication screen of the
CLSS Fusion Tool Suite.
C.11.3 To Use a NUP Connection
Some NOTIFIER panel variants use a NUP connection with the CGW-MB.
1. On the CLSS Gateway mainboard Side
Connect the NUP cable with a pre-formed connector to the NUP port of the CLSS
Gateway mainboard board.
Refer to
where the NUP port is labeled as 6. It is the P7 pin on the CLSS
Gateway mainboard board.
2. On the Panel Side
•
•
•
Pearl Panel
In the TB2 terminal at the communication card on the panel:
• Connect the White wire to the RxD+ pin.
• Connect the Green wire to the Gnd pin.
• Connect the Brown wire to the TxD+ pin.
• INSPIRE Panels
In the serial communication card on the panel:
• Connect the White wire to the pin 9 (CH2 RX/B).
• Connect the Green wire to the pin 8 (CH2 ISO GND).
• Connect the Brown wire to the pin 10 (CH2 TX/A).
Fire Alarm Panel Models
RS-485
UART/TTL
NUP
(RS-232)
USB
Pearl
Yes
No
Yes
1
1 Use the serial communication card (P/N: 124-426) on the panel.
No
INSPIRE Fusion Panels
E10
No
No
Yes
2 o r 3
2 Use the serial communication card (P/N: HOP-405-100) on the
panel.
3 Use the I/O card (P/N: HOP-404-100) on the panel.
No
E15
No
No
Yes
3 o r 4
No
<
NOTE:
Compatible CGW-MB firmware versions: 3.0.2.30 and above.