LONWORKS BUS I/O MODULES – PRODUCT DATA
EN0Z-0980GE51 R0119
17
Approvals, Certifications, and Standards
Approvals and Certifications
CE-approved
Conforms to EN 60730-1 and EN 60730-2-9
Investigated according to United States Standard
UL916 (USL-listed) as well as according to Canadian
National Standard(s) C22.2 (CNL-listed)
Classification according to EN60730-1
Environmental conditions: For use in home (residential,
commercial, and light-industrial)
environments
Pollution degree:
Class 2
Protection against shock:
Class II
Software class:
Class A
Overvoltage category:
II
Classification according to EN60529
(Degree of Protection Provided by Enclosures)
Classification:
IP20
Ambient Environmental Limits
Operating temperature:
0 … +50 °C at 5…93% r.H.
Storage temperature:
-20 … +70 °C at 5…93% r.H.
Humidity:
5 … 93% r.h. non-condensing
Current Requirement and Heat Dissipation
The L
ON
W
ORKS
Bus I/O Modules are equipped with highly-
efficient switching power supplies which provide for relatively
uniform power consumption over a wide range of supply
voltages (see Table 6). The specific heat dissipation inside
the modules amounts to less than 2 W for all models.
Table 6. Current requirements at nominal voltage
devices powered
supply voltage
24 VAC 24 VDC
CLIOL821A
130 mA
80 mA
CLIOL822A, CLIOLR822A
150 mA
90 mA
CLIOL823A
180 mA 130 mA
CLIOL824A, CLIOLR824A
140 mA
80 mA
Mechanical
Housing Dimensions (H x W x D)
The L
ON
W
ORKS
Bus I/O Modules (mounted on Terminal
Sockets) all have the dimensions: 110 X 90 X 93 mm (see
also Fig. 23 on page 18).
Housing Material
Plastic, flame-retardant
Mounting Methods
DIN-rail mounting (e.g., in control cabinet).
Calculated Lifetime of Weakest Components
MTBF
13.7 years (under typical operating conditions)