Honeywell CentraLine CLIOL821A Product Data Download Page 1

LonWorks Bus I/O Modules 

Product Data 

 

 
 

Copyright © 2019 Honeywell GmbH ● All Rights Reserved 

 

EN0Z-0980GE51 R0119 

 

GENERAL 

The CentraLine L

ON

W

ORKS

 Bus I/O Modules communicate 

via the L

ON

W

ORKS

 Bus. 

These pluggable CentraLine L

ON

W

ORKS

 Bus I/O modules 

consist of a terminal socket and a removable electronic 
module, allowing the socket to be mounted and wired before 
the electronic module is installed. All such electronic modules 
can be swapped out without disrupting the power and bus 
connections: Simply unplug the “old” and insert the “new” 
module. 
 

  WARNING 

Risk of electric shock or equipment damage! 

► 

Do not touch any live parts in the cabinet. 

► 

Disconnect the power supply before you start to install 
the control system. More than one disconnect switch may 
be required to de-energize the system. 

► 

Do not reconnect the power supply until you have 
completed the installation. 

► 

Unused terminals must be closed (by completely 
screwing in the terminal screws), thus preventing the 
accidental touching of “live” parts. 

 
Software updates, configuration, and commissioning are all 
done automatically by the controller for all L

ON

W

ORKS

 Bus I/O 

Modules. 
The L

ON

W

ORKS

 Bus I/O Modules may be used with any CPU 

supporting L

ON

W

ORKS

 Bus communication (e.g., the LION, 

EAGLE, etc.). 

FEATURES 

  Plug-and-play functionality for easy maintenance. 

  Pluggable L

ON

W

ORKS

 Bus I/O modules can be exchanged 

without rewiring. Further, the separate installation of 
terminal sockets and electronic modules lower risk of 
damage and theft in the construction phase. 

  Fast wiring with state-of-the-art push-in terminals (screw-

type terminals also available) and bridge connectors. 

  Wide range of sensors supported (NTC20kΩ, NTC10kΩ, 

PT1000-1/-2, Johnson A99 PTC, NI1000TK5000, PT3000, 
Balco500, 0/2…10 V, 0/4…20 mA). 

  Binary input LEDs of the CentraLine L

ON

W

ORKS

 Bus I/O 

Modules can be configured for status display (off / yellow) 
or alarm display (green / red) per channel. 

  Configurable safety position for outputs, in case of loss of 

communication with the controller. 

  Max. wiring flexibility due to optional accessories like 

auxiliary terminals and cross-connectors. 

  Can be mounted in small installation housings 

  Flexible mix of L

ON

W

ORKS

 Bus I/O modules covering all 

your application requirements. 

 

Summary of Contents for CentraLine CLIOL821A

Page 1: ...updates configuration and commissioning are all done automatically by the controller for all LONWORKS Bus I O Modules The LONWORKS Bus I O Modules may be used with any CPU supporting LONWORKS Bus communication e g the LION EAGLE etc FEATURES Plug and play functionality for easy maintenance Pluggable LONWORKS Bus I O modules can be exchanged without rewiring Further the separate installation of ter...

Page 2: ...el XSU823 Screw type terminal socket for BI modules incl bridge connector swivel label XS824 25 Push in terminal socket for relay floating output modules incl bridge connector cross connector swivel label XSU824 25 Screw type terminal socket for relay floating output modules incl bridge connector cross connector swivel label Table 2 Overview of auxiliary parts and spare parts order number descript...

Page 3: ...s 1 LED per input Color mode can be set per input to OFF yellow or green red using CARE COACH AX COACH NX ON 1 6 kΩ to GND or 2 5 V to GND OFF 90 kΩ to GND or 4 V to GND relay outputs default Features Changeover relays Voltage 19 250 VAC 1 29 VDC P 50 mW max total current 12 A current per relay N O 4 4 A AC or 4 1 A DC N C 2 1 A AC or 4 1 A DC Safety position remain 0 100 yellow LED per output Ver...

Page 4: ... Bus I O Modules on separate DIN rails 5 Bridge connectors between LONWORKS Bus I O Modules on same DIN rail 6 Stopper from 3rd party supplier 7 Auxiliary terminal packages LEDs Each CentraLine LONWORKS Bus I O Module is equipped with one green power LED one yellow service LED Overvoltage Protection The inputs and outputs of all CentraLine analog and binary I O modules are protected against short ...

Page 5: ...impedance input circuit for voltage input for active sensors 199 9 kOHM 8 9 VDC IF CONNECTION INTERRUPTED Vi AI GND 24 9 kOHM 10 VDC Fig 6 Analog input impedance setpoint input circuit for NTC10kΩ NTC20kΩ wall module setpoint 71 75 72 76 73 77 74 21 9 VAUX GND GND GND GND GND GND GND GND GND GND VAUX 22 10 1 11 AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8 2 12 3 13 4 14 5 15 6 16 7 17 8 18 25 26 78 COM A COM A...

Page 6: ...3 73 77 72 72 76 71 71 75 24 V 24 V 24 V COM B COM B COM B COM A COM A COM A VAUX VAUX SHIELD INTERNALLY CONNECTED TO DIN RAIL ACTIVE SENSOR 1 24V POWER 2 0 10 VDC SIGNAL 3 GND 24V 0 AUX VOLTAGE POT 1 SIGNAL 2 GND 3 10 VDC AUX 2 2 3 3 1 1 F1 F2 CLIOL 24 VAC EXTERNAL GROUND REQUIRED TO POWER EXTERNAL DEVICES SELECTED INTERNAL CONNECTIONS MIN 0 75 mm 2 MIN 1 5 mm 2 DASHED LINES THIN LINES F2 F1 LEGE...

Page 7: ... 71 75 24 V 24 V 24 V COM B COM B COM B COM A COM A COM A VAUX VAUX SHIELD INTERNALLY CONNECTED TO DIN RAIL 2 2 2 1 1 1 DRY CONTACT TEMP SENSOR NTC20k or Pt1000 0 4 20 mA 1 IN 2 OUT 78 24 V 0 77 76 75 24 V COM B COM A EXTERNAL 499 OHM RESISTOR WITH TWIN WIRE END FERRULES REQUIRED EXTERNAL DC POWER SUPPLY SELECTED INTERNAL CONNECTIONS MIN 0 75 mm 2 MIN 1 5 mm 2 DASHED LINES THIN LINES F2 F1 LEGEND ...

Page 8: ...nual overrides CLIOLR822A LONWORKS Bus Analog Output Module with manual overrides They are installed with the XS821 22 or XSU821 22 Terminal Socket 71 75 72 76 73 77 74 21 9 GND GND GND GND GND GND GND GND GND GND 22 10 1 11 AO1 NC NC AO2 AO3 AO4 AO5 AO6 AO7 AO8 2 12 3 13 4 14 5 15 6 16 7 17 8 18 25 26 78 COM A COM A COM B COM B 24 V 24 V 24 V 0 24 V 0 Fig 11 CentraLine LONWORKS Bus Analog Output ...

Page 9: ...NTERNALLY CONNECTED TO DIN RAIL 2 3 1 F1 F2 21 NC NC 22 1 AO1AO2AO3AO4AO5AO6AO7AO8 2 3 4 5 6 7 8 M 9 GNDGND GND GND GND GND GNDGND GNDGND 10 11 12 13 14 15 16 17 18 24V DRIVE WITH 0 10 VDC SIGNAL 1 24V POWER 2 GND 24V 0 3 0 10 VDC SIGNAL B XS814 A1 A 24 VAC EXT GROUND REQUIRED TO POWER EXT DEVICES SELECTED INTERNAL CONNECTIONS MIN 0 75 mm 2 MIN 1 5 mm 2 DASHED LINES THIN LINES F2 F1 LEGEND THICK L...

Page 10: ... 11 12 13 14 15 16 17 18 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 MCD 3 K1 K2 K3 24V DRIVE WITH 0 10 VDC SIGNAL 1 24V POWER 2 GND 24V 0 3 0 10 VDC SIGNAL B XS814 A1 A 24 VAC SELECTED INTERNAL CONNECTIONS MIN 0 75 mm 2 MIN 1 5 mm 2 DASHED LINES THIN LINES F2 F1 LEGEND THICK LINES MAX 12 A MAX 4 A EXT GROUND REQUIRED TO POWER EXT DEVICES Fig 13 CLIOL822A LonWorks Bus AO Module wiring example 2 Relay ...

Page 11: ...RIVE WITH 0 10 VDC SIGNAL 1 24V POWER 2 GND 24V 0 3 0 10 VDC SIGNAL B XS814 A1 24 VAC 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 MCE 3 K1 K2 K3 SELECTED INTERNAL CONNECTIONS MIN 0 75 mm 2 MIN 1 5 mm 2 DASHED LINES THIN LINES F2 F1 LEGEND THICK LINES MAX 12 A MAX 4 A EXT GROUND REQUIRED TO POWER EXT DEVICES Fig 14 CLIOL822A Lonworks Bus AO Module wiring example 3 Relay Module MCE 3 The relay module fa...

Page 12: ... with devices equipped with an open collector output Table 5 Binary inputs used as fast totalizers Frequency max 20 Hz Pulse ON min 25 ms Pulse OFF min 25 ms Bounce max 5 ms FAST TOTALIZER DRY CONTACT 4 40 VDC OPEN 0 2 VDC CLOSED 150 kOHM 10 kOHM 18 VDC NOT STABILIZED V BI GND Fig 16 Configuration of a binary input as a fast totalizer 71 75 72 76 73 77 74 GND GND GND GND GND GND GND GND GND GND GN...

Page 13: ...BI12 2 3 13 4 14 5 15 6 16 7 17 8 9 10 11 12 18 19 20 21 22 23 24 74 78 24 V 0 24 V 0 24 V 0 73 73 77 72 72 76 71 71 75 24 V 24 V 24 V COM B COM B COM B COM A COM A COM A SHIELD INTERNALLY CONNECTED TO DIN RAIL 2 1 DRY CONTACT F1 2 1 TOTALIZER MIN 25 ms SELECTED INTERNAL CONNECTIONS MIN 0 75 mm 2 MIN 1 5 mm 2 DASHED LINES THIN LINES F1 LEGEND THICK LINES MAX 4 A Fig 18 CLIOL823A LONWORKS Bus BI Mo...

Page 14: ...3 NO NC COM 51 52 53 NO NC COM 61 62 63 NO NC COM 25 71 75 72 76 73 77 74 78 COM A COM A COM B COM B 24 V 24 V 24 V 0 24 V 0 RELAY BLOCK 1 RELAY BLOCK 2 Fig 20 CentraLine LONWORKS Bus Relay Output Modules schematic Features Cross Connecter 1 yellow LED per output Optional versions with manual override switches Auto 0 1 LED flashes in override mode Feedback on manual override signal Configurable sa...

Page 15: ...OM 11 12 13 NO NC COM 21 22 23 31 32 33 NO NC COM 41 42 43 NO NC COM 51 52 53 NO NC COM 61 62 63 NO NC COM 25 SHIELD INTERNALLY CONNECTED TO DIN RAIL FIELD DEVICE 1 230 V N 2 230 V L FIELD DEVICE 1 230 V N 2 230 V L 1 2 M 230 V 1 2 M 230 V F1 F3 SELECTED INTERNAL CONNECTIONS MIN 0 75 mm 2 MIN 1 5 mm or less as per F3 2 DASHED LINES THIN LINES F3 F1 LEGEND THICK LINES MAX 12 A MAX 4 A CROSS CONNECT...

Page 16: ... COM 51 52 53 NO NC COM 61 62 63 NO NC COM 25 SHIELD INTERNALLY CONNECTED TO DIN RAIL FIELD DEVICE 1 230 V N 2 230 V L FIELD DEVICE 1 230 V N 2 230 V L 1 2 M 230 V 1 2 M 230 V F1 FIELD DEVICE 1 230 V N 2 230 V L 1 2 M 230 V OPTIONAL AUX TERMINAL PACKAGE XS814 B1 B2 B3 B4 B5 B6 B7 A1 A2 A3 A4 A5 A6 A7 F3 SELECTED INTERNAL CONNECTIONS MIN 0 75 mm 2 MIN 1 5 mm or less as per F3 2 DASHED LINES THIN LI...

Page 17: ...ture 20 70 C at 5 93 r H Humidity 5 93 r h non condensing Current Requirement and Heat Dissipation The LONWORKS Bus I O Modules are equipped with highly efficient switching power supplies which provide for relatively uniform power consumption over a wide range of supply voltages see Table 6 The specific heat dissipation inside the modules amounts to less than 2 W for all models Table 6 Current req...

Page 18: ...bH Böblinger Strasse 17 71101 Schönaich Germany Phone 49 0 7031 637 845 Fax 49 0 7031 637 740 info centraline com www centraline com Subject to change without notice EN0Z 0980GE51 R0119 Dimensions LOCK 89 5 94 1 51 5 45 83 67 5 14 110 XS814 Aux Terminal Package optional 28 30 6 SWIVEL LABEL HOLDER 38 SCREW TYPE TERMINALS Fig 23 CentraLine LonWorks Bus I O Modules example shows Manual Overrides inc...

Reviews: