Honeywell C7355A1050 User Manual Download Page 11

C7355A ROOM IAQ MONITOR

11

31-00434—01

MAINTENANCE & FAULT CHECK

Maintenance

To ensure accurate C7355A data, regular maintenance is 
required in normal use environments. Depending on the 
environment in which it is used, maintenance is usually 
required once every 3 to 6 months. Public places with high 
concentration of dust, dry seasons, pollen seasons, and 
poor environmental cleanliness can shorten the 
maintenance period.

General maintenance includes: cleaning the filter using a 
vacuum cleaner to remove dust inside the filter.

Fault Check

If a fault occurs in a normal use environment, see Table 5 
to troubleshoot. If the fault cannot be eliminated, contact 
the dealer or the manufacturer.

Waste Electrical and Electronic 
Equipment (WEEE)

FCC Part 15 compliant

This device complies with part 1 5 of the F C C Rules. 
Operation is subject to the following two conditions:

(1) This device may not cause harmful interference, and

(2)This device must accept any interference received, 
including interference that may cause undesired 
operation.

Table 5. Fault Check-out.

Fault condition 

Troubleshooting

PM2.5 data abnormal, deviation is too 
large, the value is too high or too low

Check whether there is debris or a lot of dust in the C7355A housing or on the 
air inlet and air outlet.

The CO

2

 data is abnormal, the value is 

too high or too low

The CO

2

 sensor has a self-calibration function inside. Usually the self-

calibration will return CO

2

 values to normal. Self-calibration conditions: The 

CO

2

 concentration is around 400 ppm for at least 4 hours in every 24 periods. 

The self-calibration environment should last for one week.

TVOC's deviation is too large (high or 
low)

TVOC in the environment needs to be stabilized for at least 48 hours after the 
sensor is powered on.TVOC data deviation may be a little large within a short 
time after power is on. TVOC base line deviation may result in large data 
deviation.The equipment can be placed outside the window or outdoors for at 
least 24 hours when the outdoor air is good and clear, allowing TVOC to retrace 
its baseline.

Temperature and humidity deviation is 
too large, the value is too high or low

Check whether the environmental factors surrounding the C7355A have any 
influence, such as direct sunlight, close to the heating or air conditioning air 
outlets, etc.

Temperature and humidity deviation is 
too large; value does not change for a 
long time

Sensor can be powered off and back on to see if the reading returns to normal. If 
value cannot be recovered, contact the dealer or manufacturer.

Communication interruption RS-485 
(Modbus RTU)

Check if the power supply is normal and if the RS-485 terminal is loose. Check 
whether the RS-485 communication line is accidentally cut. Check for an 
inductive load with electromagnetic interference near the equipment or RS-485 
communication line, such as a water pump.

At the end of the product life, dispose 
of the packaging and product in an 
appropriate recycling center.

Do not dispose of the device with the 
usual domestic refuse.

Do not burn the device.

Summary of Contents for C7355A1050

Page 1: ...o ensure reliability The monitor has a three color light ring to indicate different levels of indoor air quality The simple structure and installation makes wall mounting and ceiling mounting both easy and convenient Intended audience and assumed knowledge This document provides information about installing and commissioning the IAQ monitor It is assumed that the user is trained and familiar with ...

Page 2: ... non condensing Overall Dimensions 5 12 in 5 12 in 1 77 in 130 mm 130 mm 45 mm Net weight 0 66 lb 300 g Certification Standard CE FCC IAQ MONITOR AT A GLANCE Light Ring Indicator Overview The image below illustrates the typical face shell of this IAQ monitor There is a circle light ring indicator in the center of the housing This light is used to show the measured air quality Fig 2 Monitor light r...

Page 3: ...uct in a place where water may splash onto it Do not operate the detector with a hard sharp or pointed object such as a fingernail or pen 1 To separate the backplane from the detector rotate the backplane clockwise according to the direction of the arrow See Fig 3 and 4 Fig 3 Fig 4 2 Use a screwdriver to punch out the appropriate opening See Fig 5 Fig 5 3 Pull wires through the opened hole See Fig...

Page 4: ...ng Instructions After installing the monitor and powering it up for initial use or re use the device should be continuously powered for more than 48 hours to ensure stable output of all measured values Complete these steps to configure the detector and connect it to the BMS IMPORTANT Make sure the RS 485 wiring is done before pow ering up Modbus Register Table Mode RTU MSB First Baud Rate 1 4800 2...

Page 5: ...real time measurement 4 R 2 Float Big Endian 0 0 5 000 ppm 22 1010 TVOC real time measurement 4 R 2 Float Big Endian 3 0 4000 mg m3 24 1100 PM2 5 24 hour moving average measurement 4 R 2 Float Big Endian 1 0 1000 0 μg m3 26 1102 PM10 24 hour moving average measurement 4 R 2 Float Big Endian 1 0 1000 0 μg m3 32 1108 CO2 24 hour moving average measurement 4 R 2 Float Big Endian 0 0 5 000 ppm 34 1110...

Page 6: ...ion index level Calculated based on 24 hour moving average measurement 4 R 1 INT16 1 6 1351 PM10 Pollution index level Calculated based on 24 hour moving average measurement 4 R 1 INT16 1 6 1352 CO2 Pollution index level Calculated based on 24 hour moving average measurement 4 R 1 INT16 1 6 1353 TVOC Pollution index level Calculated based on 24 hour moving average measurement 4 R 1 INT16 1 6 78 3 ...

Page 7: ...ta Range Data Description Default 50 1175 PM2 5 hourly average measurement x10 4 R 1 UINT16 1 0 10000 corresponding to 0 1000 0 μg m3 51 1176 PM10 hourly average measurement x10 4 R 1 UINT16 1 0 10000 corresponding to 0 1000 0 μg m3 54 1179 CO2 hourly average measurement x1 4 R 1 UINT16 0 0 5000 corresponding to 0 5 000 ppm 55 1180 TVOC hourly average measurement x1000 4 R 1 UINT16 3 0 3575 corres...

Page 8: ... on the concentration See Table 3 for concentration level DIP switches control the Indicator Lights OFF Three color Indicator Lights and Green Indicator Lights ON Please see Fig 14 and Table 3 62 1200 PM2 5 24 hour moving average measurement x10 4 R 1 UINT16 1 0 10000 corresponding to 0 1000 0 μg m3 63 1201 PM10 24 hour moving average measurement x10 4 R 1 UINT16 1 0 10000 corresponding to 0 1000 ...

Page 9: ...ity Temperature and humidity calibration standard commercial or industrial temperature and humidity calibration standard After the temperature and humidity calibration stan dard and C7355A that needs to be corrected are powered on continuously and synchronously for more than 60 minutes start to record the value of temperature and humidity for 10 minutes use the synchronous average value within 10 ...

Page 10: ...ad 16 Write 3 Read 16 Write 3 Read 16 Write 3 Read 16 Write 3 Read 16 Write Starting point Base 0 4 6 14 12 1224 Data length 2 2 1 2 2 Data type 32 Bit Float Big endian 32 Bit Float Big endian INT16 32 Bit Float Big endian 32 Bit Float Big endian Setting value Standard reading C7355A local temperature measured value Standard reading C7355A local humiditymeasured value Standard reading C7355A local...

Page 11: ...return CO2 values to normal Self calibration conditions The CO2 concentration is around 400 ppm for at least 4 hours in every 24 periods The self calibration environment should last for one week TVOC s deviation is too large high or low TVOC in the environment needs to be stabilized for at least 48 hours after the sensor is powered on TVOC data deviation may be a little large within a short time a...

Page 12: ...lding Technologies In the U S Honeywell 715 Peachtree Street NE Atlanta GA 30308 customer honeywell com buildingcontrols honeywell com U S Registered Trademark 2020 Honeywell International Inc 31 00434 01 M S 10 20 Printed in United States ...

Reviews: