Honeywell C7110C1040 Manual Download Page 2

C7110C1040 AND C7110C1080 WALL MODULES – PRODUCT DATA 

EN0B-0775GE51 R0619 

 

TECHNICAL DATA 

General 

Power supply (terminals 
1+3) 

24 VAC ± 20%; 50/60 Hz or 
24 VDC ± 30%; 1.5 W 

Power-up time 

≤ 60 sec (incl. self-diagnostics) 

Ambient operating limits  0…50 °C, 0…95% rh, non-cond. 
Storage limits 

-40…+70 °C, 0…95% rh, non-cond. 

Sensor life expectancy 

> 15 years, maintenance-free 

 

Classification according to EN 60730-1 

EN 60730 sub part 

EN 60730-2-9 

Environmental conditions  For use in residential, commercial, 

and light-industrial environment 

Pollution degree 

Class 2 

Protection against shock  Class III 
Software class 

Automatic action 

Type 1 action 

 

Classification according to EN 60529 

Degree of protection 
provided by enclosures 

IP20 

 

CO2 Measurement 

Range 

400…2000 / …3000 ppm 

Output (terminals 1-2) 

0…10 VDC for max. ±2 mA 

Accuracy 

factory-calibration ±50 ppm or ±5% 
of measurement range 

Pressure dependence 

+1.6% per kPa deviation from 
normal pressure of 100 kPa 

Response time 

90% penetration within 2 min 

 

MOUNTING 

  WARNING 

Risk of electric shock or equipment damage!

 

► 

Do not touch any live parts. 

► 

Disconnect power supply before making connections. 

► 

Do not reconnect power until installation is complete. 

► 

Observe precautions for handling electrostatic sensitive 
devices. 

 

 

1. 

Remove the cover (see Fig. 2). 

2. 

Mount the socket onto the wall approx. 1.5 meters above 
the floor. 

3. 

Connect the wires to the terminals. Do not connect the 
power supply until all connections and settings have been 
correctly completed. 

4. 

Remount the cover. 

 

2

1

LIFT

PRESS

 

Fig. 2. Removing the cover 

 

Summary of Contents for C7110C1040

Page 1: ...esired air quality while during low occupancy periods the unnecessary conditioning of air can be avoided or reduced FEATURES Fully compatible with the Honeywell controllers CO2 sensor employing state of the art Non Dispersion Infrared NDIR technology Selectable CO2 measurement range of 400 2000 3000 ppm Self calibrating automatic drift correction ABC algorithm based on long term evaluation Interna...

Page 2: ...gree of protection provided by enclosures IP20 CO2 Measurement Range 400 2000 3000 ppm Output terminals 1 2 0 10 VDC for max 2 mA Accuracy factory calibration 50 ppm or 5 of measurement range Pressure dependence 1 6 per kPa deviation from normal pressure of 100 kPa Response time 90 penetration within 2 min MOUNTING WARNING Risk of electric shock or equipment damage Do not touch any live parts Disc...

Page 3: ...irst removing power In a normal environment the unit is maintenance free Accurate measurement is guaranteed by the built in ABC self calibration feature see below Setting Range to 2000 ppm or 3000 ppm 2000 ppm When the configuration jumper is set to the factory default position of 2000 ppm see Fig 8 or to any other position except 3000 ppm see Fig 5 the CO2 measuring range is 400 2000 ppm 3000 ppm...

Page 4: ...aring the lowest measured value over the last 7 5 days with the expected fresh air level 400 ppm When the configuration jumper is set to the factory default position of 2000 ppm or to 3000 ppm the wall module will operate normally and perform ABC Fig 8 Default setting ABC ON adjacent LED flashes GREEN for first 10 s after power restoration NOTE In buildings featuring plastered walls ceilings or ot...

Page 5: ... Threshold Level ppm SERVICE LED MAX OFF SERVICE LED IS LIT SERVICE LED FLASHES MIN SERVICE LED IS DARK 50 1000 ppm ACTUAL CO2 CONCENTRATION EXAMPLE Fig 11 Configuration potentiometer e g set to 50 1000 ppm The CO2 output can operate in two modes To select the Sensor Output mode analog set the configuration potentiometer to OFF default setting see Fig 11 See also Fig 12 To select the Relay Output ...

Page 6: ...o 400 ppm given measured concen trations below 400 ppm the output signal will gradually rise to 2 V The Relay Output Mode In the Relay Output mode digital the Service LED see Fig 11 will either flash or be lit continuously thus indicating the actual Threshold Level setting 10 V 500 ppm 1000 ppm 0 V HYSTERESIS 100 ppm CO2 LEVEL 2000 3000 ppm MIN MAX SERVICE LED IS OUTPUT OF TERMINAL 2 Fig 13 Relay ...

Page 7: ... Dark S O Calibration successful Lit continuously S O Calibration failed Dark S O CO2 1000 ppm Dark S O CO2 1000 ppm Flashing R O CO2 threshold Lit continuously R O CO2 threshold S O R O ABC ON S O R O ABC OFF OCC BYPASS BUTTON C7110C1080 ONLY AND CALIBRATION LED The functionality of the occupancy bypass button C7110C1080 only and the corresponding behavior of the calibration LED are dependent upo...

Page 8: ... 0 7031 637 01 Fax 49 0 7031 637 740 http ecc emea honeywell com EN0B 0775GE51 R0619 Subject to change without notice ACCESSORIES order no description T7460LONJACK Module for access to external buses 5 pc set T7460 LONJACK The T7460 LONJACK ordered separately is a small board with a 3 5 mm jack When mounted to the Printed Circuit Board see Fig 14 it provides easy access to external buses Order qua...

Reviews: