background image

C7005A,B GAS PILOT AND FLAME ROD ASSEMBLIES

60-2033—3

7

Table 1. Flame Signal For C7005A,B.

Flame  

Signal

Amplifier

Flame Safeguard  

Control

Minimum

Acceptable

Steady Current

(uA)

Maximum

Expected

Current  

(uA)

Minimum

Acceptable

Steady voltage

(Vdc)

Maximum

Expected

Steady voltage

(Vdc)

R7247A

BC7000L; R4140G,L,M; R4138C,D;  

2.0

5.0

R4075C,D,E

R7247B

a

AMPLI-

CHECK™

BC7000L; R4140G,L,M; R4138C,D;
R4075C,D,E

1.25

2.50

R7257A

R4150

2.0

5.0

R7289A

R4795

2.0

5.0

R7847A

RM7800E,G,L,M; RM7838A,B;  
RM7840E,G,L,M; RM7885A;  
RM7890A,B; RM7895A,B,C,D

1.25

5.0

R7847B

AMPLI-

CHECK™

RM7800E,G,L,M; RM7838A,B;  
RM7840E,G,L,M; RM7885A;  
RM7890A,B; RM7895A,B,C,D

1.25

5.0

None

RA890F, R7795B,D,F,H; R7023B,
R485

2.0

5.0

None

R4181

b

8.0

15.0

a

Set W136A selector switch to SPL (damped) position to read current.

b

Press test button while reading current.

Measure the flame signal for the pilot alone, the main burner
flame alone, and both together (unless monitoring only the
pilot flame when using an intermittent pilot, or only the main
burner flame when using direct spark ignition). Also measure
the flame signal at high and low firing rates and while
modulating in between (as applicable). With the detector in its
final position, all required flame signals must be steady (or
stable) and as specified in Table 1.

If the signal is unstable or less than the minimum acceptable
current, check the flame rod installation and circuitry:

Check the supply voltage at terminals L1-L2 on the wiring
subbase or terminal strip for the flame safeguard control.

Check the wiring for defects including:
— wrong type or size of wire.
— deteriorated wire.
— open circuits.
— short circuits.
— leakage paths caused by moisture, soot, or

accumulated dirt.

Make sure:
— there is enough ground area.
— the flame rod is properly located in the flame.
— temperature at the flame rod insulator is no greater

than 500

°

F (260

°

C).

— ignition interference is not present (see Ignition

Interference Test below).

Make sure that the flame adjustment is not too lean.

If necessary, reposition the flame rod.

If you cannot obtain proper operation, replace the plug-in
amplifier if applicable. If you still cannot obtain proper
operation, replace the flame rod.

Pilot Turndown Test

If the flame rod is used to prove a pilot flame before the main
fuel valve can be opened, perform a Pilot Turndown Test.
Follow the Instruction procedures for the appropriate flame
safeguard control, and the burner manufacturer’s instructions.

Ignition Interference Test

C7005B

Test to make certain that a false signal from the spark ignition
system is not superimposed on the flame signal.

Ignition interference can subtract from (decrease) or add to
(increase) the flame signal. If it decreases the flame signal
enough, it causes safety shutdown. (The flame relay will not
pull in and the flame safeguard control will act as though the
pilot or main burner, if using direct spark ignition, has not
been ignited.) If it increases the flame signal, it could cause
the flame relay to pull in when the true flame signal is below
the minimum acceptable value.

Test

Start the burner and measure the flame signal with both
ignition and pilot or main burner on, and then with only the
pilot or main burner on. Any significant difference greater than
0.5 microamp, or 0.25 Vdc with 7800 SERIES controls,
indicates ignition interference.

To Eliminate Ignition Interference

A

Make sure there is enough ground area.

B

Be sure the ignition electrode and the flame rod are on
opposite sides of the ground area (Fig. 1).

Summary of Contents for C7005A

Page 1: ...on the flame retention type pilot head provide the correct ratio of flame rod area to ground area for maximum flame signal and are beneficial in stabilizing the pilot flame Pilot flame retention nozzle and mixing tube are threaded internally 1 2 14 NPT and 3 8 18 NPT respectively and can be assembled with standard pipe fittings Pilot can be installed in vertical horizontal or inclined position Raj...

Page 2: ...Flame retention type with stainless steel bomb type fins Threaded onto 1 2 x 6 inch 152 mm pipe nipple with 1 2 14 NPT external threads Type of Gas Models available for use with natural and propane gases Gas Capacity Varies with Gas Pressure Gas Pressure in wc Capacity kPa ft3 hr m3 hr 3 0 75 12 0 0 34 4 0 99 13 7 0 39 5 1 24 15 3 0 43 6 1 49 16 8 0 48 7 1 74 18 2 0 52 Flame Rod Ignition Electrode...

Page 3: ...burner flame and pilot flame Do not position the flame rod so it can detect a weak pilot flame that is incapable of igniting the main burner Fig 2 IMPORTANT To assure an adequate pilot flame to ignite the main burner you MUST perform the pilot turndown test as described in the instructions for the flame safeguard control Install the pilot so the pilot flame has full contact with the gas stream fro...

Page 4: ...icient spacing is usually available so the pilot can be mounted as illustrated in Fig 5 to simultaneously light as many burners as possible If available space does not allow central mounting within the burner box see Fig 3 M3036 THE FLAME ROD SHOULD BE LOCATED ON EITHER SIDE OR BELOW THE PILOT NOTE W R O N G M3038 Fig 2 Improper position of flame rod M3037 Fig 4 Typical mounting of gas pilot and f...

Page 5: ...lt ignition transformer with the same electrical ratings as the power supply of the flame safeguard control Select the appropriate Honeywell transformer or its equivalent For 120V 60 Hz use part no 22042 For 240V 60 Hz use part no 101079 Connect the primary leadwires of the ignition transformer between the ignition and the L2 terminals of the flame safeguard control Connect the ignition electrode ...

Page 6: ...to 4 times a second from bright to dim If the lamp is on or off continuously while reading the flame signal replace the amplifier Fig 8 Measuring flame signal voltage of 7800 SERIES control G The meter reading must be as specified in Table 1 after all tests are completed and all adjustments are made With the Honeywell 7800 Series controls the flame signal is measured in Vdc The voltage flame signa...

Page 7: ...s caused by moisture soot or accumulated dirt Make sure there is enough ground area the flame rod is properly located in the flame temperature at the flame rod insulator is no greater than 500 F 260 C ignition interference is not present see Ignition Interference Test below Make sure that the flame adjustment is not too lean If necessary reposition the flame rod If you cannot obtain proper operati...

Page 8: ...ast one complete cycle to verify operation OPERATION The C7005B Gas Pilot and Flame Rod Assembly includes an ignition electrode and a flame rod The operation of these two electrodes in a simple electrically operated gas pilot installation is as follows At the beginning of the starting cycle a high voltage from the secondary winding of the ignition transformer is applied to the ignition electrode A...

Reviews: