 Thermostatic Control

The T104F Thermostatic Control is used with a V110

Valve Body to control radiators, convectors, baseboard
heating units, or other heating units with standard capacity
requirements. The control is self-powered and requires no
electrical connection. The T100A includes a setpoint dial
and valve actuator, connected by a capillary tube to a sensor.
The T104F Control attaches to the valve body by threaded
connections and may be mounted at any angle. Install the
remote sensor beneath the heating coils in the cold air re-
turn, or on a nearby wall where the air flow is not restricted.

The setpoint dial has reference marks (1-6). The control

has a low limit of 43

°

F (6

°

C) when the dial is turned fully

clockwise to the frost protection mark*. The red button
indicates the 68

°

F (20

°

C) setpoint limit. Higher settings may

be made by holding in the button while turning. The thermo-
static sensor is protected by a safety spring against tempera-
tures to 125

°

F (52

°

C).

M9730

2

3

Specifications

MATERIALS OF CONSTRUCTION:

Body: Industrial grade plastics with low thermal

conductivity.

Fastening Ring: Plated brass.
Internal Parts: Brass thermostat capsule, other metals.

TEMPERATURE RANGE: 43

°

 to 79

°

F (6

°

 to 26 

°

C).

MAX. SENSOR TEMPERATURE: 125

°

F (52

°

C).

MAX. OVERALL DIMENSIONS: 2-1/8 in. (54 mm) wide,

3-5/16 in. (84 mm) long. See Fig. 1.

CAPILLARY LENGTH: 6 ft. 8 in. (2 m).
TEMPERATURE SETTINGS:

These are the setpoint temperatures, which correspond

to the setpoint dial reference marks, under ideal conditions.
Factors affecting the temperature at the sensor vary for each
installation. It may be necessary to adjust the setpoint
higher or lower to obtain the desired space temperature.

Fig. 1—T104F dimensions in in. (mm).

AVAILABLE VALVE BODIES:

See Fig. 2.

Temperature

0

*

1

2

3

4

5

6

°F

Off 43 46 54 61 68 73 79

°C

Off

6

8

12 16 20 23 26

3 5/16 
(84)
MAX.

2 1/8 (54)

M9731

Summary of Contents for Braukmann T104F

Page 1: ...icatesthe68 F 20 C setpointlimit Highersettingsmay be made by holding in the button while turning The thermo staticsensorisprotectedbyasafetyspringagainsttempera tures to 125 F 52 C M9730 2 3 Specifications MATERIALS OF CONSTRUCTION Body Industrial grade plastics with low thermal conductivity Fastening Ring Plated brass Internal Parts Brass thermostat capsule other metals TEMPERATURE RANGE 43 to 7...

Page 2: ... VALVE BODIES V110E V110F Fig 3 T104A B C V Thermostatic Controls T104B T104C T104A T104V M9736 1 2 3 4 5 1 2 3 4 5 2 3 Installation IMPORTANT TheT104Fcanbemountedinsideanenclo sureifthesensorislocatedaminimumof3in 76mm beneath the heating coils in the cold air return Coil excess capillary tubing beneath and away from the heating coils Take care not to break kink or sharply bend the capillary tubi...

Page 3: ...gh limit settings are desired Setting the Limit To set a limit different from the factory setting proceed as follows 1 Determine the desired temperature range limit or lock ing temperature Select the appropriate number on the ad justment knob to match the desired temperature setting See Fig 5 Fig 5 Temperature settings M9729 SCALE MARKING ADJUSTMENT RANGE SETTING OFF OFF PIN POS TEMP RANGE F TEMP ...

Page 4: ...romthewhitemark unscrewthe head completely from the base and rethread the head to the base so that it is aligned with the white mark Turn the act uatorheadclockwiseuntiltheheadstops Completeremoval of the head from the base is required only if the actuator was previously dismantled NOTE Thedistancebetweentheactuatorheadandthestatic portion of the control should be approximately 3 8 in 9 mm 4 Turn ...

Page 5: ...y tube is broken kinked or bent sharply 3 Replace the control 4 Dirt or scale is under the seat preventing tight shutoff 4 Remove the control from the valve body allowing the valve to open fully and flush away scale and debris Reinstall the control and turn fully clock wise If the valve does not fully close remove con trol and cartridge using a cartridge changer tool or service socket isolate valv...

Page 6: ...nn Honeywell Braukmann Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in Germany www honeywell ca braukmann ...