Summary of Contents for Braukmann D06G

Page 1: ...stallation and application FEATURES Noncorroding unitized cartridge contains all working parts and is easily replaceable Outlet pressure range from 15 to 130 psi in all models inlet rating 400 psi Includes built in strainer and thermal bypass Narrow design to accommodate restricted installation requirements Balanced seat construction provides superior pressure regulation Inlet and outlet are inter...

Page 2: ... Design Balanced single seat Inlet Pressure Maximum 400 psi Reduced Pressure Range 15 to 130 psi all models Outlet Pressure Factory set at 60 psi Differential 14 psi minimum for optimum regulation Reduced Ratio 10 1 maximum Temperature Maximum 180 F 82 C Ambient Temperature Range 33 F to 140 F 1 C to 60 C Pipe Sizes Available 1 1 2 and 2 in Connections All models have internal NPT on inlet and out...

Page 3: ...nting in the direction of water flow any mounting orientation is acceptable The D06G can be installed directly onto a pipe using the female NPT threads on each end or by using single or double unions if required One union is provided CAUTION Heat from soldering can damage internal parts Always remove tailpiece or solder adapter prior to soldering Open the supply valve slowly and open the downstrea...

Page 4: ...seal by placing the U seal on the strainer support and pushing the assembly into place The U seal open end must face the strainer support Fig 7 Replace the strainer onto the strainer support Assemble the strainer cup O ring onto the strainer cup and insert the assembly into the body of the valve Tighten securely using the service tool Do not over torque 쐅 Replace the new cartridge ensuring the O r...

Page 5: ...rainer support Do not remove the U seal Clean the strainer cup and the strainer Replace the strainer on the strainer support Insert the assembly into the valve Assemble the strainer cup O ring onto the strainer cup and insert the assembly into the body of the valve Tighten securely using the service tool Do not over torque M11215 REMOVE STRAINER CUP USING MT06A SERVICE TOOL BONNET ASSEMBLY SPRING ...

Page 6: ...ssure is set the D06G automatically regulates to maintain the downstream pressure TROUBLESHOOTING Table 2 is a troubleshooting guide for the D06G Pressure Regulating Valves Table 2 Troubleshooting D06G Pressure Regulating Valves Problem Probable Cause Solution Will not hold pressure or pressure gradually rises a Thermal expansion b Debris on valve seat c Damaged valve seat a Install a thermal expa...

Page 7: ... Union Kit NPT 1 1 2 in includes female NPT threaded tailpiece union nut and gasket and fits all 1 1 2 in D06 and DS06 Valves K06U5034 Union Kit Sweat 1 1 2 in includes sweat tailpiece union nut and gasket and fits all 1 1 2 in D06 and DS06 Valves K06U1045 Union Kit NPT 2 in includes female NPT threaded tailpiece union nut and gasket and fits all 2 in D06 and DS06 Valves K06U5042 Union Kit Sweat 2...

Page 8: ...imited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 Helping You Control Your World 62 3051 G H 11 96 Printed in U S A Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 www honeywell ca braukmann www sparco inc com ...