M7484A

OPERATION AND CHECKOUT

OPERATION

The M7484A is a fixed 90

°

 stroke nonspring return

motor. An internal sensing circuit incorporates a feedback
potentiometer in a bridge circuit. The feedback potenti-
ometer circuit output is proportional to the mechanical
shaft position. An 8 Vdc power source from the BCS 7700
is required for circuit operation.

The M7484A is driven by applying 24 Vac to either the

open or closed motor coils. Position control is accom-
plished by using the BCS 7700 to monitor the feedback
potentiometer circuit and energize or de-energize the
drive coil(s) to achieve the required position.

CHECKOUT

After installation and linkage adjustment, check the

entire motor and control hookup to prove that:

— the motor properly operates the damper or valve.
— the motor properly responds to the BCS 7700.
Inspect the motor, linkage and valve or damper to

determine that all mechanical connections are correct and
secure. Be sure the pushrod does not extend more than a
few inches past the ball joints. Check to be sure there is

Operation and Checkout

adequate clearance for the linkage to move through its
stroke without binding or striking other objects.

The M7484A is shipped in the fully closed position (the

limit of counterclockwise rotation as viewed from the
power end of the motor).

To check operation of the M7484A:
1. Place the BCS 7700 in Standby; open the Burner

Switch.

2. Place the RUN/TEST Switch in the TEST position.
3. Place the BCS 7700 in the Manual mode using the

AUTO/MANUAL key of the Keyboard and Display Mod-
ule.

4. Place the cursor in the Keyboard and Display Mod-

ule Liquid Crystal Display beneath % Rate, using the (<)
key.

5. Using the Keyboard and Display Module (+ or - )

keys, under manual control, drive the motor through its
entire stroke to assure the motor is responding to the BCS
7700 commands.

6. While manually adjusting the motor position, ob-

serve the position of the motor, as displayed on the
Keyboard and Display Module, to assure proper operation
of the feedback potentiometer circuit.

Printed in U.S.A.

Home and Building Control

Home and Building Control

Helping You Control Your World

Honeywell Inc.

Honeywell Limited—Honeywell Limitée

1985 Douglas Drive North

740 Ellesmere Road

Golden Valley, Minnesota  55422

Scarborough, Ontario
M1P 2V9

QUALITY IS
KEY

Summary of Contents for BCS 7700 Series

Page 1: ...ectronic vibration resistant drive circuit Requires 24 Vac power supply Die cast aluminum case Feedback potentiometer circuit provides position indication input to the BCS 7700 Motor stroke is fixed 90 30 second timing Low and High Fire position proving feedback potentiometer circuit 150 lb in torque Accessories include weather proofing kit CONTENTS Specifications 2 Ordering Information 2 Installa...

Page 2: ...g Control Customer Satisfaction Honeywell Inc 1885 Douglas Drive North Minneapolis Minnesota 55422 4386 612 542 7500 In Canada Honeywell Limited Honeywell Limitee 740 Ellesmere Road Scarborough Ontario M1P 2V9International Sales and Service Offices in all principal cities of the world Manufacturing in Australia Canada Finland France Germany Japan Mexico Netherlands Spain Taiwan United Kingdom U S ...

Page 3: ...484A dimensions in in mm WIRING BOX BASE MOTOR AUXILARY END POWER END ADAPTER BRACKET 1 25 32 2 50 64 1 75 44 15 4 76 19 2 59 66 5 39 137 6 45 164 1 5 38 2 4 61 60 15 4 88 124 5 5 140 80 20 4 06 103 50 13 96 24 27 7 1 47 37 7 3 185 M2616 75 19 ...

Page 4: ...istancewhenthemotormovesthrough its full stroke 2 Stop the motor at the end of its stroke by using internal travel limit switch do not stall the motor by using the damper or valve CAUTION The motor will be damaged if it is not permitted to complete its full stroke 3 For any installation do not exceed the motor rat ings WIRING Disconnect power supply before wiring to prevent electrical shock or equ...

Page 5: ...OT VALVE IGNITION TRANSFORMER OIL MAIN VALVE GAS PRESSURE SENSOR TEST VALVE GAS MAIN VALVE KEYBOARD AND DISPLAY LIQUID CRYSTAL DISPLAY MICROCOMPUTER A B C A B C KEYBOARD 120VAC 24VAC 40VA INDICATES FEEDBACK SENSING TO OPTOISOLATORS WIRING SHOWN FOR INFRED FLAME DETECTOR FOR C7027 ULTRA VIOLET FLAME DETECTOR WIRE AS NOTED BELOW ULTRA VIOLETDECTECTOR BLUE LEAD TERMINAL 31 ULTRA VIOLET DETECTOR WHOTE...

Page 6: ...e is Operation and Checkout adequate clearance for the linkage to move through its stroke without binding or striking other objects TheM7484Aisshippedinthefullyclosedposition the limit of counterclockwise rotation as viewed from the power end of the motor To check operation of the M7484A 1 Place the BCS 7700 in Standby open the Burner Switch 2 Place the RUN TEST Switch in the TEST position 3 Place...

Reviews: