Aquastat L4006,7,8;L6006,7,8
13 60-2104—01
L1
(HOT)
L2
1
3
4
2
1
2
3
4
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
L6006C USED AS HIGH LIMIT CONTROL.
L6006C USED AS AN OPERATING CONTROL.
R-B OPENS, R-W CLOSES ON TEMPERATURE RISE.
M8960C
PROTECTORELAY
CONTROL
HIGH LIMIT
CONTROLLER
CIRCULATOR
AND LOW
LIMIT CONTROL
W
R
B
1
2
4
3
T
T
IGNITION
BURNER
MOTOR
24V
THERMOSTAT
SWITCHING RELAY
CIRCULATOR
LINE VOLTAGE
LOW VOLTAGE
Fig. 22. Typical oil-fired hydronic system with domestic
hot water. Use with L4006A,B; L6008A.
L1
(HOT)
L2
1
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
SELECT MODELS HAVE 1/4 IN. (6) TAB TERMINAL FOR W TERMINAL.
L4008A OR E
HIGH LIMIT
CONTROLLER
L6008A CIRCULATOR
LOW LIMIT CONTROLLER
R
W
B
CIRCULATOR
IGNITION
TRANSFORMER
RA89A RELAY
RA817A
PROTECTORELAY
CONTROL
BURNER MOTOR
24V THERMOSTAT
2
1
3
4
T
T
1
2
3
4
M8785C
2
Fig. 24. Typical connection diagram for an oil-fired,
hydronic heating system that provides year-round
domestic hot water using RA817A.
Fig. 23. Typical oil-fired hydronic heating system that
provides year-round domestic hot water using RA832A.
Use with L4006A,B; L6008A.
L1
(HOT) L2
1
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
WHEN USING CIRCULATOR LOW LIMIT CONTROL,
REMOVE L1-L2 JUMPER.
2
L6006
CIRCULATOR
AND
LOW LIMIT
CONTROL
L1
L2
3
T
T
R
W
B
B
R
C1
C2
B1
B2
SERIES 80
THERMOSTAT
L8148A
CIRCULATOR
PILOTSTAT
LINE VOLTAGE
GAS CONTROL
OIL BURNER RELAY
LINE VOLTAGE
TERMINALS
1
1
2
2
1
2
M8783D
LOW VOLTAGE
LINE VOLTAGE
Fig. 25. Typical wiring hookup using L6006 or L6007
with L8148A. Use with L4006A,B; L6008A.
WIRING
1
2
3
4
T
T
IGNITION
BURNER
L4006B OR L4007B
CIRCULATOR
AQUASTAT
CONTROLLER
CIRCULATOR
L4006A OR L4007A LOW LIMIT
AQUASTAT CONTROLLER
L1
(HOT)
L2
L4006A OR L4007A
HIGH LIMIT
AQUASTAT
CONTROLLER
24 VOLT
THERMOSTAT
RA832A
SWITCHING RELAY
PROTECTORELAY
CONTROL
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
USE L4006E FOR MANUAL RESET.
1
2
M2855C
T
T
X
X
4
2
1
1
2
®
®
®