The parameters in the installer’s configuration menu must be modified by qualified
personnel only. Incorrect settings can result in property damages.
1.
Remove the thermostat from its base.
2.
Place switch 2 on the back of the thermostat in the up position (Installer mode).
3.
Return the thermostat to its base. The first parameter is displayed.
4.
To modify a parameter, press either of the
buttons.
5.
To view the next parameter, briefly press the backlight button.
6.
To exit the menu, place switch 2 back to its initial position.
The parameters appear in the order shown in the following table.
Installer’s Configuration Menu
Parameter
Default setting
Range
Minimum setpoint temperature
41 °F (5 °C)
41 °F (5 °C) to 100 °F (38 °C)
Maximum setpoint temperature
100 °F (38 °C)
41 °F (5 °C) to 100 °F (38 °C)
Freeze Protection temperature
41 °F (5 °C)
41 °F (5 °C) to 100 °F (38 °C)*
Minimum floor limit
41 °F (5 °C)
41 °F (5 °C) to 100 °F (38 °C)
Maximum floor limit
100 °F (38 °C)
41 °F (5 °C) to 100 °F (38 °C)
* The Freeze Protection temperature range is set by the minimum and maximum setpoint temperatures.
For example, if you change the minimum setpoint temperature to 50 °F (10 °C), you cannot then set the
Freeze Protection temperature lower than 50 °F (10 °C).