Honeywell ADEMCO 745 3 Series Installation And Setup Manual Download Page 2

¬19Ul

N9080-1V2  3/04 

multiple speaker systems, cutting any speaker will trip the 
control panel’s supervision zone.  In parallel-connected 
speaker systems, each branch must be cut before the control 
panel’s supervision zone will trip.  Note:  The Supervision 
option has been determined to be compatible with the 
controls listed in Table 2.   

2 B/F:  BURGLARY/FIRE INPUT: 

Connect the control panel’s Burglary (steady) Output to this 
terminal.  This terminal may also be used to trip the FIRE 
message if the control provides a pulsing output for fire (re-
programming may be required).  In this case, no connection 
to terminal 3 is required.   

3F:  FIRE INPUT:   

Connect the control panel’s output designation as the FIRE 
(steady) Output to this terminal (unless this output was 
connected to terminal 2).   

4 SPKR & 5 SPKR:  SPEAKER TERMINALS: 

Connect an 8-ohm, 16-ohm, or 32-ohm 15-watt speaker to 
these terminals.  See Figure 3 for multiple speaker 
configurations.  For UL installations, the Listed Ademco 
705-820, 713, or 746-32 speakers must be used.   

6(+):  12VDC(+) POWER INPUT: 

Connect to a 12VDC (+) source on the control.  

 

7(-):  GND(-) GROUND INPUT: 

Connect to a ground point (-) on the control panel.   

Speakers Specifications

:  Use compatible speakers above.   

Sound Output:  85 dB minimum @10 ft.   
Current Drain (max):   

8-ohm Speaker:  1400 mA (steady siren) 
12-ohm Speaker: 1050 mA (steady siren) 
16-ohm Speaker:  875 mA (steady siren) 
32-ohm Speaker:  500 mA (steady siren) 

Important

:  

The 745x3 must be mounted in the control 

cabinet.   

745x3-001-V0

SPEAKER

8

SEE

TABLE

1

JP2
JP3

JP6
JP7

JP4
JP5

JP1

BURG & FIRE

INPUT SIGNAL

INTACT = HIGH

CUT = LOW

FIRE
BURG

SPEAKER SUPERVISION

CONNECT TO (+) SIDE OF

24 - HR ZONE ON CONTROL.*

TO BURGLARY/FIRE ALARM

OUTPUT ON CONTROL.**

TO FIRE ALARM

OUTPUT ON CONTROL

*IF EOLR SUPERVISION DESIRED ON THIS ZONE,

USE APPROPRIATE EOLR IN ACCORDANCE WITH

THE CONTROL'S INSTRUCTIONS.

**IF THE ALARM OUTPUT IS 

STEADY

 FOR BURG AND 

PULSING

FOR FIRE, NO CONNECTION IS NEEDED AT TERMINAL 3.

4

3

6

5

7

2

1

12VDC

GND

VOICE
SIREN

DRIVER

 

Figure 1.  Siren Driver Board 

745x3-002-V0

VOICE
SIREN

DRIVER

7(  )

6(  )

CONTROL

GROUND

12V (   )

POS

(   )

NEG

(   )

2 AMP

IN-LINE FUSE

BATT

 

Figure 2.  Connecting Power from the System’s Battery 

(Not applicable for UL installations) 

745x3-003-V0

2 SPEAKERS

16 OHM

LOAD

4 SPEAKERS
8 OHM LOAD

3 SPEAKERS

12 OHM

LOAD

8

8

8

8

8

8

8

8

8

5

4

5

4

5

4

 

Figure 3.  Typical Multiple Speaker Configurations 

Table 2.  Wiring Connections For Honeywell Ademco 

Control Panels* 

 

REFER TO THE INSTALLATION INSTRUCTIONS FOR THE 
CONTROL PANEL THAT IS USED WITH THIS DEVICE FOR 
WARRANTY INFORMATION AND LIMITATIONS OF THE 
ENTIRE ALARM SYSTEM.   

165 Eileen Way, Syosset, New York 11791

Copyright © 2004 Honeywell International, Inc.

www.honeywell.com/security

 

745x3 TERMINALS 

ADEMCO 

CONTROL 

PANEL 

1 2 

4110 

4110XM 

VISTA-10P/15P/20P 

VISTA-10SE/20SE 

– 

Splice to Red BATT 

lead thru 2A fuse  

(see Fig. 2).   

For UL 

Installations, use 

the 32-ohm speaker 

(746-32) and 

connect to +12V 

LUG 

4140XM 8 

– 

+12V 

LUG 

15 

4140XMP 

4140XMPT 

VISTA-40/ 

VISTA-50P 

VISTA-128B/BP 

OPTION

AL S

P

KR

 S

U

PERVIS

ION

 

(C

ON

N

ECT T

O

 2

4

-H

Z

O

N

E

4 – 

S

P

EAKER CO

N

N

E

CTION

S

 

Splice to RED 

BATT lead thru 2A 

fuse  

(see Fig. 2). 

For UL 

Installations, use 

the 32-ohm speaker 

(746-32) and 

connect to +12V 

LUG. 

*  For further information, consult the control panel’s instructions.   

Note:

  If using the 745x3 with a control with a built-in siren 

driver, consult that control’s instructions to determine the method 
to disable the built-in siren driver and enable the bell output.   

Reviews: