Smoke Detector Trouble Conditions 

 
There are several different models of Smoke Detectors. If yours is not listed below, please refer 
to the 

Peripheral Device Manual

 

page to locate the user’s manual for your device. 

 
 

Ademco Honeywell 5806 W3 

 
 
These Trouble Conditions apply to the 

Ademco Honeywell 

5806W3

 wireless smoke detector. This smoke detector has 2 

LEDs and a sounder to indicate the detector’s status. 
 
 
 
 

State 

Green LED  Red LED 

Sounder 

Action 

Normal 
(standby) 

Blinks every 

10 seconds 

Off 

Off 
 
 

The device is operating normally. No 
action needed. 

Smoke Alarm 

Off 

Blinks every 

1 second 

Pattern 
 
 

Smoke has been detected. ADT has 
been contacted. Press the recessed 
test switch to silence the smoke 
detector sounder for 5 minutes. If 
necessary, silence the alarm keypad.  
 
Remove the source of the smoke, if it 
can be done safely. If necessary, fan 
the smoke detector for a few minutes 
to further dissipate any smoke or 
particles. If the device still indicates a 
problem, it may be necessary to clean 
it. Please refer to Caring for Your 
Smoke Detector below. 

Thermal 
Alarm (>135

o

Off 

Blinks every 

4 seconds 

Pattern 

The unit has detected that the 
temperature is above 135

o

F. ADT has 

been contacted. Press the recessed 
test switch to silence the smoke 
detector sounder for 5 minutes. If 
necessary, silence the alarm keypad. 
 
Remove the source of the heat, if it 
can be done safely.  

Freeze 
Trouble 
(<41

o

Off 

Blinks every 

10 seconds 

Off 
 
 

The unit has detected that the 
temperature is below 41

o

F, which 

could lead to a freeze situation within 
the premises. Investigate the cause 
and resolve. 

Summary of Contents for Ademco 5806 W3

Page 1: ...ed test switch to silence the smoke detector sounder for 5 minutes If necessary silence the alarm keypad Remove the source of the smoke if it can be done safely If necessary fan the smoke detector for a few minutes to further dissipate any smoke or particles If the device still indicates a problem it may be necessary to clean it Please refer to Caring for Your Smoke Detector below Thermal Alarm 13...

Page 2: ...tery Replacement page Power Up Blinks every 5 seconds Blinks every 5 seconds Off The device is powering up The lights will blink for approximately 20 seconds until the unit has completed the power up cycle Out of Sensitivity Off Blinks every 5 seconds Off A problem has been detected with the smoke detector The smoke detector compensates for long term changes in the environment resulting from dust ...

Page 3: ...r sounder for 5 minutes If necessary silence the alarm keypad Remove the source of the heat if it can be done safely Trouble Off Chirp Trouble signal A problem has been detected with the smoke detector The smoke detector compensates for long term changes in the environment resulting from dust and other factors This automatic compensation may need to be reset Please refer to the DSC WS4916 manual f...

Page 4: ... visible button 3 Depress the Test Button if present For a recessed test switch use a small screwdriver or Allen key no more than 0 18 diameter to push and hold the recessed test switch for at least 5 seconds The smoke detector LED should blink once per second and the smoke detector sounder not the system siren sound within 3 seconds indicating that the detector is functioning properly Remove the ...

Page 5: ...iness of the heat detector please refer to the Contact Us page How They Work Smoke Detectors There are three common styles of Smoke Detectors Ionization Detects fast flaming fires caused by chemicals petroleum based products paper and wood It is equipped with two metal plates and a small amount of radioactive material to ionize air When smoke passes through the device it interrupts the ionization ...

Page 6: ...stalled normally in areas such as garages basements attics kitchens boiler rooms bathrooms and smoking areas They are used for property protection and not life safety Caring for the Smoke Detector Your smoke detector is sensitive to dust and particles in the air False alarms can occur if activities creating excess dust or smoke are performed near the detector To avoid false alarms before performin...

Page 7: ...ps into place 11 Reinstall the battery into the battery compartment noting proper orientation The red and green LEDs will flash once every 5 seconds for approximately 20 seconds until the power up cycle is complete 12 Reinstall the detector housing onto the base 13 Test the smoke detector Please refer to Testing the Smoke Detector below 14 Remove your system from Test mode Please refer to the Syst...

Page 8: ...ot paint the heat detector Related Topics Smoke and Heat Detector Battery Replacement Here is information on how to replace the battery in your device Finding the Right Peripheral Battery Here you can locate the correct size and type of battery for your device System Panel Troubleshooting Here is information about how smoke and heat alarms may affect your system and keypad as well as how to reset ...