Honeywell 997 Installation Instructions Download Page 1

 

997

 

Ceiling-Mounted Passive Infrared Motion Detector

 

INSTALLATION INSTRUCTIONS 

GENERAL INFORMATION 

This passive infrared motion detector is a ceiling-mounted 
unit employing a 360°, 31-zone Fresnel lens and offering an 
efficient protection pattern for commercial and residential 
applications. The detector senses sudden and slight 
changes in temperature within the area of detection; thus, 
when an intruder crosses or enters any zone, the resulting 
change in infrared energy is detected for alarm reporting. 
Best coverage will be obtained if the PIR is mounted such 
that the likely direction of intruder motion is in the direction 
shown in Figure 1. 

The Detector features installer-selectable Alternate Polarity 
Pulse Count, which provides protection against false alarms, 
and an LED enable/disable feature (installer-selectable). 

 

INSTALLATION HINTS 

•  Do not install where the detector is exposed to direct 

sunlight or directly above strong sources of heat. 

•  Make sure the detection area does not have obstructions 

(curtains, screens, large pieces of furniture, plants, etc.) 
that may block the pattern of coverage. 

•  Avoid locating a detector in areas that contain objects 

likely to produce a rapid change in temperature, such as 
central heating, radiators or ducts (or heaters of any kind), 
air conditioners, open flame, etc. 

•  Do not mount on an unstable surface. 

Important:  Avoid running alarm wiring close to heavy-duty 
electrical power cables. 

 

PROTECTION PATTERNS 

The PIR’s protection pattern is shown below.  

 

Detection Area 

 

TOP VIEW 

CENTER ZONE

ZONES B (6 ZONES)

ZONES C (12 ZONES)

ZONES D (12 ZONES)

11.5 ft

(3.5m)

11.5 ft

(3.5m)

18 ft

(5.5m)

18 ft

(5.5m)

0

12 ft

HEIGHT

(3.66m)

8 ft

HEIGHT

(2.4m)

NOTE: EACH ZONE

CONSISTS OF TWO

FIELDS (INCLUDING

THE CENTER ZONE)

997-004-V0

 

 

 
 

SIDE VIEW 

 

 

 

SPECIFICATIONS 

Detection Method:

 Passive Infrared. 

Coverage:

 

23-ft (7m) diameter @ 8 ft (2.4m) height, 

 

11.5-ft (3.5m) radius. 

 

36-ft (11m) diameter @ 12-ft (3.7m) height,

 

18-ft (5.5m) radius. 

Pulse Count: 

1- or 2-event, installer-selectable. 

Detectable 

Walk Rate: 

 0.5 

– 5ft/Sec (0.15 – 1.5m/Sec). 

Indicator: 

Red LED with enable/disable feature. 

Mounting 
Height:

 

12-ft (3.7m) maximum 

Voltage:

 

12VDC nominal (voltage reversal makes
 PIR inoperative).

 

Alarm Relay:

 

SPST, Form A, 0.5A max. contact rating @ 
30VDC. Reed relay, 15 ohm protective 
resistor. 

Current Drain:

 17mA. 

Standby 
Capability:

 

Power source should be capable of at least

 

4 hours of battery standby. 

Operating 
Temperature:  

32°F – 122°F (0°C – 50°C). 

Operating 
Humidity:

  

Up to 95% RH (max), non-condensing. 

Dimensions: 

3-1/2” (89mm) diameter x 1” (25.4mm) high.

 

INSTALLING AND WIRING THE PIR 

The ceiling on which the PIR is to be mounted must be firm 
and vibration-free.  

1. 

Select a location 

that will provide the coverage desired. 

Wiring (from the control, etc.) to be connected to the PIR 
should be brought to this location. The ceiling wiring hole 
should be no more than 5/16” (8mm) in diameter. 

2. 

Remove the cover

 from the PIR by pressing it in gently 

and turning it counterclockwise (to the left). To replace the 
cover, align the tabs on the cover's edge with the notches 
on the base's rim, press the cover gently in, and turn it 
clockwise (to the right). 

3. 

Break out one of the two knockouts

 that have been 

provided for wire access (see Figure 3), and pass the 
wires into the base of the PIR. 

Caution:

 

Be certain that 

wires do not obstruct the detector’s field of view. 

4. 

Connect all wires

 to the screw terminals (see Figure 3 for 

wiring details). Seal all openings in the base with foam or 
RTV (not supplied) to prevent drafts or insects from 
entering the unit. 

5. For walk-test purposes, initially set the LED to “on” 

(jumper removed), and set Pulse Count “off” (jumper 
removed).

 

6. 

Mount the PIR base

 to the ceiling with two screws, using 

the screw holes provided in the base of the PIR. 

Important Note: 

Optimum mounting orientation is shown in 

Figure 1. Mount the PIR in such a manner that the likely path 
of an intruder is in the direction shown. This will ensure 
maximum effectiveness of the Alternate Polarity feature. 

 

RELAY

12V

LED

ALARM

DET

ON

PULSE

COUNT

LED

OFF

INTRUDER’S MOST LIKELY DIRECTION OF MOTION

997-001-V0

 

 
 

Figure 1. Optimum Mounting Orientation 

 

LED ENABLE/DISABLE 

The detector is shipped with the Alarm LED disabled (LED 
enable/disable plug in place). The LED should be enabled (for 
a walk-test) by 

removing

 the LED enable/disable plug (see 

Figure 3 for location). To prevent the loss of the plug, we 
suggest you install it on one pin when the plug is not in use. 
When the walk-test is completed, the LED may be disabled, if 
desired (plug in place). 

The LED may also be controlled from a remote location, as 
follows: 

Remove the LED enable/disable plug. Connect a switched 
line to the upper pin (#1) of the two LED pins that can be 
grounded or opened (see Figure 2). Grounding pin #1 will 
disable the LED. Disconnecting it from ground will enable the 
LED.  

 

 

 

997-002-V0

RELAY

12V

1         LED

ENABLE

DISABLE

TO A GROUND TERMINAL ON THE ASSOCIATED
CONTROL OR TO (   ) TERMINAL ON DETECTOR

 

 
 

Figure 2. Remote Control of LED 

 

TAMPER SWITCH 

This PIR is equipped with a cover tamper switch. With 
cover on, the switch is closed; when cover is removed, the 
switch opens. The tamper terminals (see Figure 3) should 
be connected to the control panel’s tamper loop. 
 

PULSE COUNT OPTION 

Each detector includes Pulse Count circuitry that is 
designed to provide stability in adverse environments to 
minimize false alarms. Two-event pulse count is provided 
by positioning the jumper plug across the pulse count pins 
(see Figure 3 for location). To select one-event pulse count 
(instant response), remove the jumper plug. When 
programmed for 2-event pulse count, the detector will 
signal an alarm within 3 or 4 steps, since the processing 
logic requires more complex motion than just a momentary 
event. When the detector verifies an intrusion, the LED will 
light and the alarm relay contacts will transfer, both 
conditions lasting for approximately 1 to 3 seconds 
(dependent upon signal strength). 

To prevent the loss of the plug, we suggest you install it on 
one pin when the plug is not in use. 

 

TAMPER SWITCH

(OPENS WHEN
COVER IS
REMOVED).

LED

"OFF" WITH
PLUG
INSTALLED.
"ON"
WITH PLUG
REMOVED.

MOUNTING

HOLES (2)

KNOCKOUTS (2)

FOR WIRE ENTRY

PULSE COUNT

"ON" WITH PLUG

INSTALLED."OFF"

WITH PLUG

REMOVED.

RELAY

LED

ALARM

DET

ON

LED

OFF

997-003-V0

NO

T USED

12V

TO CLOSED CIRCUIT

PROTECTIVE LOOP

TO 12VDC

+ POWER SOURCE

TO SEPARATE
TAMPER CIRCUIT

 

 

Figure 3. PC Board (in base of PIR) 

 

  

TEST PROCEDURES 

Important:

 Two-minute warm-up time is required after 

applying power. Testing should be conducted with the 
protected area cleared of all people. Disarm the protective 
system's control during the test procedure to prevent 
reporting of unwanted alarms.  

Walk-Test 

1.  Pulse Count in the PIR must be “OFF” (jumper plug 

removed) to provide instant response. The Alarm LED 
must be enabled at this time (LED jumper plug removed). 

2.  With the cover installed on the PIR, walk through the 

protective zones, observing that the PIR's LED lights 
whenever motion is detected (the LED serves as a walk-
test indicator during this procedure). 

Note:

 With pulse count “OFF” (instant), the LED stays lit 

(and the alarm relay contacts remain open) for 
approximately 1 to 3 seconds after detecting motion. 

3.  If pulse count is to be used in this installation, install the 

pulse count jumper plug on the pulse count pins, and 
repeat the walk test procedure. With pulse count “ON,” 
the LED serves as an alarm indicator. 

The absolute range of all PIR units is subject to variation 
because of different types of clothing, backgrounds and 
ambient temperature. For this reason, ensure that the most 
likely intruder routes are well within the PIR's protective 
zones and that walk-testing is carried out along these routes. 

After the walk-test is complete, the LED may be disabled if 
desired (LED enable/disable plug installed). 

 

MAINTAINING PROPER OPERATION 

In order to maintain the detector in proper working condition, 
it is important that the following be observed by the user. 

1. 

Power should be provided at all times.

 Loss of power 

to the unit will result in the alarm contacts reverting to an 
alarm state. The unit's DC source should have standby 
power available for at least 4 hours of operation during 
emergencies. 

2. 

Units should never be relocated

 without the advice or 

assistance of the alarm service company. 

3. 

The physical surroundings of the protected area 
should not be changed

. If furniture or stock is moved, 

or air-conditioning or additional heating is installed, the 
system may have to be readjusted by the alarm service 
company. 

4. 

Walk-tests should be conducted frequently (at least 
weekly)

 to confirm continued proper coverage by each 

detector. 

 

TROUBLESHOOTING 

 

INTERMITTENT ALARM (LED OPERATIVE) 

Probable Causes: 

A. Rapid temperature change. Check for electric or gas 

heaters, open flames, electric arcs, etc.. 

Remedy:

 

Locate source and reposition detector if 
necessary. 

B.  Drafts causing drapes, light fixtures, display material to 

move. 

Remedy:

   Eliminate source of motion. 

 

INTERMITTENT OR CONTINUOUS ALARM 

Probable Causes: 

A. DC voltage supplied to detector is inadequate, 

intermittent, or polarity reversed. 

Remedy:

 

 Ensure that proper polarity and adequate 

voltage is supplied and that wiring is intact (no 
opens or shorts) and connections secure. 

B.  Protective loop is interrupted (open). 

Remedy:

 

Determine whether interruption is in protective 
loop wiring or at detector's alarm relay 
contacts. Disconnect protective loop at detector 
relay contact terminals and check continuity 
across terminals. If absent at terminals (and 
proper voltage is supplied to the detector), 
return unit for service. If present, check 
protective loop wiring. 

 

LED INOPERATIVE 

Probable Causes: 

A.  LED enable/disable plug is installed. 

Remedy:

  Remove LED enable/disable plug. 

B.  LED malfunction. Check for broken/shorted leads. 

Remedy:

  Return unit for service. 

NO ALARM WHEN MOTION TAKES PLACE IN THE 
PROTECTED AREA (LED DOES NOT LIGHT) 

Probable Causes: 

A.  Detection area has changed. Possibly due to repositioned 

furniture or equipment in the protected area. 

Remedy:

  

Caution customer about layout changes.  

 

 

 

WARRANTY INFORMATION 

 

For the latest warranty information, please go to: 

 

www.honeywell.com/security/hsc/resources/wa 

 

 

 

 

Summary of Contents for 997

Page 1: ...H This PIR is equipped with a cover tamper switch With cover on the switch is closed when cover is removed the switch opens The tamper terminals see Figure 3 should be connected to the control panel s tamper loop PULSE COUNT OPTION Each detector includes Pulse Count circuitry that is designed to provide stability in adverse environments to minimize false alarms Two event pulse count is provided by...

Page 2: ...r estabilidad en entornos adversos minimizando así las falsas alarmas El contador de impulsos de dos eventos se obtiene colocando el puente entre las patillas del contador de impulsos véase Ilust 3 para la ubicación Para seleccionar un contador de impulsos de un evento respuesta instantánea quite el puente Si programa la unidad para 2 eventos el detector indicará una alarma a los 3 o 4 pasos ya qu...

Page 3: ...rnes d autoprotection se reporter à la figure 3 doivent être raccordées à la boucle correspondante sur la centrale FONCTION DE COMPTAGE D IMPULSIONS Chaque détecteur est muni d un circuit de comptage d impulsions conçu pour accroître la stabilité lors d une installation dans un environnement perturbé et éviter tout déclenchement d alarme intempestif Le comptage 2 impulsions est obtenu en plaçant l...

Page 4: ... wordt er contact gemaakt Als de kap wordt verwijderd wordt het contact onderbroken De sabotagecontacten moeten worden aangesloten op de sabotagekring van de alarmcentrale PULSENTELLER MOGELIJKHEID Elke detector heeft een pulsentellersysteem dat is ontworpen om voor stabiltiteit te zorgen in een ongunstige omgeving zodat de mogelijkheid van valse alarm wordt geminimaliseerd Door het plaatsen van d...

Reviews: