background image

Page 8 of 14 

 

51-52-33-157 Rev. 6 

Example #2 

Ethernet

10/100Base-T 

100m each

Ethernet 
Switch

HC900
Controller
C30, C50, C70 CPU

900 Control Station

Experion LS, SpecView
or 3

rd

Party Software

 

Use shielded CAT5 cable with RJ45 connectors.  Connect to HC900 Ethernet port.  (On models C70 and 
C70R with two ports E1 and E2; either port can be used.) 

Example #3 

Ethernet

10/100Base-T 

100m each

HC900
Controller
C70 CPU (with 2 Ethernet ports)

900 Control Station

Experion LS, SpecView
or 3

rd

Party Software

 

Use shielded CAT5 cable with RJ45 connectors.  Connect to HC 900 to E2 of the C70 CPU and connect the 
host PC to E1. 

Summary of Contents for 900CS10-00

Page 1: ...Using Station Designer software create data tags from your cde file create your operator interface configuration and save the sds file 4 Download the sds file to the 900 Control Station and verify operation Note Configuration of the 900 Control Station may be performed prior to mounting if found to be more convenient when using the USB port since once loaded the configuration is maintained in non ...

Page 2: ...025 MANUFACTURED BY SANYO ENERGY CORP OR VARTA BATTERIE AG OR PANASONIC WARNING EXPLOSION HAZARD DO NOT CONNECT OR DISCONNECT CABLES WHILE POWER IS APPLIED UNLESS AREA IS KNOWN TO BE NON HAZARDOUS USB PORT IS FOR SYSTEM SET UP AND DIAGNOSTICS AND IS NOT INTENDED FOR PERMANENT CONNECTION WARNING EXPLOSION HAZARD THE AREA MUST BE KNOWN TO BE NON HAZARDOUS BEFORE SERVICING REPLACING THE UNIT AND BEFO...

Page 3: ... Action 1 With the 900 Control Station positioned face forward and with connectors on the bottom locate the Flash Memory Module receptacle through the access hole on the right side of the case 2 Insert the Flash Memory Module into the connector being sure the card is fully engaged in its receptacle Note the card is keyed to assure proper orientation Note Control Station supports a minimum of 4MB a...

Page 4: ...using a 3 16 inch 4 76mm size drill bit Remove any loose material from the mounting cut out to prevent that material from falling into the Control Station during installation 2 Mount the gasket by placing its 14 holes over the Control Station s 14 mounting bolts Push gasket all the way on to the mounting bolts Insert Control Station into panel cutout 3 Install the 14 kep nuts provided with the Con...

Page 5: ...ing cut out to prevent that material from falling into the Control Station during installation 2 Mount the gasket by placing its 22 holes over the Control Station s 22 mounting bolts Push gasket all the way on to the mounting bolts Insert Control Station into panel cutout 3 Install the 22 kep nuts provided with the Control Station Tighten evenly for uniform gasket compression Do not tighten the ke...

Page 6: ...s created via the Ethernet shield of the controller Other equipment connected to the unit may require isolation between signal common and earth ground To maintain isolation care must be taken when connections are made to the unit For example a power supply with isolation between its signal common and earth ground must be used Connecting a device via a USB cable may also connect signal common and e...

Page 7: ...d connect the power supply s 24Vdc lead to terminal 2 and the Common lead to terminal 1 See figure below Plug the terminal block into the connector located on the bottom of the interface 5 Connect communications Overview Connections and ports used depend on the architecture of your installation See architecture examples starting on page 7 For cabling and connections see page 10 For details on conn...

Page 8: ...CAT5 cable with RJ45 connectors Connect to HC900 Ethernet port On models C70 and C70R with two ports E1 and E2 either port can be used Example 3 Ethernet 10 100Base T 100m each HC900 Controller C70 CPU with 2 Ethernet ports 900 Control Station Experion LS SpecView or 3rd Party Software Use shielded CAT5 cable with RJ45 connectors Connect to HC 900 to E2 of the C70 CPU and connect the host PC to E1...

Page 9: ...rminated ON 1 2 3 4 See manual 51 52 25 107 for full details Note Ethernet connections will provide faster performance than RS 485 Example 5 B A 100 base T Up to 100m 10 100 base T Ethernet Switch Ethernet or RS 485 Non redundant Experion LS SpecView or 3rd Party Software Dual Ethernet support HC900 Redundant Controller C70R CPU 900 Control Station Connect to C70R using either RS 485 or Ethernet C...

Page 10: ... each Ethernet Switch HC900 Controller C30 C50 C70 CPU 900 Control Station 1 900 Control Station 2 900 Control Station 3 Up to 3 Control Stations may be connected to a HC900 controller using Ethernet Multiple stations via RS 485 are not supported Cables Ethernet Ethernet communications are recommended for best performance ...

Page 11: ...of the shielded CAT5 cable 2 Connect the wires indicated to the 3 plug connector that was supplied with the HC900 CPU module See table below Shielded CAT5 cable 3 plug connector Signal Pin Terminal Shield aluminum polyester foil tape with 26 AWG stranded drain wire Connect to 1 TXA 2 Connect to 2 TXB 1 Connect to 3 RXA 3 RXB 4 TXEN 5 Common 6 TXB 7 Connect to 3 TXA 8 Connect to 2 3 Cut off any unu...

Page 12: ...he station communicate with other Honeywell or Modbus compatible equipment create a communications cable as follows RJ12 connector Connector of slave device Terminal no Signal Terminal no Signal 1 CTS 7 RTS 2 RX 3 TXD 3 Ground 5 Ground 4 Ground 1 DCD 5 TX 2 RXD 6 RTS 8 CTS 1 6 5 1 9 6 4 3 2 8 7 ...

Page 13: ...Ordinary Location Safety UL evaluated to CSA C22 2 No 61010 1 2004 Second Edition General Purpose Ordinary Location Safety UL CSA and FM Class I Div 2 Groups A B C and D Electromagnetic Compatibility IEC61326 2005 CE Mark EMC requirements for electrical equipment for measurement control and laboratory use Immunity to Industrial Locations ESD IEC 61000 4 2 Criterion A 4kV contact discharge 8kV air ...

Page 14: ...ce without charge those items it finds defective The foregoing is Buyer s sole remedy and is in lieu of all other warranties expressed or implied including those of merchantability and fitness for a particular purpose Specifications may change without notice The information we supply is believed to be accurate and reliable as of this printing However we assume no responsibility for its use While w...