Model 6820 / 6820-EVS Installation Manual
LS10144-001SK-E
1-3
1.3
Compatible Products
Table 1-1 lists the products available from Honeywell Silent Knight for use with the 6820 and 6820EVS.
Output Point
(or “Output Circuit”)
A notification point or circuit for notification appliances. Relay circuits and auxiliary power
circuits are also considered output points.
Output Group (OPG)
A group of output points. Operating characteristics are common to all output points in the
group.
Output (or “Cadence”) Pattern
The pattern that the output will use, for example, Constant, March Code, ANSI 3.41. Applies to
zones and special system events. See Appendix D for additional information.
Mapping
Mapping is the process of specifying which outputs are activated when certain events occur in
the system. Section 8.2 explains mapping in detail.
EVS
Emergency Voice System.
Common Communication Link
Up to 17 panels can be linked. Consist of any combination of 17 panels of these model
numbers:6700, 6808, 6820, or 6820EVS. For reporting purposes only. Not a peer-to-peer
networked system.
SWIFT
Smart Wireless Integrated Fire Technology
Table 1-1: 6820 or 6820EVS Compatible Products
Type of Device
Model
Description
SK Addressable
SLC Devices
See Section 7.1 for a list of compatible devices.
SD Addressable
SLC Devices
See Section 7.2 for a list of compatible devices.
SWIFT Wireless
SLC Devices
See Section 7.3 for a list of compatible devices
Other Modules
5815XL (Rev H or higher)
SLC Expander
Allows an additional 127 SD devices to be added to the system for a maximum
of 635 points. Supports SD devices only.
6815 SLC Expander
Allows an additional 159 SK modules and 159 SK sensors to be added to the
system for a maximum of 1110 points. Supports System Sensor SK devices only.
5824 Serial/Parallel Printer
Interface Module
Allows a printer to be attached for the on-site event logging. Maximum of four
5824s per control panel.
5895XL (Rev F or higher)
Intelligent Power Module
Provides additional power, six Flexput™ circuits, and
two Form C relays. Max. 16 per system see
Model
5895XL Installation Instructions P/N 151142
.
5895XLs and 5496s can
be used in any
combination, up to a
total of 16 devices on
one system.
5496 (Rev F or higher)
Intelligent Power Module
Provides 4 additional Notification Appliance Circuits/
Auxiliary power. (Up to 16 per system).
6860 LCD Annunciator
4x40 backlit LCD remote fire annunciator Up to 16
any combination of annunciators per system
up to a total of 16 in any
combination on one
system.
5860 LCD Annunciator
4x20 LCD remote fire annunciator. 5860 is gray;
5860R is red.
6855 LCD Annunciator
4x20 LCD remote fire annunciator
5860TG and 5860TR Trim
Ring Kit
Trim ring kits for surface mounting the 5860 annunciator. 5860TG is gray;
5860TR is red.
5865-3 and 5865-4 LED
Annunciator
LED annunciator can display up to 30 LEDs (15 red
and 15 yellow). 5865-4 has key switches for silence
and reset, and a system trouble LED.
5865-3, 5865-4, and
5880 can be used in any
combination, up to a
total of eight devices on
one panel.
5880 (Rev C or higher)
LED I/O Module
Driver for up to 40 LEDs. Interfaces with customized
annunciator boards. In addition, the 5880 has eight
generic switch input points.
Term
Description