6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
79
SK, SD and SWIFT™Wireless SLC Device Installation
2.
Set the address for each device as described in Section 7.9.
Figure 7.6 Heat or Smoke Detector Connection to the FACP (Class B)
7.9 Addressing SD SLC Detectors
This section tells how to address detectors and modules. See Table 7.2 for list of detectors.
1.
Connect a detector base temporarily to the programming terminals as shown in Figure 7.7. (You can use the same base for each
detector).
Figure 7.7 Temporary Connection of Detector Base to Panel for Addressing
2.
Enter the Installer code, then press ENTER.
3.
Select 2 for Point Functions.
4.
Select 3 for Set SLC Dev Addr.
5.
Select “Yes” by pressing the up arrow, then press ENTER. (The panel will go into trouble at this point. You can use the SILENCE
key to stop the PZT. The trouble will clear automatically when the panel reinitializes when you finish programming.)
6.
When the wait message clears, the following options display:
1- for Read Address. Use to read (or check) a single detector’s address.
2 - for Write Address. Use to program a single detector’s address.
3 - for Seq. Programming. Use to program more than one detector in sequential order.
7.
If you are changing addresses, write the programmed address on the back of the device.
8.
To exit press left arrow until fully exited.
Summary of Contents for 6808
Page 13: ...6808 Manual P N LS10146 001SK E C 09 28 2017 13 Introduction ...
Page 67: ...6808 Manual P N LS10146 001SK E C 09 28 2017 67 Common Communication Link ...
Page 97: ...6808 Manual P N LS10146 001SK E C 09 28 2017 97 Programming Overview ...
Page 143: ...6808 Manual P N LS10146 001SK E C 09 28 2017 143 Testing and Troubleshooting ...
Page 159: ...6808 P N LS10146 001SK E C 09 28 2017 159 ...
Page 161: ...6808 P N LS10146 001SK E C 09 28 2017 161 ...
Page 163: ...6808 P N LS10146 001SK E C 09 28 2017 163 ...
Page 165: ...6820 6820EVS Manual P N LS10144 001SK E C 09 28 2017 165 ...
Page 168: ...Cut Along the Dotted Line ...
Page 169: ......