6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
23
Before You Begin Installing
2.
The FACP can only support 5 devices w/LED’s on. This current draw has been added to the panels alarm current.
3.
SK-Beam-T draws a maximum of 500 mA from Auxiliary power only when the test feature is used. This should be considered
when determining auxiliary power capacity but not calculated into current requirements for day to day operation.
4.
If using door holders, you do not need to consider door holder current for alarm/battery standby, because
power is removed during that time. However, during normal operation, door holders draw current and must be included in the
6.0A total current that can be drawn from the panel.
5.
Use next size battery with capacity greater than required.
6.
Total does not include isolator devices or accessory bases.
Current Draw Worksheet for SD SLC Devices
Use Table 3.3 to determine current requirements during alarm/battery standby operation when SD SLC devices are installed. You can
install up to 127 SD devices per panel.
5
Device
Number of
Devices
Current per Device
Standby
Current
Alarm
Current
For each device use this formula: This column X This column = Current per number of devices.
Fire Panel (Current draw from
battery)
1
Standby: 190 mA 190 mA
Alarm: 250 mA
250 mA
Addressable SLC Devices
SD500-AIM
Standby/Alarm: .55 mA
1
mA
mA
SD500-MIM
mA
mA
SD500-ARM
mA
mA
SD500-PS
SD505-HEAT
mA
mA
SD505-PHOTO
mA
mA
SD500-ANM
Aux. Pwr
Standby: 8 mA mA
Alarm: 60 mA
mA
SLC
Standby/Alarm: 55 mA mA
mA
SD500-SDM
SLC
Standby/Alarm: .55 mA mA
mA
Aux. Pwr
Standby: 20 mA mA
Alarm: 106 mA
mA
SLC Accessory Bases
SD505-6RB
Standby/Alarm: .082 mA mA
mA
SD505-6SB
Aux. Pwr
Standby: 1 mA mA
Alarm: 32 mA
mA
SLC
Standby/Alarm: .082 mA mA
mA
SD505-DUCTR
Aux. Pwr
Standby: 20 mA
2
mA
Alarm: 62 mA
2
mA
SLC
Standby/Alarm: .5 mA mA
mA
SD505-DTS-K
None, included with SD505-DUCTR worst case.
SD505-DUCT
SLC
Standby/Alarm: .5 mA mA
mA
SLC Isolator Devices
SD500-LIM
(100 max)
Standby/Alarm: .092 mA mA
mA
SD505-6IB
(50 max.)
Accessories Modules
6860 Remote LCD Annunciator
(12 max)
Standby: 20 mA mA
Alarm: 25 mA
mA
5860 Remote LCD Annunciator
Standby 20mA mA
Alarm 25 mA
mA
6855 Remote LCD Annunciator
Standby: 20 mA mA
Alarm: 25 mA
mA
5824 Serial/Parallel Printer
Interface
(4 max.)
Standby/Alarm: 45 mA mA
mA
Table 3.3 Current Draw worksheet for SD Devices
Summary of Contents for 6808
Page 13: ...6808 Manual P N LS10146 001SK E C 09 28 2017 13 Introduction ...
Page 67: ...6808 Manual P N LS10146 001SK E C 09 28 2017 67 Common Communication Link ...
Page 97: ...6808 Manual P N LS10146 001SK E C 09 28 2017 97 Programming Overview ...
Page 143: ...6808 Manual P N LS10146 001SK E C 09 28 2017 143 Testing and Troubleshooting ...
Page 159: ...6808 P N LS10146 001SK E C 09 28 2017 159 ...
Page 161: ...6808 P N LS10146 001SK E C 09 28 2017 161 ...
Page 163: ...6808 P N LS10146 001SK E C 09 28 2017 163 ...
Page 165: ...6820 6820EVS Manual P N LS10144 001SK E C 09 28 2017 165 ...
Page 168: ...Cut Along the Dotted Line ...
Page 169: ......