CAUTION: Carbon Monoxide Gas and its Detection 

This carbon monoxide detector is designed for indoor use only. Do not 
expose to rain or moisture. Do not knock or drop the detector. Do not 
open or tamper with the detector as this could cause malfunction. The 
detector will not protect against the risk of carbon monoxide 
poisoning if not properly installed. The detector will only indicate the 
presence of carbon monoxide gas at the sensor.  

 

Carbon monoxide gas may be present in other areas. 
This carbon monoxide detector is NOT: 
• Designed to detect smoke, fire or any gas other than carbon 

monoxide 

• To be seen as a substitute for the proper servicing of fuel-burning 

appliances or the sweeping of chimneys. 

• To be used on an intermittent basis, or as a portable alarm for the 

spillage of combustion products from fuel-burning appliances or 
chimneys. 

 

Carbon monoxide gas is a highly poisonous gas which is released 
when fuels are burned. It is invisible, has no smell and is therefore 
impossible to detect with the human senses. Under normal conditions 
in a room where fuel burning appliances are well maintained and 
correctly ventilated, the amount of carbon monoxide released into the 
room by appliances should not be dangerous. 

 

Symptoms of carbon monoxide poisoning: 

Carbon monoxide 

bonds to the hemoglobin in the blood and reduces the amount of 
oxygen being circulated in the body. The following symptoms are 
related to carbon monoxide poisoning and should be discussed with 
all members of the household: 
Mild exposure: Slight headache, nausea, vomiting, fatigue (often 
described as “flu-like” symptoms). 
Medium exposure: Sever throbbing headache, drowsiness, confusion, 
fast heart rate. 
Extreme exposure: Unconsciousness, convulsions, cardio respiratory 
failure, death. 
Many causes of reported carbon monoxide poisoning indicate that 
while victims are aware that they are not well, they become so 
disoriented that they are unable to save themselves by either exiting 
the building or calling for assistance. 
Also young children and pets may be the first to be affected. 

 

!

 

WARNING: IMPORTANT INFORMATION FOR THE USER 

 

Actuation of your CO alarm indicates the presence of carbon 
monoxide (CO), which can cause injury or death.  

 

Individuals with medical problems may consider using warning 
devices which provide audible and visual signals for carbon monoxide 
concentrations under 30ppm. 

 

What to do if the carbon monoxide detector goes into alarm: 

1.  Push the Hush/Test button. If the detector reactivates or the 

detector does not silence, continue with step 2. 

2.  Immediately move to fresh air, outdoors or by an open window. 

Check that all persons are accounted for. Do not reenter the 
premises nor move away from the open door/window until 
emergency service responders have arrived. 

3.  Call your local fire department from a phone in an area where the 

air is safe. 

4.  If your detector reactivates within a 24-hour period, repeat steps 

1-3 and call a qualified appliance technician to investigate for 
sources of CO from fuel burning equipment and appliances, and 
inspect for proper operation of this equipment. If problems are 
identified during this inspection, have the equipment serviced 
immediately. Note any combustion equipment not inspected by 
the technician and consult the manufacturer’s instructions, or 
contact the manufacturers directly, for more information about 
CO safety and this equipment. Make sure that motor vehicles are 
not, and have not been, operating in an attached garage or 
adjacent to the residence. 

 

IMPORTANT: 

This detector should be tested and maintained 

regularly following National Fire Protection Association (NFPA) 720 
requirements. (Generally this detector should be tested at least once 
per month.) 

 

MAINTENANCE 

Occasionally clean the outside casing with a cloth. Ensure that the 
holes on the front of the alarm are not blocked with dirt and dust. 

Do not paint, and do not use cleaning agents, bleach, or polish 
on the detector. 
 

DETECTOR REPLACEMENT 

This detector is manufactured with a long-life carbon monoxide 
sensor. Over time the sensor will lose sensitivity, and will need to be 
replaced with a new carbon monoxide detector. This detector’s 
lifespan is approximately six years from the date of manufacture. 

 

The user should periodically check the detector’s replacement date. 
Remove the detector from its base and check the replacement date 
label on the underside of the detector. The label indicates the date 
that the detector should be replaced. 

 

NOTE:

 When the detector is removed from its base, a message is sent 

to the central station. If the system is armed, a tamper alarm 
message is sent; if disarmed, a trouble message is sent. 

 

The detector will also cause a trouble condition once it has reached 
the end of its useful life. If this occurs, it is time to replace the 
detector. 

 

NOTE: 

Before replacing the detector, notify the proper authorities 

that maintenance is being performed and the system will be 
temporarily out of service. Disable the zone or system undergoing 
maintenance to prevent any unwanted alarms. Dispose of detector in 
accordance with any local regulations. 

 

CAUTION 

It should be noted the installation, operation, testing and 
maintenance of the 5800CO is different than smoke detectors. Per 
NFPA 720 section 5.3.7.2 the detector shall not be connected to a zone 
that signals a fire condition (i.e. smoke detector zones). Therefore, the 
5800CO detector must be programmed as a non-fire zone. See the 
control’s Installation Instructions for the appropriate carbon 
monoxide zone type to be programmed. 
 

SPECIFICATIONS 

Power Source: 

One 3-volt CR123A Lithium Battery 
(included). (Replace with Duracell 
DL123A, Panasonic CR123A or 
ADEMCO 466.) 

Audible Signal (temp 4 tone):  85 dBA min. in alarm (at 10ft) 

Height: 

2.3 inches (58 mm) 

Diameter: 

5.3 inches (135 mm) with mounting 
base 

Weight: 

7 oz. (241 g) without battery 

Operating Ambient  
Temperature Range: 

32° to 100°F (0° to 37.8°C)   

Operating Humidity Range:  15% to 95% Relative Humidity, non-

condensing 

Agency Listings: 

UL standard 2075

 

Patent numbers:  

5,155,469;  5,004,999;  7,120,795 

 

Please see insert for Limitations of Carbon Monoxide Detectors. 

 

 

FOR WARRANTY INFORMATION AND FOR DETAILS REGARDING 
THE LIMITATIONS OF THE ENTIRE ALARM SYSTEM, GO TO: 

www.honeywell.com/security/hsc/resources/wa 

 

 

 

ÊK14631V1*Š 

K14631V1 4/08  Rev. A 

 

2 Corporate Center Drive, Suite 100

P.O. Box 9040, Melville, NY 11747

Copyright © 2007 Honeywell International Inc.

www.security.honeywell.com

 

 

Summary of Contents for 5800CO

Page 1: ... TESTING THE DETECTOR Table 1 Detector LED Modes Green LED Red LED Sounder Normal standby Blinks every 10 seconds Off Off Alarm Test Off Blinks every 1 second Temporal 4 Pattern Low Battery Off Blinks every 45 seconds for 37 days Chirp every 45 sec beginning 7 days after LED blinks continues 30 days Detector Trouble Off Blinks every 5 seconds One chirp every 45 seconds Detector End of Life Off Bli...

Page 2: ...es proper carbon monoxide detection see Figure 4 for suggested detection locations and a strong wireless transmission path Proper Carbon Monoxide Detection Location In a wall location the detector should be at least as high as a light switch and at least six inches from the ceiling In a ceiling location the detector should be at least 12 inches from any wall Where to install ideally Within 10 feet...

Page 3: ... 5800CO 004 V0 PUSH RECESSED BUTTON WITH A 0 18 MAX DIAMETER TOOL TEST H U S H D O N O T P A I N T N O R M A L A L A R M C A R B O N M O N O X I D E D E T E C T O R W A R N I N G I N A L A R M M O V E T O F R E S H A I R C A U T I O N ADDITIONAL M A R K INGS ON BACK LEDs RECESSED TEST BUTTON Figure 5 Recessed Test Button Opening Testing Signal Strength NOTE Remove battery tab before installation T...

Page 4: ...re identified during this inspection have the equipment serviced immediately Note any combustion equipment not inspected by the technician and consult the manufacturer s instructions or contact the manufacturers directly for more information about CO safety and this equipment Make sure that motor vehicles are not and have not been operating in an attached garage or adjacent to the residence IMPORT...

Reviews: