T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
63-2605—5
16
3.
Press up
S
or down
T
until the desired time is
displayed.
4.
Press
Run Schedule
.
IMPORTANT
— Invalid holidays are ignored.
— Valid holidays require valid: month, day and duration.
— Holidays such as the fifth Tuesday of a month with
only four Tuesdays are also invalid.
Copying a Day
Use the PDA or almost exclusively keys in the “Schedule”
area of the keypad for this procedure:
1.
Press
Occupied
.
2.
Press
Day
to select the day to be copied.
3.
Press
Copy
.
4.
Press
Copy
again. The following day is automatically
selected. (For example: If the day to be copied is Mon-
day, Tuesday will automatically be selected.)
5.
If necessary, press
Day
until the day to receive the copy
is displayed.
NOTE: To cancel the copy press
Run Schedule
before
6.
Press
Copy
.
NOTE: DONE displays for two seconds then the
program display reappears.
7.
Repeat steps 2 through 6 for all the days desired.
8.
Press
Run Schedule
.
Clearing Program Start Times
1.
Press
Occupied
or
Not Occupied
until the start period to
be cleared is displayed.
2.
Press
Day
until desired day is displayed.
3.
Press
Clear Start
Time
.
4.
Repeat steps 1 through 3 for all the start times to be
cleared.
5.
Press
Run Schedule
.
Temperature Setpoints
Setpoint Limits
The setpoint temperature range is 40°F to 90°F (4°C to 32°C)
for heating and 45°F to 99°F (7°C to 37°C) for cooling.
NOTES: The ranges mentioned can be limited based upon
setpoints and stops:
1.
The greater of the Minimum Heat Stop and the
Not Occupied Heat setpoints determines the
lowest setting to which the occupied heat setpoint
can be adjusted:
°F: Stop/NotOcc
≤
OccHeat
≤
(OccCool - 2).
°C: Stop/NotOcc
≤
OccHeat
≤
(OccCool - 1).
2.
The lesser of the Maximum Cool Stop and Not
Occupied Cool setpoints determines the highest
setting to which the occupied cool setpoint can be
adjusted:
°F: Stop/NotOcc
≥
OccCool
≥
(O 2).
°C: Stop/NotOcc
≥
OccCool
≥
(O 1).
3.
The Maximum Occupied Heat Setpoint is limited
by Occupied Cool Setpoint – 2° F (1° C).
4.
The Minimum Occupied Cool Setpoint is limited
by the Occupied Heat Se 2° F (1° C).
Programming Temperature Setpoints
1.
Press
Occupied Heat
.
2.
Press up
S
or down
T
until the desired
temperature is displayed.
3.
Press
Occupied Cool
.
4.
Press up
S
or down
T
until the desired
temperature is displayed.
5.
Press
Not Occupied Heat
.
6.
Press up
S
or down
T
until the desired
temperature is displayed.
7.
Press
Not Occupied Cool
.
8.
Press up
S
or down
T
until the desired
temperature is displayed.
9.
Press
Run Schedule
.
Temperature Setpoint Overrides
IMPORTANT
— The setup determines the duration of Occupied
overrides.
— Default duration is three hours.
NOTE: To cancel the Override and immediately return to the
program, press
Run Schedule
.
T7770 Setpoint Knob
A T7770 setpoint knob can remotely adjust the T7350 setpoint.
Adjustment can be made with the sensor in override.
NOTES:
—
During override, only occupied and standby heat
setpoints, and cool setpoints are adjusted.
—
The maximum adjustment is ±5° F (3° C).
—
With a disconnected or failed T7770, or a T7350
not set for setpoint, offset is zero.
T7771 Setpoint Button
A T7770 setpoint button can remotely adjust the T7350
setpoint. Adjustment can be made with the sensor in override.
NOTES:
—
During override, only occupied and standby heat
setpoints, and cool setpoints are adjusted.
—
The maximum adjustment is ±3° F (2° C).
—
With a disconnected or failed T7771, or a T7350
not set for setpoint, offset is zero.
Changing Temperature Setpoint Until Next Program
Period
This is a simple change to perform even with the door closed:
1.
Press up
S
or down
T
until the desired
temperature is displayed.
NOTE: If done while in Standby or Not Occupied
mode, Temporary Occupied override engages
2.
The temporary temperature appears for approximately
ten seconds, then the room temperature is displayed.