5. Internal Memory Configuration and Functions
5.3. Operation parameters setting area
90
Resistance Temperature Detector 2MLF-RD4A User's Guide
R200
Honeywell
September 2010
WORD
Description
0
Set the sensor type to Pt100
1
Set the sensor type to JPt100
Address 1 to 4 is used for channels 0 to 3, respectively.
3.
Use
I/O Parameter
window of SoftMaster for more convenient setting of the
sensor type.
Figure 39 – I/O Parameter window 2 (sensor type)
Temperature conversion unit (address 5)
1.
Temperature-converted value is displayed in °C or °F as specified. The bits 0 to 3
are set to 0 or 1 to specify the temperature conversion unit. The rest of the bits are
ignored.