background image

272630D Auxiliary Board 

INSTALLATION 

When installing this product... 

1.  Read these instructions carefully. Failure to 

follow them could damage the product or 
cause a hazardous condition. 

2. Check ratings given in instructions and on 

the product to ensure the product is suitable 
for your application. 

3. Installer must be a trained, experienced 

service technician. 

4. After installation in complete, check out 

product operation as provided in these 
instructions. 

CAUTION: 

1. Disconnect power supply before beginning 

installation to prevent electric shock and 
equipment damage. 

2.  All wiring must comply with applicable local 

electrical codes, ordinances and regulations. 

3.  DO NOT electrically operate the ML6-7984 

actuator before assembly to the valve 
because damage not apparent to the installer 
may occur. Mount the actuator to the valve 
before connecting to power. 

Assembly 

1. Remove plastic cover from the ML6-7984 

by loosening the two screws located on the 
top. (Note: These screws are captive. 
Rotate three complete revolutions to 
remove cover). 

2. Slide the auxiliary board into the two slots 

at the bottom of the bridge. Push back and 
snap the board into the fingers. (See Fig. 1) 

3. Connect one end of the 4-pin connector to 

the main board and the other end to the 
auxiliary board if it is not already connected. 
The connectors are keyed and only install 
one way. 

4. Mount the actuator onto the valve body and 

connect wiring. 

5. Reinstall cover after operational check. 

Fingers  

Bridge 

Slots 

1. Install 
circuit 
board 

Fig. 1 - Installation of auxiliary board 

OPERATION 

The first time the valve is powered, the 
microprocessor will automatically cycle the 
valve through a full stoke to calibrate its 
position. Any stroke between 1/2" (13 mm) and 
1" (25 mm) will be divided into 30 equal steps. 
Run time will be proportional to stroke length. 
(For example: nominal timing for 3/4" stroke 
is 63 seconds. For 1/2" stroke this would be 
42 seconds). The LED lights up when 
terminals T5-T6 are powered, and flash when 
the actuator is in motion. 

NOTE: 272630D requires that the actuator be 
continuously powered, so ML6984 must be 
wired in "5-wire" configuration. 

C-NC contact  C-NO contact 
CLOSED 

CLOSED 

2-10 V, 

when valve 

when valve 

(4-20 mA 

position is 

position is 

into 

below trim pot  above trim pot  500 

setting (direct  setting (direct 

feedback 

acting). 

acting). 

output  COM 

Trim pot 

J1

LED 

+FB

NC 

C  NO 

RLY1 

-COM 

Connect to main 
board for position 
feedback. 

Fig. 2 - Wiring and operation of auxiliary 

board 272630D 

2

 