background image

IMMERSION WELLS AND COMPRESSION FITTINGS

68-0040—04

8

threaded end of the spud can extend into the controlled 

medium. Consider this additional length when determining how 

far the well extends into the controlled medium.

The length of the well shell starting at the end of the spud 

defines the insertion length. This is the 

active

 part of the well 

where the fastest heat transfer occurs. The bulb should be the 

same length as the well shell; however, the well shell can be 

longer, but not shorter, than the length of the bulb. Longer 

shells require inserting the bulb until the end touches the well 

bottom. Shorter shells do not expose the full length of the bulb 

to the temperature of the controlled medium, inhibiting proper 

temperature controller operation.

Securing Bulb in Well

REMOTE BULB APPLICATIONS

Securing the capillary at the spud with a spring clip or a 

mounting clamp holds the sensing bulb securely in place. See 

Fig. 1. Use the spring-loaded clip on well spuds with no 

mounting flange. Slip it over the capillary and snap it in place in 

the end of the spud. The mounting requires sizing to fit both the 

spud and the capillary diameter. The mounting clamp requires 

wells with a mounting flange at the spud end. The jaws adjust 

to fit both 1/2 and 3/4 in. spuds, and it holds a 5/64 in. capillary. 

Wells are available with and without the matching spring clip or 

mounting clamp. This mounting hardware is also available 

separately.

A few wells have a setscrew in the spud. These wells are 

designed for use on controllers with an armored capillary that 

has a brass plug at the sensing bulb end; for example, 

R8182H,J.

DIRECT INSERTION APPLICATIONS

Most Honeywell direct insertion controllers include provision for 

clamping the controller case on the immersion well spud. This 

requires a well spud with a mounting flange at the end. If the 

well spud has a setscrew, but no mounting flange, a 124904 

Well Adapter can provide the necessary flange. See Fig. 3. 

The well adapter is shipped with several Honeywell 

TRADELINE® direct-insertion controllers.

Fig. 3. Mounting direct insertion controller 

case on well spud.

Capillary Compression Fittings

A capillary compression fitting includes a spud, several 

aligning washers, a neoprene packing ring and a packing nut. 

The spud is internally threaded to hold the packing material 

and the packing nut and externally threaded to fit standard 

boiler tappings. The washers and packing ring are sized to fit a 

particular capillary diameter.

Capillary compression fittings are used to replace an 

immersion well when the sensing bulb of a remote bulb 

controller requires direct insertion into the controlled medium. 

The fitting seals around the capillary. However, compression 

fittings cannot seal off against as much pressure as immersion 

wells. Capillary compression fittings can be used in duct 

applications to minimize air leakage from the duct; a waste nut 

is recommended to provide a secure mounting.

Material Selection

Capillary compression fittings are available in brass and 

stainless steel. In hydronic applications, brass fittings with 

copper sensing bulbs are used and stainless steel is used with 

all other fittings to minimize electrolytic action.

Sizing

Capillary compression fittings must fit the tapping and the 

capillary diameter. Because the spud must slip over the bulb 

during installation, 11/16 in. bulbs require 3/4 in. spuds.

Element Holders

Bulb holders are used to support a remote bulb and capillary in 

a duct, but are not suitable for hydronic applications. A bulb 

holder must be selected according to the length needed to 

support the bulb in the main airstream and the need for 

plugging the opening in the duct wall.

For best response, string averaging elements evenly back and 

forth across the duct. The element is held in place with either 

perforated pipe strap or 314439 Mounting Clips. If access to 

the duct is limited, use the 7640HX Duct Mounting Kit. Always 

use a grommet to protect the element from abrasion where it 

enters the duct.

NOTE: To minimize heat loss through the fitting, use a waste 

nut and compression fitting.

INSTALLATION

When Installing this Product…

1.

Read these instructions carefully. Failure to follow them 

could damage the product or cause a hazardous 

condition.

2.

Check the ratings given in the instructions and on the 

product to make sure the product is suitable for your 

application.

3.

Installer must be a trained, experienced service techni-

cian.

4.

After installation is complete, check out product opera-

tion as provided in these instructions.

WARNING

Severe Scalding Hazard.

Contact with hot liquid can cause severe injury or 

death.

Drain system before beginning well or compression 

fitting installation.

M17261

BACK 

OF 

CASE

WELL 
CLAMP 
SCREW

WELL
ADAPTER

IMMERSION 
WELL CLAMP

SENSING BULB

SETSCREW

WELL
SPUD

BOILER 
WALL

WELL 
SHELL

Summary of Contents for 104484A

Page 1: ... steel mild steel or Monel Element holders support the capillary and bulb or an averaging element in duct applications Bulb shields protect the sensing bulb from sun and weather with the bulb installed outdoors Accessories including mounting clips heat conductive compound waste nuts a pipe strap and a well adapter are available for mounting sensing bulbs in various applications Immersion wells all...

Page 2: ... for copper See Table 2 for stainless steel mild steel and Monel Compression Fittings Allow bulb insertion directly into the controlled medium with boiler draining Can also be used to provide positive seal in duct applications Available in brass and stainless steel See Table 3 Element Holders Support bulb and capillary or averaging element in a duct See Table 4 Dimensions See Tables 1 2 3 and 4 an...

Page 3: ...MOUNTING FLANGE MOUNTING FLANGE MOUNTING CLAMP WELL SPUD FITS 1 2 OR 3 4 14 NPT TAPPED HOLE FITS 1 2 OR 3 4 14 NPT TAPPED HOLE FITS 1 2 OR 3 4 14 NPT TAPPED HOLE FITS 1 2 OR 3 4 14 NPT TAPPED HOLE 1 8 1 2 in OF THREADS MAY EXTEND INTO CONTROLLED MEDIUM 1 8 1 2 in OF THREADS MAY EXTEND INTO CONTROLLED MEDIUM WELL SHELL M17259A SET SCREW FITS 1 2 OR 3 4 14 NPT TAPPED HOLE FITS 1 2 OR 3 4 14 NPT TAPP...

Page 4: ...nting Clamp 121371B 123870A 3 5 64 121371 Mounting Clamp 121371M 121371 Mounting Clamp plastic sleeve 123171N 123871A Plastic sleeve on well tube 123871B 4 1 2 122555D Plastic sleeve on well tube 122555A 3 1 2 1 1 2 5 64 121371 Mounting Clamp 121371Q 2 1 4 138134B 4 1 2 Plastic sleeve on well tube 122555B 122555C 3 8 5 8 3 2 1 4 Plastic sleeve on well tube 138134E 4 1 2 122555E 1 2 4 1 4 1 1 2 1 8...

Page 5: ...8 5 8 in 2 3 4 in x 1 3 4 in Supports capillary and bulb in duct mounting screws not included 2 3 4 in x 3 in 14 in 3 1 4 in x 3 1 4 in Holds 1 or 2 elements in 0 F to 100 F air grommet holds one 5 64 in and one 1 8 in diameter capillary helps reduce airflow through opening in duct Averaging element holders Mounting clip use with grommet mounting screws not included one required per clip Use with ...

Page 6: ... Holds capillary in place on 1122620AA 112639AB Immersion Wells 1 2 in well spud 5 64 capillary 112721 112720 1 2 in well spud 1 8 capillary 3 4 in well spud 1 8 capillary Heat conductive compound Improves heat conduction in well applications where bulb does not fit tightly 4 oz 118 ml Single application tube 1 2 oz Well Adapter Adapts well with setscrew on spud for use with direct insertion bulb ...

Page 7: ...l mild steel and Monel wells are also available for applications requiring higher maximum temperature and pressure ratings or greater corrosion resistance Some copper wells are available with a plastic sleeve over the tube to reduce electrolytic and corrosive activity Well Sizing Major factors in selecting well size are size of the boiler tapping bulb diameter insulation depth insertion length Imm...

Page 8: ...ng material and the packing nut and externally threaded to fit standard boiler tappings The washers and packing ring are sized to fit a particular capillary diameter Capillary compression fittings are used to replace an immersion well when the sensing bulb of a remote bulb controller requires direct insertion into the controlled medium The fitting seals around the capillary However compression fit...

Page 9: ... must be gradual to pre vent breaks in the tubing and subsequent loss of fill For faster heat transfer use heat conductive compound to fill the space between the bulb and the well A tube of heat conductive compound ships with Honeywell TRADELINE Aquastat Controllers The compound is also available as an accessory See Table 5 Use the following procedure when installing the compound 1 Fill the well w...

Page 10: ...re air at representative temperatures can circulate around it In a plenum application locate the element far enough from the combustion chamber to avoid the effect of direct radiation Bulb Holders 1 Cut a hole large enough to admit the bulb and holder in the duct or plenum at the mounting location 2 Drill holes for the bulb holder mounting screws 3 Mount the bulb and capillary on the holder See Fi...

Page 11: ...et inserted in a hole in the duct wall For ducts with limited access the 7640HX Averaging Element Mounting Kit allows mounting the element through a single hole in the side of the duct This kit requires a length of 1 2 in EMT conduit See Fig 15 Fig 13 Mounting averaging element with perforated strap iron Fig 14 Mounting averaging element with 314439 Mounting Clips Fig 15 Mounting averaging element...

Page 12: ... use either the 105900 Pipe Strap or metal hose clamps The pipe strap fits pipe up to 3 4 in OD External mounting of the sensor produces a slight offset in the temperature control point Typically the control temperature increases as much as 5 F 2 8 C with a bare sensor strapped to the discharge pipe Applying insulation around the sensor and pipe decreases the offset Insulation must be used if larg...

Page 13: ...ving the system through one complete cycle CROSS REFERENCE Some series 121371 Wells are also available without the mounting clamp These pairs are listed together in Table 1 and in Table 7for your convenience The cross reference in Table 8 lists wells and fittings no longer available and suggests functional replacements Table 7 Wells With and Without Mounting Clamp 121371 Part Number With Clamp Par...

Page 14: ...iameter bulb None 122555G Immersion well Copper 3 4 14 NPT 4 1 2 in insulation 5 in insertion dual diameter bulb None 123870E Immersion well Copper 3 4 14 NPT 1 1 2 in insulation 3 in insertion includes plastic sleeve dual diameter capsule 138134E 2 1 4 in insulation 123871D Immersion well Copper 3 4 14 NPT 3 in insulation 3 in insertion includes plastic sleeve dual diameter well 138134E 123871E I...

Page 15: ...IMMERSION WELLS AND COMPRESSION FITTINGS 15 68 0040 04 ...

Page 16: ... Registered Trademark 2008 Honeywell International Inc 68 0040 04 M S Rev 07 08 By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or r...

Reviews: