Mounting and Connection Instructions - Door module RS485
13
3.
Adjust the voltage at the battery terminals by means of the RV2 potentiometer under consideration of the
ambient temperature according to the table below.
Note the battery type!
Warning! Destruction of device possible!
The end-of-charging voltagemust only be modified:
1.
after having exactly measured the temperature
2.
if the battery voltage deviates by >200mV from the nominal value according to the table below
3.4.3
Connection/component mounting diagram
Current drain output
I
12V
= max. 400mA
Current drain PL1 (U
ext
)
U
ext
= 9 - 17,5 V DC
I
ext
= max. 900mA
I
12V
+ I
ext
= < 900mA