38
Mounting and Connection Instructions Door controller module for MB
9.
Start-up
On completion of installation and after switching on the operating voltage, the following must be
programmed in the corresponding functions of the control panel:
Allocation of detector groups, authorization granted, blocking time, possible door release time and
door strike functions. For operating units with keypad, the number of digits of the code, the personal
code itself and a hold-up code can also be defined.
The installation mode is then activated at the control panel so that the addresses of the IK3 operating
units/readers can be allocated.
Cover the screw opening with a VdS seal.
10.
Technical data
Rated operating voltage
12 V DC
Operating voltage range
9 V to 15 V DC
current-limited at 200 mA max.
Current consumption:
-
Module no-load current
< 15 mA (maximum value)
-
GBS terminated with 12k1
+ 1 mA
-
Relay
+ 17 mA
-
Buzzer
+ 3 mA
-
, plus all inputs terminated
plus 1 IK3 reader
Type 25 mA
Detector group inputs:
-
Release contact
3.3 V DC DG, monitored at 12k1±40%
-
Glass breakage sensor
12
Housing dimensions (W x H x D)
118 x 118 x 31 mm
Colour
Traffic white (similar to RAL 9016)
Operating voltage U_BDT for one reader
12 V DC, output short circuit-proof,
Module
V DC DG, monitored at 12k1±30%
-
Bolt switching contact
12 V DC DG, active LOW
-
Cover contact - external reader
3.3 V DC DG, monitored at 12k1±40%
Contact rating of relays
max. 2 A, 30 V AC/DC, 30 VA
Interface to readers
RS-485
Protection category as per EN 60529
IP30
Environmental class as per VdS
II
Operating temperature range
-5 °C to +55 °C