Honeywell Home VisionPRO 8000 Smart Product Data Download Page 2

VISIONPRO® 8000 SMART THERMOSTAT

3

33-00096—05

SPECIFICATIONS

Thermostat Description:

Power Consumption of TH8321:

Backlight on: 1.48 VA
Backlight off: 0.88 VA

Temperature Setting Range:

Heating: 40 to 90 °F (4.5 to 32 °C).
Cooling: 50 to 99 °F (10 to 37 °C).

Temperature Sensor Accuracy:

 ± 1.5 F at 70 F (0.75 C at 21.0 C)

Humidification Setting Range:

10% to 60% RH.

Dehumidification Setting Range:

40% to 80% RH.

Humidity Display Range:

0% to 99%.

Humidity Sensor Accuracy:

 ± 5% RH from 30% to 50% RH at 75 F.

Cool Indication:

VisionPRO® 8000 Smart thermostat displays “Cool On” 

when the thermostat turns the cooling on.

Heat Indication:

VisionPRO® 8000 Smart thermostat displays “Heat On” 

when the thermostat turns the heating on.

Auxiliary Heat Indication:

VisionPRO® 8000 Smart thermostat displays “Aux Heat On” 

when the thermostat turns the auxiliary heat on.

Interstage Differential:

Comfort: The thermostat keeps the indoor temperature 

within 1 degree of the setpoint (droop less control). The 
thermostat turns on stage 2 when the capacity on stage 
1 reaches 90%.

When the interstage differential is set to 1.0 or higher, the 

thermostat stages the equipment based on how far the 
indoor temperature is from the setpoint (ISU 303 to 
309). See page 16 for more information.

Clock Accuracy: 

1 minute per month at 77 °F (25 °C). ± 2 

minutes per month over the operating ambient tem-
perature range.

Mounting Means:

Thermostat mounts directly on the wall in the living space 

using mounting screws and anchors provided. Fits a 
horizontal 2 x 4 in. junction box.

Fig. 1. Dimensions of thermostat in in. (mm).

Feature

Description

Powering method

Common wire

System types (up 
to 3 heat/2 cool 
heat pump and up 
to 2 heat/2 cool 
conventional)

Gas, oil or electric heat with air 
conditioning

Warm air, hot water, high-
efficiency furnaces, heat pumps, 
steam and gravity

Cool only

Changeover

Manual or Auto changeover 
selectable

System setting

Em Heat-Heat-Off-Cool-Auto

Fan setting

Auto-On-Circ-Follow Schedule

Terminal 

Voltage 

(50/60 Hz) 

Max. 

Current 

Rating

W - O/B

18 to 30 VAC and 
750 mVDC

1.00A

Y (cooling)

18 to 30 VAC

1.00A

G (fan)

18 to 30 VAC

0.50A

W2 - Aux 1 (heating)

18 to 30 VAC

0.60A

Y2 (cooling)

18 to 30 VAC

0.60A

A-L/A (Output)

18 to 30 VAC

1.00A

U1, U1, S1, S1

30 VAC max.

0.50A

M34521

4-15/16 (126)

4-5/8

(118)

1-1/8 (29)

3-5/16 (84)