SiXCOMBO-CN 

Combination Smoke/Carbon Monoxide (CO) Detector / Combinaison de détecteur de fumée/de monoxyde de carbone (CO)

 

 

Before installing this product ensure that the security seal on the packaging is unbroken and the product has not 

been tampered with since leaving the factory. Do not install this product if there are any indications of tampering. If 

there are any signs of tampering the product should be returned to the point of purchase.  It is the responsibility of 

the system owner to ensure that all system components, i.e. devices, panels, wiring etc., are adequately protected 

to avoid tampering of the system that could result in information disclosure, spoofing, and integrity violation.

 

Avant d’installer ce produit, assurez-vous que le sceau de sécurité sur l’emballage soit intact et que le produit n’a pas 

subi de manipulations depuis sa sortie de l’usine. N’installez pas ce produit s’il y a la moindre indication de manipulation. 

En cas de tels signes, le produit devrait être retourné au point de vente. Il en va de la responsabilité du propriétaire de 

système de veiller à ce que tous les éléments du système, soit les dispositifs, les panneaux, le câblage, etc., sont 

adéquatement protégés afin d'éviter toute forme de sabotage portée au système pouvant mener à une divulgation 

d'informations, usurpation et violation de l’intégrité. 

 

Quick Installation Guide

 

 

Guide d'installation Rapide

 

This device is intended for use with Honeywell Home controls that support SiX series 

devices including the SiXCOMBO-CN. Check the control for compatibility with this device. 

This device occupies 3 control panel zones, one zone for each service (smoke detection, 

heat detection, carbon monoxide detection). 

NOTE

: This device must be installed by a qualified technician. 

 

FEATURES 

  Multi-Criteria Sensing: uses four sensing elements to react faster while minimizing 

false alarms: 

  -

 Photoelectric smoke sensor detects airborne smoke particles 

  -

 Carbon Monoxide (CO) sensor detects smoldering fires 

  -

 Infrared (IR) sensor measures ambient light and flame signatures, such as flame flicker 

  -

 Thermal detection monitors for dangerous rise in temperature 

  CO Detector End-of-Life reporting (detector needs replacing) 

  Smoke detector maintenance reporting (detector needs cleaning or replacing) 

  Low Battery Detection 

  One Go / All Go: all smoke/CO detectors in the system programmed as one-go-all-go 

will sound on alarm. 

  Voice announcements (English or French) 

 

See 

Installation Instructions 

(I56-6241-000) – https://mywebtech.honeywellhome.com/) 

and the 

Limitations of Fire Alarm Systems 

Insert

 

(800-15144 12/15), 

System Smoke 

Detectors Application Guide

 (SPAG9101 7/12), and Limitations of Carbon Monoxide 

Detectors (P/N K14670V1 4/8 Rev B).

 

 

 

 

 

 

Ce produit est conçu pour être utilisé avec les panneaux de commande Honeywell Home 

qui prennent en charge les dispositifs de la série SiX, y compris le SiXCOMBO-CN. 

Confirmez la compatibilité des commandes avec ce dispositif. Il occupe 3 zones de 

panneau de commande, une zone pour chaque service (détection de fumée, détection de 

chaleur, détection de monoxyde de carbone). 

REMARQUE

 : ce dispositif doit être installé par un technicien qualifié. 

CARACTÉRISTIQUES 

 

   Capteurs à critères multiples: utilise quatre élément de détection pour réagir plus 

rapidement en réduisant au minimum les fausses alarmes : 

  -

 Capteur photoélectrique détectant la fumée et les particules de fumée en suspension 

  -

 Capteur de monoxyde de carbone (CO) détectant les feux couvants 

  -

 Capteur à infrarouge (IR) mesurant les conditions ambiantes de la lumière et un agent 

ignifuges et de flammes comme un jeu de flammes 

  -

 Détection thermique pour les élévations de température dangereuses 

  Signalement de la fin de vie du détecteur de CO (détecteur devant être remplacé) 

  Signalement qu'un détecteur de fumée/CO à besoin d'entretien (détecteur devant être 

nettoyé ou remplacement) 

  Détection de pile faible 

  Une seule fois pour tout : tous les détecteurs de fumée du système programmés 

comme « Une seule fois pour tout » retentiront. 

  Messages vocaux (français ou anglais) 

 

Voir le

 Guide D’Applications des Détecteurs de fumée du système 

(I56-6241-000 – 

https://mywebtech.honeywell.com/) 

Restrictions de ce système d’alarme de feu

 insert

  

(800-15144FC 12/15) et les Voir le 

Guide D’Applications des Détecteurs de fumée du 

système 

(SPAG9101 7/12). 

 

INDICATEURS À DEL 

Le détecteur de fumée/CO SiXCOMBO-CN est muni d'une DEL multicolore sur le dessus 

de l'unité :   

Verte = Ceci indique un problème de supervision; elle clignote durant la mise sous tension 

et durant le fonctionnement normal de l'unité. 

Ambre = Signal de maintenance et de défectuosités 

Rouge = Condition d'alarme (soit de fumée, soit de CO, ou chauffer) 

Les fenêtres de DEL du côté indiquent les alarmes : rouges = fumée, bleues = CO. 

 

Le circuit d’alarme au monoxyde de carbone de ce dispositif est conçu pour détecter le monoxyde 

de carbone à partir de TOUTE source de combustion. Le circuit d'alarme pour monoxyde de 

carbone de ce dispositif n’est PAS conçu pour détecter la fumée, les incendies ou tout autre gaz. 

AVERTISSEMENT 

:

 

cet article est destiné à une utilisation en intérieur dans des zones 

résidentielles ordinaires. Il n'a pas été conçu pour la mesure de conformité aux normes 

commerciales et industrielles. 

LED INDICATORS

 

The SiXCOMBO-CN Smoke/CO detector has a multi-color top LED:   

Green =   Supervisory indication; blinks during power on, reset, and during normal 

operation 

Amber =  Signal maintenance and trouble events 

Red =   Alarm condition (either Smoke, CO, or Heat) 
Side LED windows indicate alarms:  

Red =  

Smoke or Heat alarm 

Blue = 

CO alarm 

The carbon monoxide alarming circuit of this device is designed to detect carbon monoxide gas 

from ANY source of combustion. The carbon monoxide alarming circuit of this device is NOT 

designed to detect smoke, fire, or any other gases. 

WARNING

: This product is intended for use in ordinary indoor residential areas. It is not 

designed to measure compliance with commercial and industrial standards. 

 

ENROLLMENT

 

ENREGISTREMENT

 

IMPORTANT NOTES:

  

 The Smoke, Heat, and Carbon Monoxide (CO) sensors each have 

unique MAC ID numbers (serial numbers) that are enrolled in 

separate zones. 

 Once enrolled, the device cannot be used with another system until 

it is removed from the current controller. See the 24-hour 

Enrollment Deletion section below or the controller’s instructions. 

 

Enroll the Device Services (Smoke, Heat, CO) 

1. Remove the detector from the base plate (tamper switch must 

be faulted when enrolling) and when prompted: 

2. Pull the battery tab to activate enrollment process (be sure 

batteries are seated properly to avoid a false low battery 

condition). If the battery tab has already been removed and the 

unit is powered up, press either Test switch for less than 3 

seconds to activate the enrollment process. 

3. The device attempts enrollment (green LED flashes about 8 

seconds). If successful, the green LED lights steady for 3 

seconds and the device announces successful enrollment. 

  If the LED does not light steady, enrollment failed. Retry by 

pressing either Test switch for less than 3 seconds. 

  All services (Smoke, Heat, and CO) are automatically enrolled 

in sequential (or next available) zone numbers with the following 

default attributes: 

Zone 

Device Type 

Zone Response Type 

Smoke Det.  Smoke Detector 

Fire No Verification 

Heat Det. 

Heat Sensor 

Fire No Verification 

CO Det. 

Carbon Mono. Det. 

Carbon Monoxide 

 

 

NOTE

: Maintenance and CO End-of-Life are automatically 

enrolled for the respective smoke and CO zones. Upon either of 

these conditions, Contact ID code E386 “Low Maintenance 

Smoke” is sent for the CO zone at End-of-Life and Contact ID 

code E385 “High Maintenance Smoke” is sent for the Smoke 

Zone when dirty. 

 

Supervision

: Detector supervision transmission is factory set 

for 1 minute and is not programmable. 

 

24-Hour Enrollment Deletion 

Use this procedure within 24 hours of initial enrollment to delete 

this device from the controller. This allows reenrollment in a 

specific controller in case enrollment in that controller failed. 

This resets the device to factory default settings and removes 

the communication link data in the controller in which it is 

enrolled. 

1.  Press and hold both the Smoke and CO test switches 

simultaneously until the welcome message announces, 

then release. 

2.  Wait for the green LED to flash rapidly. 

3.  Press and hold both switches again for one second and 

release. 

4.  LED blinks rapidly after 15 seconds, confirming deletion. 

TO SILENCE THE DETECTOR 

Press the test switch. The detector sounds again 

after 5 minutes if the alarm condition continues.

 

 

 

 

Operation Modes / Modes de fonctionnement 

MODE 

Status LED (Top) / 

DEL d’état (sur le 

dessus) 

LED Windows 

(Side)

 

/ Fenêtres 

de DEL (sur le 

côté)

 

Sounder / 

Avertisseur 

sonore 

Speaker

 

/ Haut-

parleur

 

Power Up / 

Mise sous tension 

Blink Green, every  

2 secs/ Un 

clignotement vert à 

toutes les 2 

secondes 

Dark / 

Foncée 

Silent / 

Silencieux 

Voice welcome, 

instructions after first 

time power-up or after 

default 

/ Message vocal de 

bienvenue et 

instructions après la 

première mise sous 

tension ou après une 

remise aux valeurs par 

défaut.

 

Normal (Standby) 

Normal (en veille) 

Single Blink Green  

every 10 sec / 

clignotement vert à 

toutes les 10 

secondes 

Dark / 

Foncée 

Silent / 

Silencieux 

Silent / 

Silencieux 

Smoke Alarm / 

Alarme de fumée 

Blink Red every 10 

secs / clignotement 

en rouge à toutes les 

10 secondes 

Blink Red / 

Clignote en rouge 

Temp-3 / 

Tempo.-3 

“Warning, smoke, 

evacuate”/ 

“Avertissement, fumer, 

évacuer” 

Heat Alarm / 

Alarme de chaleur 

Blink Red every 10    

secs / clignotement 

en rouge à toutes les 

10 secondes 

Blink Red / 

Clignote en rouge 

Temp-3 / 

Tempo.-3 

“Warning, smoke, 

evacuate”/ 

“Avertissement, fumer, 

évacuer 

CO Alarm / Alarme 

de CO 

Blink Red every 10    

secs / clignotement 

en rouge à toutes 

les 10 secondes 

Blink Blue / 

Clignote en bleu 

Temp-4 / 

Tempo.-4 

“Warning, carbón 

monoxide, move to 

fresh air” / Attention, 

monoxyde de carbón, 

passez à l'air frais 

 

 

 

 

 

 

 

 

 

 

 

REMARQUE IMPORTANTE :

 

 Les capteurs de fumées, chaleur et monoxyde de carbone (CO) 

possèdent chacun un numéro d'identification MAC (numéro de série) 

inscrit dans des zones séparées. 

 Une fois enrôlé, le dispositif ne peut pas être utilisé avec un autre 

système avant d'avoir été supprimé du panneau actuel. Consultez la 

section Détection d’enregistrement 24 heures ci-dessous ou les 

instructions du contrôleur. 

Enregistrez les services liés au dispositif (fumée, 

chaleur, CO) 

1. Retirez le détecteur du support de montage (l’interrupteur 

antisabotage doit être mis en défaut au moment de l’enregistrement), 

lorsqu’ invite : 

2.  Tirez sur la languette des piles pour activer le processus 

d’enregistrement (assurez-vous que les piles soient bien installées 

pour éviter une fausse situation de pile faible). Si la languette des 

piles a déjà été retirée et que l’unité est mise sous tension, appuyez 

sur l’un des interrupteurs Test durant au moins 3 secondes pour 

activer le processus d’enregistrement. 

3.  Le dispositif tente de s’enregistrer (la DEL verte clignote durant environ 

8 secondes). S’il y parvient, la DEL verte s'allume en continu durant 

3 secondes et le dispositif annonce le succès de l’enregistrement. 

  Si la DEL ne s’allume pas en continu, l’enregistrement a échoué. 

Réessayez en appuyant sur l’un des interrupteurs Test durant moins 

de 3 secondes. 

  Tous les services (fumée, chaleur et CO) sont automatiquement 

enregistrés par séquence de numéro de zone (ou le suivant 

disponible) avec les paramètres par défaut suivants : 

Zone 

Type de 

dispositive 

Types de réponse de 

zone 

Dét. de fume  Détecteur de fume  Incendie sans verification 

Dét. de 

chaleur 

Détecteur de 

chaleur 

Incendie sans verification 

Dét. de CO  Dét. de mono. de 

carbone Det. 

Monoxyde de carbone 

 

 

REMARQUE 

: l’entretien et la fin de vie CO sont automatiquement 

enregistrés pour les zones de fumée et de CO respectivement. Sur 

l’une ou l’autre de ces conditions, le code ID de contact E386  

« Low Maintenance Smoke » (Faible entretien fumée) est envoyé 

vers la zone CO en fin de vie, et le code ID de contact E385 « High 

Maintenance Smoke » (Entretien élevé fumée) est envoyé lorsque 

la zone « fumée » est sale. 

 

Supervision 

: le paramètre par défaut de la transmission de supervision 

du détecteur est réglé à 1 minute et il n'est pas programmable. 

 

 

Suppression d’enregistrement de 24 heures 

Utilisez cette procédure dans les 24 heures après l’enregistrement 

initial pour supprimer le dispositif du contrôleur. Cela permet de 

réenregistrer dans un contrôleur précis au cas où l’enregistrement 

dans ce contrôleur échoue. Cela rétablit les paramètres par défaut 

définis en usine du dispositif et supprime les données de liaison de 

communication du contrôleur dans lequel le dispositif est inscrit. 

1.  Appuyez et maintenez enfoncés simultanément les deux 

commutateurs d'essai de fumée et de CO jusqu’à ce que le 

message de bienvenue s'affiche, puis relâchez-les. 

2.  Attendez que la DEL verte clignote rapidement. 

3.  Appuyez et maintenez à nouveau les deux commutateurs 

durant une seconde, puis relâchez-les. 

4.  La DEL clignote rapidement après 15 secondes pour confirmer 

la suppression.

 

POUR FAIRE TAIRE LE DÉTECTEUR 

 

Appuyez sur le bouton de test. Le détecteur sonne de nouveau 

après 5 minutes si la condition d'alarme est toujours présente. 

 

MOUNTING

 

After enrolling, verify adequate signal strength with the device in its intended mounting location. Adjust the 

device location and orientation as necessary. 

NOTE: This device should not be located within 5 ft (1.5 m) of any cooking appliance.

 

 

MONTAGE

 

Si l’appareil n’est pas dans son emplacement de montage final lorsqu’il est enrôlé, effectuez des tests Tout ou 

rien (voir les instructions du panneau de commande) pour vérifier que la puissance dusignal est adéquate. Au 

besoin, modifiez l'emplacement ou l'orientation du dispositif. 

REMARQUE : ce dispositif ne doit pas être situé à moins de 1,5 m (5 pi) de tout appareil de cuisson.

 