Shipped on Board:
(1) Shunt in Class A/B position
(Shipped in Class B position, remove shunt for Class A)
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Fire•Lite system control panel (list available from Fire•Lite).
COMPONENTS
Following are descriptions of the MMF-300-10 mounting frameworks. There are
two mounting options for MMF-300-10 modules:
Up to six MMF-300-10 modules can be installed on a CH-6 in
a
•
BB-6 cabinet
One or two MMF-300-10 modules can be installed in a BB-2 cabinet
•
Chassis
The CH-6 chassis is used to mount MMF-300-10 modules in a
BB-6 cabinet. It accommodates up to six MMF-300-10 modules in a single
cabinet row three modules wide and two modules deep.
FIgURE 1. CH-6 CHASSIS:
The BB-2 cabinet has a built-in chassis that will accommodate one or two
MMF-300-10 modules.
BEFORE INSTALLINg
This information is included as a quick reference installation guide. Refer to
the appropriate Fire•Lite control panel installation manual for detailed sys-
tem information. If the modules will be installed in an existing operational
system, inform the operator and local authority that the system will be tempo-
rarily out of service. Disconnect the power to the control panel before install-
ing the modules. This system contains static sensitive components. Always
ground yourself with a proper wrist strap before handling any circuits so that
static charges are removed from the body. The module housing should also
be grounded.
NOTICE: This manual should be left with the owner/user of this equipment.
gENERAL DESCRIPTION
The MMF-300-10 Ten Input Monitor Module is intended for use in an intel-
ligent alarm system. Each monitor module is intended to interface between a
control panel and normally open contact devices, such as pull stations. A com-
mon SLC input is used for all modules, and the initiating device loops share
a common supervisory supply and ground. Otherwise, each monitor operates
independently from the others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the first module
from 01 to 150. The remaining modules are automatically assigned to the next
nine higher addresses. Provisions are included for disabling a maximum of
two unused modules to release the addresses to be used elsewhere. Each mod-
ule also has panel controlled green LED indicators. The panel can cause the
LEDs to blink, latch on, or latch off.
INCLUDED:
(6) 1 x 4 Terminal Blocks (2) 11/4˝ Stand offs (2) Nuts
(4) Machine Screws (3) Shunts
(10) 47k Ohm
End of Line Resistors
F300-20-00
1
I56-1873-005
SPECIFICATIONS
Normal Operating Voltage:
15-32 VDC
Stand-By Current:
3.5 mA
Alarm Current:
55 mA (assumes all six LEDs solid on)
Temperature Range:
32°F to 120°F (0°C to 49°C)
Humidity:
10 to 93% Non-condensing
Dimensions:
6.8˝H x 5.8˝W x 1.25˝D
Accessories:
CH-6 Chassis; BB-6 Cabinet; BB-2 Cabinet
Wire Gauge:
12-18 AWG
Maximum IDC Wiring Resistance:
1500 Ohms
Maximum IDC Voltage:
12 VDC
Maximum IDC Current:
1 mA
MMF-300-10 Ten Input Monitor Module
C0202-00
C0206-00
I56-1873-00
5
INSTALLATION AND MAINTENANCE INSTRUCTIONS