AQUATROL ZONE SYNCHRONIZING INJECTION/MIXING BOILER RESET CONTROLS

69-1990—03

6

TROUBLESHOOTING

Power Disruption 

The AQ252’s system and thermostat (zone settings) 
parameters are stored in non-volatile memory and are 
updated as they change. 

When a power disruption or loss of power occurs, the 
system configuration is retained in memory. 

When power is restored, the AQ252 Control Panel enters 
auto-detection mode, reads its previously-stored settings, 
and initializes all AQUATROL network components 
according to their saved parameters.

POWER DISRUPTION GREATER THAN 4 HOURS

If a power disruption lasts for more than 4 hours, the 
AQ252 will have discharged its internal super capacitor, 
and the DATE and TIME OF DAY settings will need to be 
reset.

Upon restart, the AQ252 displays its clock settings as: 
YEAR = 2008, MONTH = JAN, DATE = 1. The message PLS 
SET DAY/TIME displays. This displayed message 
continues until the DATE and TIME OF DAY are updated.

NOTE:

If the power failure parameter is set to Backlight 
(USER MENU > PREFERENCES/TIME), the LCD 
backlight flashes repeatedly, along with the mes-
sage.

The AQ252 remains permanently in OCCUPIED (or 
Comfort) mode until the DAY and TIME OF DAY are 
updated.

System Status and Error Codes

System status alerts and error messages display on the 
System Status Page. These messages are shown in 
Table 2. 

Table 2. LCD Status Notices and Error Messages.

LCD Display

Parameter

Meaning

A/C MIN. OFF TIME

n/a

The A/C compressor is disabled, because the minimum OFF time has not yet 
elapsed.

A/C MIN. ON TIME

n/a

The A/C compressor is active and the minimum ON time has not yet elapsed.

AUX IN EM. SHUT

n/a

Auxiliary Input's Emergency Shut Down is active.

BOILER:

EM SHUT

Boiler is disabled, because the AQ252 is in Emergency Shut Down mode.

FRZ PROT

Boiler freeze protection activated:

Communication between Control Module and Zoning Module has been lost for 
more than 1 minute
or

Boiler supply temperature is less than 50°F (10°C)

HEAT DHW

Boiler is active to serve DHW.

HEATING

Boiler is active to serve zones.

IDLE

Boiler is not active.

INIT

Boiler contacts (terminals 22 and 23) on the AQ1520, which are connected to the 
boiler's T-T terminals, have been shorted and the boiler is beginning its firing 
sequence.

INST PURG

Boiler is active while the AQ252 is conducting the PURGE operation in the Installer 
Setup.

INSTALL

Boiler is in ready mode during Installer Setup.

PMP EXER

Boiler is disabled while the AQ252 is exercising all pumps and valves connected to 
the AQUATROL network.

POST PURG

Boiler is active with Post Purge operation and is sending the purged water to the 
Boiler (Primary) loop.

PURGE DHW Boiler is active with Post Purge operation and is sending the purged water to the 

DHW tank.

CALL FOR COOL

n/a

At least one zone with a programmable thermostat requires cooling.

CALL FOR DHW

n/a

The DHW requires heat.

CALL FOR HEAT

n/a

At least one zone requires heat.

CWSD ACTIVE

n/a

Zone calls for cooling are not served because CWSD (Cold Weather Shutdown) is in 
progress.

DHW DISABLE

n/a

DHW call is not served because it is disabled.

INJECTION%: xx%

n/a

The variable speed injection pump terminals are active and operating at xx% of full 
speed.

Summary of Contents for AQUATROL AQ252

Page 1: ...icians should service this Control Panel The front cover of the AQ251 Control Panel should not be removed as this will expose the user to potentially dangerous line voltage 120V electricity Congratula...

Page 2: ...alue will decrease increase by pressing these buttons When holding the or button for more than a second the values automatically decrease increase at a faster pace similar to setting the time on a dig...

Page 3: ...dule you must use the or button to change the time 2 The OK button when pressed defaults the time setting to midnight If the active menu item leads to a further sub menu pressing the OK button display...

Page 4: ...n this sub menu are The temperature scale for the display Fahrenheit or Celsius for both the AQ252 control s LCD and the zone thermostats The time display in 12 hour e g 7 00 PM or 24 hour format e g...

Page 5: ...AKE program time for all days the LEAVE program time for all days etc When all four programs have been set select the COPY TO ALL DAYS option This displays the prompt COPY TO ALL DAYS ARE YOU SURE Sel...

Page 6: ...OFF time has not yet elapsed A C MIN ON TIME n a The A C compressor is active and the minimum ON time has not yet elapsed AUX IN EM SHUT n a Auxiliary Input s Emergency Shut Down is active BOILER EM S...

Page 7: ...the return sensor is at or below the minimum return water temperature NO DHW PROBE n a No DHW sensor connected or it is defective NO LINE VOLTAGE n a No line voltage has been detected on the N and L t...

Page 8: ...RETURN PROBE NO SECOND PROBE NO SUPPLY PROBE SHORT CYCLE PROT VALVE INIT WATER READY WWSD ACTIVE SYSTEM STATUS 1 ZONE A 1 ROOM TEMP FLOOR TEMP SETPOINT 70 FLOOR SETPT 70 HEAT COOL STATUS SETBACK 7 SET...

Reviews: