12
69-2005EF—02
INSTALLER’S CONFIGURATION MENU
1.
Remove the thermostat from its base.
2.
Place switch 2 on the back of the thermostat in the up position (Installer mode).
3.
Return the thermostat to its base. The first parameter is displayed.
4.
To modify a parameter, press either of the
▲▼
buttons.
5.
To view the next parameter, briefly press the backlight
button.
6.
To exit the menu, place switch 2 back to its initial position.
The parameters appear in the order shown in the following table.
* The Freeze Protection temperature range is set by the minimum and maximum setpoint
temperatures. For example, if you change the minimum setpoint temperature to 50 °F (10 °C), you
cannot then set the Freeze Protection temperature lower than 50 °F (10 °C).
The parameters in the installer’s configuration menu must be modified by qualified
personnel only. Incorrect settings can result in property damages.
Parameter Default
setting Range
Minimum setpoint temperature
41 °F (5 °C)
41 °F (5 °C) to 100 °F (38 °C)
Maximum setpoint temperature
100 °F (38 °C)
41 °F (5 °C) to 100 °F (38 °C)
Freeze Protection temperature
41 °F (5 °C)
41 °F (5 °C) to 100 °F (38 °C)*
Minimum floor limit
41 °F (5 °C)
41 °F (5 °C) to 100 °F (38 °C)
Maximum floor limit
100 °F (38 °C)
41 °F (5 °C) to 100 °F (38 °C)