49
Start-up
The smoke alarm may only be mounted to the
ceiling. Another type of installation, e.g. side wall
mounting, is not allowed.
5.2.5 Pitched ceiling
When mounting the smoke alarm in attic rooms with
pitched roofs the device must not be installed at the apex
of the roof. If it is to be installed on the pitched roof, it
must be mounted around 1 m below the rooms highest
point or, even better, on a (roof) beam.
Wohnzimmer
- Empfohlener Schutz -
children‘s room
- minimum protection-
bedroom
- minimum protection-
attic
- recommended protection -
Keller
- Empfohlener Schutz-
Esszimmer
- Empfohlener Schutz -
Flur
- Mindestschutz -
corridor
- minimum
protection-
50 cm
50 cm
1 m
The smoke alarm has to be installed horizontally in
any case. Contrary to DIN 14676 4.3.5.4, the instal-
lation on sloping ceilings is not allowed.