holthausen
elektronik GmbH
Electronic Vibration monitoring Unit
ESW
®
-small-Compact
9. Display- and operation- elements
The display and operating elements will be accessible after unscrewing the cover of the
ESW
®
-small-Compact.
Display elements
LED1 yellow flashes Limit value G1 exceeded
or adjust Limit value K1
yellow on
Limit value G1 exceeded longer
than the rise time,
K1 has switched
LED2 red flashes
Limit value G2 exceeded
or adjust Limit value K2
red on
Limit value G1 exceeded longer
than the rise time,
K2 has switched
LED3 green on
Operating voltage “on“
green flashes Self test “active“
or error code signal
Operating elements
P1
Potentiometer for setting Limit value G1
10 bis 100%
P2
Potentiometer for setting Limit value G2
10 bis 100%
S1
Self test inactive
OFF
Self test activated
ON
S2
Analog output corresponds to measured value
OFF
Set-Mode (Analog output corresponds to limit value)
ON
S3
switcher for the choice of the Limit values
Analog output corresponds to adjust Limit value G1
OFF
Analog output corresponds to adjust Limit value G2
ON
S4
Analog output
4 to 20mA
OFF
0 to 20mA
ON
S5, S6
measuring range adjustment (see chapter 11)
J1, J2
ground- adjustment (see chapter 13)
9
LED1 LED2
LED3
P1
P2
J1,J2
On
1 2 3 4 5 6