16.
run
Generator Run - This display shows the gen-set is running. The moving _. _. _. indicates normal
condition.
17.
Sdt
Shutdown Timer - This display shows shutdown timer has started. The timer can be set from 30 to
990 seconds in 30 seconds increments. Default is 120 seconds.
18.
SEt
Set Mode - This display shows set mode is active. To do this, press the
SET
button at the back in
the
OFF
mode. To change the default settings, press and release the
MFB
button to toggle to the
desire parameter. Press and HOLD to change the setting, when the desired value is shown, quickly
release the button. Press and release the
MFB
button again to toggle to the next parameter. 10 seconds
of inactivity and the new value will be burn into the memory. The - - - display is shown when this is
taking place. In case auxiliary supply failure occurs in this stage, the memory burning may not be
complete and you may have to repeat the process.
19.
SFC
Supply Fail Contact - If the supply fail contact setting is ‘1’, then the supply fail timer start when
supply fail contacts closes. If the setting is ‘0’. then the supply fail timer start when supply fail
contacts opens. This give you the flexibility to choose either ‘close contacts’ or ‘open contacts’ to start
20.
SFt
Supply Fail timer - This display shows supply fail timer has started. The timer can be set from 1
to 10 seconds in 1 second increments. Default is 5 seconds.