background image

Thermostat Hardware

•  Thermostat cover
•  Thermostat base
•  Electrical box cover (for a 2” X 4” electrical box).

Mounting Hardware

• 

Two #6 x 1/2” painted screws (secures electrical box 
cover to electrical box).

•  Two #6 x 1” phillips screws (secures Thermostat base to 

electrical box cover).

•  Three Wire nuts (secures stat wiring to field wiring).
•  Two Wall anchors (for direct to wall mounting).

Electrical Mounting

All 906 Series Thermostats – Figure 1

(Miniature & standard sizes)

1.

  Remove Thermostat cover from Thermostat base. (See 

Figure 3.)

2.

  Insert wires from Thermostat base through the 1/2” 

hole in the electrical box cover.

3.

  Wire Thermostat to field Thermostat cable using wire 

nuts. (Color-coded to assure proper connection.)

4.

  Mount electrical box cover to the electrical box with 

two #6 x 1/2” painted head screws. (See Figure 1.)

NOTE

Be sure the Thermostat base is centered on electrical 

box cover. If  incorrectly installed, the Thermostat base 

will not symmetrically align with the electrical box 

cover.

5.

  Attach Thermostat base to electrical box cover with the 

two premounted #6 x 1” phillips screws. Do Not Remove 
nylon shims. The Thermostat base can be mounted with 
less than 1/16” clearance to the electrical box cover.

NOTE

Clearance is required to allow the Thermostat cover to 

snap onto the base.

CAUTION

Thermostat base should be firmly secured to the elec-

trical box cover. Do not over tighten!

6.

  Place Thermostat cover onto Thermostat base, securing 

the left side first, then push right side until it “snaps” 
securely into place.

Description

Direct To Wall Mounting – Figure 2

Miniature size, horizontal Thermostats

906-13 Series:  13AW, 13ADRW, 19CDRW, 19DDRW, 23W, 
and 23ADRW only

1.

  Remove Thermostat cover from Thermostat base. (See 

Figure 3.)

2.

  Wire Thermostat base to field Thermostat cable using 

wire nuts. (Color coded to assure proper connection.)

3.

  Place the Thermostat base on the wall at the proposed 

mounting location. Use the two premounted #6 x 1” 
phillips screws (in the Thermostat base) as a template to 
mark the location for the wall anchoring hole location.

4.

  Drill holes at markings for plastic wall anchors. Do Not 

Remove nylon shims (holding the pre-mounted screws 
in the Thermostat base).

5.

  Install wall anchors. Attach Thermostat base directly 

to the wall with the two premounted #6 x 1” phillips 
screws. Thermostat base will mount with less than 1/16” 
clearance to wall.

6.

  Place Thermostat cover onto Thermostat base, secur-

ing left side first, then push right side until it “snaps” 
securely into place.

Thermostat Release Cover

(Miniature size, horizontal Thermostats) Figure 3.

906-13 Series:  13AW, 13ADRW, 19CDRW, 19DDRW, 23W, 
and 23 ADRW only

NOTE

The Thermostat assembly should be held against a 

solid surface, if  it is not mounted on the wall.

1.

  When facing the Thermostat cover, place a small screw-

driver between the 4th and 5th ribbed openings on the 
right side of the Thermostat cover.

Hoffman

|

Controls

Installation & Operating

||

Instructions

906 Series

Electronic Thermostats