After the SPC-ET has completed its initialisation it should be tested using the filters supplied.  The range 1 filter relates to 
25%, the range 2 filter relates to 50% and the range 3 filter relates to 60%.  Firstly place the no alarm side of the filter in 
front of the SPC-ET for at least one minute this should cause no fire or fault signals, if a fault occurs the amber LED will 
flash once every 3 seconds.  Next place the alarm side of the filter in front of the SPC-ET for at least one minute.   
During this time a fire alarm should occur and the red LED should illuminate continuously, if no alarm occurs, then the 
SPC-ET is not operating as expected. 

 

Fig.5Installation Data 

 

 

Guide Settings 

Allowable Misalignment Angle 

 

Range 

Sensitivity 

Emitter 

± 0.5° (max) 

 

5 ~10 m 

25% (1.25 dB) 

Receiver 

± 1.0° (max) 

 

10 ~ 100 m 

50% (3.01 dB) 

Approved Settings 

The SPC-ET is EN54-12:2002 approved at the 25% and 50% sensitivity settings. 

 

 

 

SPC-ET 

0832-CPR-F0212/13 

13 

EN54-12 Line type smoke detectors 

 
 
 

 

 

 

 
 

 
Hochiki Europe (UK) Ltd 

Grosvenor Road, Gillingham Business Park, 
Gillingham, Kent, ME8 0SA, England Telephone: 
+44(0)1634 260133    Facsimile: +44(0)1634 260132 
Email: [email protected] 
Web: www.hochikieurope.com

 

 
 
 
 

Hochiki Europe (UK) Ltd. reserves the right to alter the 
specification of its products from time to time without notice. 
Although every effort has been made to ensure the accuracy of 
the information contained within this document it is not 
warranted or represented by Hochiki Europe (UK) Ltd. to be a 
complete and up-to-date description.  Please check our web 
site for the latest version of this document.

 

Reviews: