Hochiki SPC-ET Mounting Manuallines Download Page 1

SPC-ET Mounting Guidelines  

Page 1

 

Hochiki Europe (UK) Ltd 

 

2-3-0-796/ISS6/SEPT13 

SPC-ET PHOTOELECTRIC BEAM DETECTOR  
MOUNTING GUIDELINES 

When installing the SPC-ET Beam Detectors, it is important that the following guidelines are adhered to: 

 

Do not mount in locations that are exposed to 
extremely high temperatures or water vapour. 

 

Do not mount SPC-ET within 300mm of any 
obstruction. 

 

Do not mount where the distance between the 
Emitter and Receiver is less than 5 metres or greater 
than 100 metres. 

 

Make sure the surface that the SPC-ET units are to 
be mounted on is rigid (ideally part of the building 
structure) to avoid any possibility of movement. 

 

When fixing the SPC-ET allow enough space to gain 
access to the sight hole for aligning purposes (this is 
located on the top right hand side of the Receiver 
unit, when viewed from the front). 

List of Parts 

The SPC-ET Beam Detector kit consists of three separate parts: - 

 

SPC-ET Receiver and Emitter. 

 

SPC-ET Receiver and Emitter interface kit (including 2 way and 10 way ribbon cables). 

 

Test Filters (25%, 50% and 60%) 

– located in packaging – DO NOT DISCARD. 

Mounting the SPC-ET Beam Detector (c/w SPC-ET 2WI Interface Kit)  

The SPC-ET Beam Detectors are designed to mount vertically onto Dual Gang back boxes (suggested type is Appleby 
AL5136).  These boxes should be fixed securely to the wall and directly opposite each other, they must also be mounted 
the same distance from the ceiling at each end. 

Wiring and Set Up 

There are three main wiring methods available for the SPC-ET Beam Detector depending on the application.  These are 
shown below.  In all methods, cables should be brought through the top of the back box, and terminated into the 
appropriate connector blocks. 

 

Method One 

The Receiver is wired 
directly to the zone from 
the conventional panel.  
The Emitter is powered 
by a separate power 
supply. 
 

 

Method Two 

The Receiver is wired 
directly to the zone from 
the conventional panel 
and the Emitter is also 
powered via the 
conventional zone*

1

 

Method Three 

The Receiver is wired 
directly to the loop from 
the analogue panel via a 
CHQ-SZM Single Zone 
Monitor*

2

.  The Emitter 

is powered by a 
separate power supply, 
but can also be powered 
directly from the ESP 
loop if required. 

Fig.1 