Hochiki IFD-E(Exd) User Manual Download Page 7

Hochiki Europe (UK) Ltd 

 

 

 

 

 

2-3-0-810/ISS3/SEP14 

System Design 

Engineers familiar with codes of practice for hazardous area systems should only undertake the design of 
an flameproof fire detection system. In Europe the standard is EN 60079-0 (formally EN 50014), Electrical 
apparatus for potentially explosive atmospheres 

– General requirements.  

The fire detector performance is the same as the standard none flameproof counterparts. Performance 
information given in standard product guides is therefore applicable to the flameproof range. 

The ISSeP certification of the flameproof device enclosure covers their characteristics as components of 
a flameproof system. This indicates that the flame detectors can be used with a margin of safety in such 
systems. 

Service & Repairs 

Frequent inspection should be made. A schedule for the maintenance check should be determined by the 
environment and frequency of use but should be regular enough to ensure the detector continues to 
operate in the designed manner. It is recommended that it should be at least once a year. 

1.  External surfaces of the enclosure should be periodically cleaned to ensure dust deposits are not 

allowed to accumulate. 

2.  Check flamepath/threads on enclosure body and lid for signs of corrosion. If badly pitted, replace 

component.  

3.  All components that are replaced must be in accordance with the manufactures specification. 

Failure to use such components may invalidate the certication/approval on the enclosure and 
may make the enclosure dangerous. 

4.  After inspection and maintenance have been carried out, items 3 & 4 of the installation 

instructions should be adhered to when resealing the enclosure. 

5.  Servicing of the fire protection system should be carried out as recommended by the local 

regulation in force. 

Selection of Cable Glands

 

Application of barrier glands certified and approved to meet EN 60079-14 for Thermo Plastic, 
Thermosetting and Elastomeric Cables. 

 

Hazardous Area Type 

Gland Method 

1) 

Zone 1, 2 21 & 22 Hazardous areas 
requiring IIC apparatus 

EExd Barrier Glands 
mandatory 

2) 

Zone 2 & 22 Hazardous areas requiring IIA 
& IIB apparatus. 

Any EExd Gland 
permitted 

 

Table 5 Examples of barrier glands 

 

Summary of Contents for IFD-E(Exd)

Page 1: ...IFD E Exd Explosion Proof Flame Detector User Manual...

Page 2: ...vapour is or may be present intermittently or as a result of an accident These are defined as hazardous areas by EN 60079 0 formally EN 50014 Electrical apparatus for explosive gas atmospheres General...

Page 3: ...usceptible to fire damp Group II Electrical apparatus for places with a potentially explosive atmosphere other than mines susceptible to fire damp These flame detectors are designed to meet the requir...

Page 4: ...level of protection in which explosive atmosphere mixture of air and gases vapours or mist are likely to occur 1 3 normal level of protection in which explosive atmosphere mixtures of air and gases v...

Page 5: ...re approved IIC for listed gases in EN 50014 Table 4 Subdivisions of Group II Gases Temperature Class Referred to ambient of 20 C to 40 C Maximum Surface Temperature T6 85 C T5 100 C T4 135 C T3 200 C...

Page 6: ...sources by responding only to low frequency flickering produced by flames typically 1 to 15Hz The detectors ignore fixed light sources and rapidly flickering illumination predominantly produced by li...

Page 7: ...esigned manner It is recommended that it should be at least once a year 1 External surfaces of the enclosure should be periodically cleaned to ensure dust deposits are not allowed to accumulate 2 Chec...

Page 8: ...damage during installation Any such damage can destroy the validity of the enclosure 3 Before the cover is refitted the flame path threaded joint between cover and body must be thoroughly wiped clean...

Page 9: ...Hochiki Europe UK Ltd 9 2 3 0 810 ISS3 SEP14 Enclosure with Front Cover Removed...

Page 10: ...onal installation requirements for example to EN 60079 14 NOTE 4 If required a loading resistor or end of line device EOL can be connected between the detector terminals of any circuit The total power...

Page 11: ...Hochiki Europe UK Ltd 11 2 3 0 810 ISS3 SEP14 Hochiki CHQ Module Connection Information Fig 10 Connection Diagram using a CHQ SZM Single Zone Monitor or CHQ MZ...

Page 12: ...12 Hochiki Europe UK Ltd 2 3 0 810 ISS3 SEP14 Fig 11 Connection Diagram using a CHQ DIM Dual Input Module or CHQ S...

Page 13: ...Hochiki Europe UK Ltd 13 2 3 0 810 ISS3 SEP14 Fig 12 Connection Diagram using a CHQ POM Powered Output Module NOTE The CHQ POM has a variable output this should be set at 30mA...

Page 14: ...14 Hochiki Europe UK Ltd 2 3 0 810 ISS3 SEP14 Fig 13 Connection Diagram using a CHQ DZM Dual Zone Monitor or CHQ Z...

Page 15: ...l sales hochikieurope com Web www hochikieurope com Hochiki Europe UK Ltd reserves the right to alter the specification of its products from time to time without notice Although every effort has been...

Reviews: