Hochiki FN-1024X-220 Installation Manual Download Page 5

- 5 - 

 

Battery Size Calculation Worksheet: 

 

A.   FN-1024X-220 internal current consumption (stand-by) 

  

  0.05 A 

 

B.  Load current consumption 

(stand-by) 

  

  A 

C.  Stand-by time required (hours) 

 

  

  H 

D.  Battery capacity required for standby 

(A+B)*C 

  

  AH 

E.  FN-1024X-220 series internal power consumption  (Alarm) 

  

  0.05 A 

F.  Load current consumption 

(Alarm) 

  

  A 

G.  Alarm duration (Hours; 15 Min = 0.25 Hour) 

(Alarm) 

  

  H 

H.  Battery capacity required for Alarm 

(E+F)*G 

  

  AH 

I.  Total calculated battery capacity 

D+H 

  

  AH 

J.  Battery capacity required 

I*1.8 (safety factor) 

  

  AH 

 

 

Note: 

FN-1024X-220 power supply is designed to work with batteries up to 65AH. Please note, line [I] must 

not exceeds 36AH. You have to reduce either standby current consumption or standby time in order to comply 

with requirement. 

 

To determine actual battery size please round line [J] to the nearest larger standard battery size 

(e.g. 3.5 AH = 4.0 AH). 